NetSafety Rack-Mount Fire Controller Owner's manual

Type
Owner's manual
ISO
9001
Certified Company
MODEL #: R1F, R2F & R4F-UV and UVC120
ULTRAVIOLET FIRE DETECTION SYSTEM
1, 2 and 4 Channel Rack Mount Controller
with the UVC120 Detector
Part Number: MAN-0025-00 Rev 2
November 2003
Copyright © 20032 Net Safety Monitoring Inc.
Printed in Canada
This manual is provided for informational purposes only. Although the information contained in
this manual is believed to be accurate, it could include technical inaccuracies or typographical
errors. Changes are, therefore, periodically made to the information within this document and
incorporated without notice into subsequent revisions of the manual. Net Safety Monitoring Inc.
assumes no responsibility for any errors that may be contained within this manual.
This manual is a guide for the use of a 1, 2 and 4 Channel Rack Mount Controller and the data
and procedures contained within this document have been verified and are believed to be
adequate for the intended use of the controller. If the controller or procedures are used for
purposes other than as described in the manual without receiving prior confirmation of validity or
suitability, Net Safety Monitoring Inc. does not guarantee the results and assumes no obligation
or liability.
No part of this manual may be copied, disseminated or distributed without the express written
consent of Net Safety Monitoring Inc.
Net Safety Monitoring Inc. products, are carefully designed and manufactured from high quality
components and can be expected to provide many years of trouble free service. Each product is
thoroughly tested, inspected and calibrated prior to shipment. Failures can occur which are
beyond the control of the manufacturer. Failures can be minimized by adhering to the operating
and maintenance instructions herein. Where the absolute greatest of reliability is required,
redundancy should be designed into the system.
Net Safety Monitoring Inc., warrants its sensors and detectors against defective parts and
workmanship for a period of 24 months from date of purchase and other electronic assemblies
for 36 months from date of purchase.
No other warranties or liability, expressed or implied, will be honoured by Net Safety Monitoring
INC
Contact Net Safety Monitoring Inc. or an authorized distributor for details.
Table of Contents
Unit I GENERAL INFORMATION .................................- 1 -
DESCRIPTION .......................................................... - 1 -
FEATURES............................................................. - 1 -
CONTROLLER SPECIFICATIONS ........................................... - 1 -
Figure 1 - Controller Dimensions....................................... - 2 -
DETECTOR SPECIFICATIONS ............................................. - 3 -
Figure 2b - Swivel Mount Dimensions ................................... - 3 -
Figure 2a - Detector Dimensions....................................... - 3 -
BASIC OPERATION - CONTROLLER ........................................ - 4 -
Figure 3 - Controller
Face-Plate ................................................. - 4 -
CONTROLLER FACEPLATE DESCRIPTION............................. - 4 -
OUTPUTS ....................................................... - 4 -
Table 1 - Selectable Output Options .................................... - 5 -
Figure 4 - Jumper Selections for an Isolated or Non-isolated Current Output...... - 5 -
PROGRAMMING OPTIONS.......................................... - 5 -
EXTERNAL RESET ................................................ - 6 -
AUTOMATIC DIAGNOSTICS AND FAULT IDENTIFICATION ................ - 6 -
VOTING LOGIC (not applicable to R1F)................................. - 6 -
DETECTOR ............................................................ - 6 -
Unit II UV FIRE DETECTION.....................................- 7 -
SYSTEM APPLICATION ................................................... - 7 -
DETECTOR SENSITIVITY ................................................. - 7 -
SPECTRAL SENSITIVITY RANGE ..................................... - 7 -
Figure 5 - Various Spectral Distributions ................................. - 7 -
CONE OF VISION ................................................. - 9 -
Figure 6 - Detector Cone of Vision ..................................... - 9 -
SYSTEM SENSITIVITY .................................................... - 9 -
Unit III SYSTEM INSTALLATION .................................- 9 -
INSTALLATION.......................................................... - 9 -
