MULTISPAN CC-12 Owner's manual

Type
Owner's manual

MULTISPAN CC-12 is a current controller with a range of 0 to 5 Amp AC and a resolution of 0.1A or 1A. It has two relay outputs, each with a contact rating of 10A at 230V AC or 28V DC. The CC-12 can be used to control a variety of loads, such as motors, pumps, and heaters.

The CC-12 has a number of features that make it easy to use and configure. These features include:

  • Time 1: This is a minimum relay off delay, where relay 1 is on for a minimum time when the current reaches the setpoint 1.
  • Time 2: This is a trip delay, if the current value is greater than setpoint 2 for the amount of trip time, then relay 2 is on after the trip time.

MULTISPAN CC-12 is a current controller with a range of 0 to 5 Amp AC and a resolution of 0.1A or 1A. It has two relay outputs, each with a contact rating of 10A at 230V AC or 28V DC. The CC-12 can be used to control a variety of loads, such as motors, pumps, and heaters.

The CC-12 has a number of features that make it easy to use and configure. These features include:

  • Time 1: This is a minimum relay off delay, where relay 1 is on for a minimum time when the current reaches the setpoint 1.
  • Time 2: This is a trip delay, if the current value is greater than setpoint 2 for the amount of trip time, then relay 2 is on after the trip time.
CC-12
INPUT SPECIFICATION:
CURRENT CONTROLLER
DISPLAY AND KEYS:
DIMENSION:
OUTPUT SPECIFICATION:
POWER SUPPLY:
ENVIRONMENT CONDITION:
TIME PARAMETER :
Display
Size
Keys
Panel Cutout
Power
Consuption
(VA Rating)
Relative Humidity
Protection Level
(As per request)
Relay
Supply
Voltage
Operating Temp.
Time 1
Time 2
Relay Type
Rating
Upper: 4 digit, 7 segment, 0.70” White
Lower: 4 digit, 7 segment, 0.50” Green
96 (H) x 96 (W) x 43 (D) mm
100 to 270V AC, 50-60Hz
0°C to 55°C
It is a minimum relay off delay, where
relay 1 is on for minimum time when
Amp. reach to the set 1
It is a trip delay, if Amp. value is greater
than set 2 for the amount of trip time
than relay 2 is on after trip time
UP to 95% RH
(non-condensing)
IP-65 (Front side) As per IS/IEC
60529 : 2001
1 Nos
1C/O (NO-C-NC)
10A, 230V AC / 28V DC
SET, INC, DEC, ENTER/RESET
92 (H) x 92 (W) mm
4VA @ 230V AC MAX
Relay Output
TECHNICAL SPECIFICATION MECHANICAL INSTALLATION
TERMINAL CONNECTION
96
92
92
96
Outline Dimension (mm) Panel Cutout
Dimension (mm)
Primary CT value
Secondary current AC
Resolution
5 to 4000 Selectable
0.5 to 5 Amp AC
0.1A, 1A
SET
CC 12
Amps
Set
Value
Controller
2 01 4
81 00
R
TEST
ENT
RST
Current
43
3
1 2 3 4 78910
56
L N
20 19 18 17 14 13 12 11
16 15
NC CNO
RELAY-1
Made in India
~
50/60 Hz
100
270AC
I/P
0 To 5A AC
www.multispanindia.com
Input :
Range: 5 to 4000 CT SELE
0 to 5 Amp AC
Output: 1R1C/O
Read complete instructions prior to installation
and operation of the unit.
WARNING : Risk of electric shock.
SAFETY PRECAUTION
!
All safety related codifications, symbols and instructions that
appear in this operating manual or on the equipment must be
strictly followed to ensure the safety of the operating personnel
as well as the instrument.
If all the equipment is not handled in a manner specified by
the manufacturer, it might impair the protection provided by the
equipment.
1 - Relay - 1 output indication
Blinking : Time 1(Minimum relay on time) is calculated
STATUS LED DESCRIPTION
KEY OPERATION
To enter in parameter setting
Long press
Long press
To reset the operation
PRESS KEYFUNCTION
OPERATOR MODE
PARAMETER SETTING MODE
To set parameter value
To increment parameter value.
To decrement parameter value.
Set parameter to be save & exit.
WARNING GUIDELINES
WARNING : Risk of electric shock.
1. To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is
being supplied.
2. To reduce electro magnetic interference, use wire with
adequate rating and twists of the same of equal size shall
be made with shortest connection.
3. Cable used for connection to power source, must have a
cross section of 1mm or greater. These wires should have
insulations capacity made of at least 1.5kV.
4. When extending the thermocouple lead wires, always use
thermocouple compensation wires for wiring for the RTD
type, use a wiring material with a small lead resistance
(5 max per line) and no resistance differentials among
three wires should be present.
5. A better anti-noise effect can be expected by using
standard power supply cable for the instrument.
Ω
INSTALLATION GUIDELINES
1. This equipment, being built-in-type, normally becomes a
part of main control panel and in such case the terminals
do not remain accessible to the end user after installation
and internal wiring.
2. Do not allow pieces of metal, wire clippings, or fine metallic
fillings from installation to enter the product or else it may
lead to a safety hazard that may in turn endanger life or
cause electrical shock to the operator.
3. Circuit breaker or mains switch must be installed between
power source and supply terminal to facilitate power ‘ON’
or ‘OFF’ function. However this mains switch or circuit
breaker must be installed at convenient place normally
accessible to the operator.
4. Use and store the instrument within the specified ambient
temperature and humidity ranges as mentioned in this
manual.
MECHANICAL INSTALLATION GUIDELINES
1. Prepare the panel cutout with proper dimensions as shown
above.
2. Fit the unit into the panel with the help of clamp given.
3. The equipment in its installed state must not come in close
proximity to any heating source, caustic vapors, oil steam,
or other unwanted process Byproducts.
4. Use the specified size of crimp terminal (M3.5 screws) to
wire the terminal block. Tightening the screws on the
terminal block using the tightening torque of the range of
1.2 N.m.
5. Do not connect anything to unused terminals.
MAINTENANCE
1. The equipment should be cleaned regularly to avoid blockage
of ventilating parts.
2. Clean the equipment with a clean soft cloth. Do not use
isopropyl alcohol or any other cleaning agent.
3. Fusible resistor must not be replaced by operator.
1
2345
2500
ENT
RST
ENT
RST
PARAMETER SETTING
CORRECTION FACTOR
RELAY CHECK
Set
Hysteresis
0.0 to CT Primary Value
0.1 TO 99.9
DelayTime
000 to 999 Sec
000 to 999 Sec
CT Primary
5 to 4000 AC AMP
Press & key
to set setpoint value
set
1000
HY
0000
Stdt
deLy
0000
0000
CT
MODE
1000
L-AL
Press key
Press key
Press key
Press key
Press key
Press key
Press & key
Press & key
Press & key
Press & key
to set CT Primary Value
Press & key
Press key
Correction Factor
-25.0 to +25.0
CRFC
RELAY
0000
0N
Press & key
Press & key
to set correction
factor value
Press key for to save & exit
Press key for to save & exit
Press key exit
ENT
RST
ENT
RST
ENT
RST
Starting Delay time
(Low Alaram,High Alaram
In Band/ Out Band
Abs. Low/Abs.Out band,)
TEST
5Sec. Press
RELAY
ON-OFF
ON
LOW ALARM:
RLY-ON
RLY-OFF
HYST
S.V
ON
OFF OFF
HIGH ALARM:
RLY-ON
RLY-OFF
S.V
HYST
OFF ON OFF ON
INBAND ALARM
RLY-ON RLY-ON
RLY-ON
RLY-OFF
OFF ON OFF ON ON
Delay
Time
Delay
Time
Delay
Time
Delay
Time
Delay
Time
Delay
Time
Delay
Time
HYST
S.V
CONTROL FUNCTION
OUTBAND ALARM
RLY-ON
RLY-ON
RLY-OFF
RLY-OFF
ON OFF OFF
ON ON ON
ABSOLUTE LOW ALARM
RLY-OFF
RLY-OFF
RLY-ON
RLY-ON
RLY-OFF
S.V
HYST
ON ON
OFF
OFF
ABSOLUTE OUTBAND ALARM
RLY-ON
RLY-ON
RLY-OFF
RLY-ON
RLY-OFF
RLY-OFF
ON ON
OFF
Delay
Time
OFF
Delay
Time
Delay
Time
Delay
Time
Delay
Time
Delay
Time
OFF
HYST
S.V
S.V
HYST
CONTROL FUNCTION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

MULTISPAN CC-12 Owner's manual

Type
Owner's manual

MULTISPAN CC-12 is a current controller with a range of 0 to 5 Amp AC and a resolution of 0.1A or 1A. It has two relay outputs, each with a contact rating of 10A at 230V AC or 28V DC. The CC-12 can be used to control a variety of loads, such as motors, pumps, and heaters.

The CC-12 has a number of features that make it easy to use and configure. These features include:

  • Time 1: This is a minimum relay off delay, where relay 1 is on for a minimum time when the current reaches the setpoint 1.
  • Time 2: This is a trip delay, if the current value is greater than setpoint 2 for the amount of trip time, then relay 2 is on after the trip time.