GENERAL WIRING REQUIREMENTS.................................. - 9 -
CONTROLLER WIRING............................................ - 10 -
Figure 7a - Wiring for R1F with Non-Isolated Current Output................. - 11 -
Figure 7b - Wiring for R1F with Isolated Current Output .................... - 12 -
Figure 8a - Wiring for R2F with Non-Isolated Current Output................. - 13 -
Figure 8b - Wiring for R2F with Isolated Current Output .................... - 13 -
Figure 9a - Wiring for R4F with Non-Isolated Current Output................. - 14 -
Figure 9b - Wiring for R4F with Isolated Current Output .................... - 16 -
POSITION AND DENSITY OF DETECTORS .................................. - 17 -
MOUNTING THE DETECTOR ....................................... - 17 -
Figure 10 - Detector with Swivel Mount Assembly ........................ - 17 -
DIP SWITCH SETTINGS ................................................. - 17 -
Figure 11a - Relay and Dip Switch Positions ............................. - 18 -
Figure 11b - Dip Switch ............................................ - 18 -
CHANNEL SELECTION ............................................ - 18 -
CONTROLLER SENSITIVITY ADJUSTMENT ........................... - 18 -
FIRE AREA VOTING SEQUENCE (not applicable to R1F).................. - 19 -
RELAY OUTPUTS LATCHING/NON-LATCHING ......................... - 19 -
RELAY OUTPUTS ENERGIZED/DE-ENERGIZED........................ - 19 -
TIME DELAY FOR AREA ALARMS ................................... - 20 -
RELAY SETTINGS ...................................................... - 20 -
Figure 11c - Relay Settings.......................................... - 20 -
Unit IV SYSTEM OPERATION .................................. - 21 -
SYSTEM OPERATION ....................................................- 21 -
STARTUP PROCEDURE ............................................- 21 -
CHECKOUT PROCEDURE ..........................................- 21 -
MANUAL vi CHECK/COUNT TEST ....................................- 21 -
MANUAL CHECK PROCEDURE ......................................- 22 -
ALTERNATE TEST PROCEDURE .....................................- 22 -
NORMAL OPERATION ...................................................- 23 -
FIRE RESPONSE .................................................- 23 -
Table 2 - Current Outputs............................................- 24 -
AUTOMATIC DIAGNOSTICS AND FAULT IDENTIFICATION ................- 24 -
Table 3 - Error Codes ...............................................- 25 -
MAIN MENU............................................................- 26 -
ERROR CHECK MODE (Err Chc) .....................................- 26 -
BYPASS MODE (bPS) ..............................................- 26 -
SPECIAL FUNCTION MENU ...............................................- 26 -
FORCED CURRENT OUTPUT MODE (FoP) .............................- 27 -
CURRENT CALIBRATION MODE (CuC) ................................- 27 -
ADDRESS SET MODE (do not use) ....................................- 27 -
Unit V MAINTENANCE ....................................... - 28 -
ROUTINE MAINTENANCE.................................................- 28 -
TROUBLESHOOTING ....................................................- 28 -
DEVICE REPAIR AND RETURN ............................................- 29 -
Appendix A Net Safety Monitoring Inc. Electrostatic Sensitive Device
Handling Procedure..............................................i
Appendix B Record Of Dip Switch Settings ......................... ii
Appendix C Common Ultra-Violet Absorbing Gases ..................iii
Appendix D Wire Resistance In Ohms..............................iv
- 1 -
Unit I GENERAL INFORMATION
DESCRIPTION
The UVC120 Flame Detectors combined with the R1F, R2F or R4F-UV Fire Controller provide
fast, reliable flame detection in a wide variety of applications. The microprocessor based
controllers simultaneously monitor up to four ultraviolet (UV) detectors to provide maximum
operating flexibility at minimum expense. The Automatic Visual Integrity (vi) feature provides a
continuous check of optical surfaces, sensitivity and electronic circuitry of the detector/controller
system. Automatic fault identification monitors system operation and provides a digital display of
system status using a numerical code. Controller response includes actuation of relays for direct
control of field response devices and a full array of faceplate indicators. Other features include
individual channel and area identification, "voting" capability and manual vi testing.
FEATURES
Instantaneous response to ultraviolet radiation
Automatic and manual Visual Integrity (vi) testing
Adjustable sensitivity and time delay
All automatic test functions performed with the system on line
Automatic fault identification
Individual channel identification with voting options
Latching Area LEDs identify the area responding to fire
Microprocessor-based controller is easily field-programmable
Two digital displays, one bar graph display and high intensity LEDs indicate
system status information
Relay outputs are field adjustable as latching or non-latching
Alarm relays are programmable for normally energized or de-energized
operation
Individual detector output (count rate) can be visually monitored on the digital
display
Two 4-20mA current outputs (R2F and R4F). One 4-20mA output on R1F
Conduit seals recommended to prevent moisture damage but not required
CONTROLLER SPECIFICATIONS
Operating Voltage:
24 Volts DC nominal. 18 to 32Vdc.
Power Consumption (controller only):
2.4 watts nominal, 4.4 watts maximum.
100 mA nominal, 180 mA maximum at 24 Volts DC.
Maximum startup current is 1.5 Amperes for 10 milliseconds. Power supplies
with fold back current limiting are not recommended.
Maximum Ripple:
Ripple should not exceed 5 Volts peak-to-peak. The sum of DC plus ripple must
be
18 Vdc and 32 Vdc
Temperature Range:
Operating: -40ºC to +85ºC (-40ºF to +185ºF)
Storage: -55ºC to +150ºC (-65ºF to +302ºF)
- 2 -
Figure 1 - Controller Dimensions
Relay Contacts:
Normally open/normally closed contacts rated for 5 Amperes at 30 Volts DC/ 250
Volts AC
Current Outputs:
4-20mA DC into a maximum external loop resistance of 600 Ohms at 18-32
Volts DC
Dimensions:
Refer to Figure 1
Shipping Weight (approximate):
2 lbs (0.9 kilograms)
Certification:
CSA certified for ordinary, non-hazardous locations
System Sensitivity:
Sensitivity for the standard controller is field adjustable over a range of 8
through 120 counts per second (cps) in increments of 8 cps. The maximum
response distance is achieved at an 8 cps sensitivity setting. For applications
involving high background radiation potential, the system can be de-sensitized
by increasing the count rate required to actuate alarms. The 120 cps setting is
the lowest sensitivity.
Response Time:
Response to a saturating (high intensity) UV source is typically 10 milliseconds
for the instant alarm outputs and 0.5 seconds for the area alarm outputs when
sensitivity is set for 8 cps and time delay is set for 0.5 seconds (minimum
settings)
- 3 -
Figure 2a - Detector Dimensions
0.5"
5.50"
0.25"
2.50"
4.13"
4, 1/4"
holes in
base for
mounting
Figure 2b - Swivel Mount
Dimensions
DETECTOR SPECIFICATIONS
Operating Voltage:
290 Vdc ± 3V (provided from controller)
Power Consumption (each detector):
0.29 Watts nominal, 0.5 Watts maximum
1 mA nominal, 1.7 mA maximum
Temperature Range:
Operating: -40ºC to +125ºC (-40ºF to +257ºF)
Storage: -55ºC to +150ºC (-65ºF to +302ºF)
Dimensions:
Refer to Figures 2a and 2b
Detector Enclosure Materials:
Available in anodized copper-free aluminum or optional stainless steel
Shipping Weight (approximate):
2 lbs (0.9 kilograms)
Certification:
CSA, NRTL/C, NEMA 4X certified for hazardous locations
Class 1, Division 1, Groups B, C and D
IEC approval (Class 1, Zone 1 Groups IIB+H2 T5)
Spectral Sensitivity Range:
The detector responds to UV radiation over the range of 185 to 260 nanometers
(1850 to 2600 angstroms)
Cone of Vision:
The Detector has a nominal 120 degree cone of vision
- 4 -
Figure 3 - Controller
Face-Plate
BASIC OPERATION - CONTROLLER
CONTROLLER FACEPLATE DESCRIPTION
The controller faceplate provides LEDs and two digital displays for
identifying status conditions, a bar graph display for indicating an alarm
condition and MENU/SET and SELECT/RESET push-button switches
for testing and resetting the system. Refer to Figure 3.
Digital Displays - The upper digital display is normally off. If a
fire alarm or visual integrity fault is detected, it indicates the
channel number of the alarm or fault. The digital displays
indicate system status including system error codes, visual
integrity (vi) faults, system faults or fire alarms. The lower
display shows ‘nor’ in normal operating mode. If more than
one channel is in an alarm or fault condition the digital displays
will cycle through these channels. Since at least one display is
always lit they also function as a power indicator.
Bar Graph Display - Normally off. Flashing when fire
detected in any area.
INSTANT LED - (no time delay) Flashes when any detector
signal exceeds the fire sensitivity setting.
AREA 1 & 2 LEDs - (Area 1 only for R1F) If the selected
“voting” criteria of the area and the preset time delay has
elapsed the corresponding LED starts flashing.
FAULT LED - flashes upon detection of an overall system fault
or vi fault.
CHANNEL LEDs - (1, 2 or 4 depending on model) flash to indicate detector in alarm
and remain illuminated until reset, after an alarm condition has returned to normal.
MENU/SET Push-button - is used to enter the main menu, to toggle through menu
selections and in conjunction with the SELECT/RESET push-button to enter the special
functions menu.
SELECT/RESET Push-button - is used for a basic system reset, menu selection and
with the MENU/SET push-button to enter the special functions menu. This switch is
also used during the manual vi test.
OUTPUTS
Relay Outputs:
The Instant, Area and Fault relays have SPDT contacts rated 5 Amps at 30 Volts dc or 250
Volts ac.
The Instant and Area alarm relays are programmable for either normally energized or normally
de-energized operation and for latching or non-latching (programmable as a group not
individually). The fault relay is only normally energized. The relays can be configured with
jumpers for normally open or normally closed contacts.
- 5 -
RECOMMENDATION
The fault relay output should not be used to activate an automatic shutdown procedure.
The fault output indicates a potential problem with the controller, not an alarm condition.
Refer to Table 1 for a summary of the relay programming options.
Table 1 - Selectable Output Options
OUTPUT
Selectable Normally
Open/Closed
Selectable Normally
Energized/De-Energized
Selectable
Latching/Non-Latching
AREA
1
YYY
INSTANT Y Y Y
FAULT Y N
2
N
3
1
Area alarms are programmed together, not individually
2
Fault relay is normally energized
3
Fault relay is non-latching
Current Outputs:
4-20 mA DC current outputs transmit system information to other devices. The current outputs
can be wired for isolated or non-isolated operation by changing the jumpers as shown in
Figure 4. Refer to Unit IV, System Operation for a description of the current output signal levels.
Figure 4 - Jumper Selections for an Isolated or Non-isolated Current
Output
PROGRAMMING OPTIONS
DIP switches located on the circuit board are used to “program” various options including:
channel selection,
system sensitivity,
fire area voting logic,
time delay for fire area alarms,
relay latching/non-latching selection, and
relay energized/de-energized selection.
- 6 -
NOTE
Power to the controller must be cycled to make dip switch changes take effect.
EXTERNAL RESET
A normally open, momentary closure switch connected between the external reset terminal and
the negative power terminal provides remote reset.
AUTOMATIC DIAGNOSTICS AND FAULT IDENTIFICATION
The microprocessor-based controller features self-testing circuitry that continuously checks for
problems that could prevent proper system response. When power is applied, the
microprocessor automatically tests memory. In the Normal Operating Mode it continuously
monitors the system to ensure proper functioning. A "watchdog" timer is maintained to ensure
that the program is running correctly.
The main loop of the operating program continuously cycles through the Automatic Visual
Integrity test, checking each detector and its wiring. The microprocessor can be interrupted by
any one of several status changes such as a fault or a "fire" signal from one of the detection
areas to take appropriate action.
If a system or vi fault is detected the Fault LED flashes, digital displays and current outputs
identify the nature of the fault and the fault relay is de-energized.
VOTING LOGIC (not applicable to R1F)
The controller can be DIP switch configured for either one or two monitoring areas. For a one
area configuration, all channels are considered as being in Area 1 and both Area alarm relays
will be activated together.
The dip switches can be set so that only one channel need be in alarm to activate the area alarm
or any two channels must ‘vote’ (see a fire at the same time) to activate the area alarm. The
instant alarm will be activated when any channel sees UV radiation exceeding the preset
sensitivity setting, no matter what voting option is being used.
For a two area configuration, channel one (one and two for R4F) make up Area 1 and channel
two (three and four for R4F) make up Area 2. With the R4F each Area alarm may be
programmed with different voting criteria (ie. Area 1 may be set so that either channel one OR
channel two may activate the area alarm, and Area 2 may be set so that both channels three
AND four must see the fire at the same time to activate the Area alarm).
DETECTOR
The detector responds to UV radiation over the range of 185 to 260 nanometers. It is not
sensitive to direct or reflected sunlight nor to normal artificial lighting.
The detector is housed in an explosion-proof enclosure that is designed to meet most national
and international standards. It is available in anodized aluminum or optional stainless steel.
The detector is typically mounted with a swivel mounting assembly which is recommended.
Other mounting arrangements are possible.
- 7 -
Unit II UV FIRE DETECTION
SYSTEM APPLICATION
The detector responds instantly to ultraviolet radiation emitted by a flame. It is designed for use
in hazardous locations and is suitable for use in outdoor applications.
Typical applications for UV detection systems are:
around highly combustible materials
if instantaneous response to flame is needed
where automated fire protection is required
to protect large capital investments
Petroleum Products Handling
petroleum loading terminals
offshore platforms
pipeline stations
tank farms
refineries
engine rooms
Gaseous Fuel Handling
butane and propane loading and storage
pipeline compressor stations
gas gathering facilities
LNG loading, transfer and storage
hydrogen
gas turbines
Other Processes
paint spray booths
chemical and petrochemical production
powder coating booths
Automated fire protection systems also have applications in any manufacturing or research
facility where the potential of fire may be low to moderate but the losses due to a fire would be
high.
DETECTOR SENSITIVITY
SPECTRAL SENSITIVITY RANGE
The UV fire detector responds to radiation wavelengths of 185 to 260 nanometers (1850 to 2600
angstroms). Figure 5 illustrates the range of sensitivity and compares this range to other forms
of radiation. Note that UV radiation reaching the earth from the sun does not extend into the
sensitivity range of the detector. Nor does radiation from normal artificial lighting, such as
fluorescent, mercury vapor and incandescent lamps.
- 8 -
Figure 5 - Various Spectral Distributions
NOTE
Some mercury vapor lamps can operate for extended periods with cracked or damaged
envelopes and will then emit UV radiation in the range of the detector. Remove defective
mercury vapor lamps from service.
The UV sensor responds to radiation other than ultraviolet. X-rays can activate the detector and
are often used in industrial inspection. It may be necessary to disable the system if X-ray
inspection is conducted nearby.
UV radiation other than that produced by an actual fire is referred to as “background UV.” An
example of a high level of background UV could be the case of a flare stack situated outside of a
building. The UV radiation produced by this flare may be detected when a door to the building is
opened. Windows or reflective surfaces may also result in unusually high levels of UV radiation
entering the building from the flare. In a situation like this, the fire detection system response
must be carefully checked and the sensitivity level adjusted high enough so that this
“background” UV will not cause false alarms.
Caution must be exercised if the detection system is turned off, since the hazardous area will not
be protected.
NOTE
Ultraviolet detectors are sensitive to arc welding and if this type of radiation can be
expected, nuisance alarms must be controlled through proper application including
careful positioning and shielding of the detectors. Some applications may require a
UV/IR system.
- 9 -
CONE OF VISION
The fire detector has a nominal 120 degree cone of vision. Figure 6 shows the cone of vision
and detector response to a UV source at various distances. The practical application distance is
up to about 50 feet (15 meters). The distance is directly related to the intensity of the ultraviolet
radiation source. Programming the controller to require a high count rate results in low system
sensitivity. Consider that UV absorbing chemical vapors may be present. (See Appendix C)
Figure 6 - Detector Cone of Vision
SYSTEM SENSITIVITY
The UV tube count rate generated by different fires at the same distance is unpredictable.
Generally, if a fire doubles in size the tube response is increased by about 60 percent.
Controller sensitivity and time delay settings for various applications is dependent on the severity
of the hazard and the action required if a fire occurs. The system can be adjusted to various
sensitivity levels by programming the controller to respond at a pre-determined detector count
rate which is dependent upon the intensity of the ultraviolet radiation reaching the detector,
which in turn depends on the type of fuel, temperature, flame size, distance from the detector
and concentration of UV absorbing vapors present.
Programming the controller to respond to a low count rate results in high system sensitivity.
Unit III SYSTEM INSTALLATION
INSTALLATION
GENERAL WIRING REQUIREMENTS
NOTE The wiring procedures in this manual are intended to ensure proper functioning of the
device under normal conditions. However, because of the many variations in wiring
codes and regulations, total compliance to these ordinances cannot be guaranteed. Be
certain that all wiring complies with applicable regulations that relate to the installation of
electrical equipment in a hazardous area. If in doubt, consult a qualified official before
wiring the system.
- 10 -
Shielded cable is highly recommended for power input and signal wires to protect against
interference caused by extraneous electrical 'noise'. Relay outputs do not require shielded cable.
Recommended detector cable is four conductor, shielded cable, 18 AWG, rated 300V. If the
wiring cable is installed in conduit, the conduit must not be used for wiring to other electrical
equipment. Detectors can be located up to 2000 feet (600 meters) from the controller.
Water will damage electronic devices. Moisture in the air can condense within electrical conduit
and drain into the enclosure, therefore, water-proof and explosion-proof conduit seals are
recommended to prevent water accumulation within the enclosure. Seals should be located as
close to the device as possible and not more than 18 inches (46 cm) away. Explosion-proof
installations may require an additional seal where conduit enters a non-hazardous area.
Conform to local wiring codes.
When pouring a seal, use a fibre dam to assure proper formation of the seal. The seals should
never be poured at temperatures below freezing.
The jacket and shielding of the cable should be stripped back to permit the seal to form around
the individual wires. This will prevent air, gas and water leakage through the inside of the shield
and into the enclosure.
It is recommended that explosion-proof drains and conduit breathers be used. In some
applications, alternate changes in temperature and barometric pressure can cause 'breathing'
which allows moist air to enter and circulate inside the conduit. Joints in the conduit system are
seldom tight enough to prevent this 'breathing'.
CONTROLLER WIRING
NOTE
The controller contains semiconductor devices that are susceptible to damage by
electrostatic discharge. An electrostatic charge can build up on the skin and discharge
when an object is touched. Therefore, use caution when handling, taking care not to
touch the terminals or electronic components. For more information on proper handling,
refer to the Appendix.
The controller can be configured for isolated or non-isolated current outputs by changing jumpers
on circuit board as per Figure 4. Figures 7a, 8a, and 9a show the proper wiring for non -isolated
current outputs and Figures 7b, 8b and 9b show wiring for isolated current outputs.
- 11 -
Figure 7a - Wiring for R1F with Non-Isolated Current Output
- 12 -
Figure 7b - Wiring for R1F with Isolated Current Output
- 13 -
Figure 8a - Wiring for R2F with Non-Isolated Current Output
- 14 -
Figure 8b - Wiring for R2F with Isolated Current Output
- 15 -
Figure 9a - Wiring for R4F with Non-Isolated Current Output
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

NetSafety Rack-Mount Fire Controller Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI