For more information view the latest User or Service manuals on GSPN. If you have any questions please
raise them via the Subsidiary Technical Support
Page 5 of 5
Make sure to change the installation option code #Seg5 for centralized
control prior to tracking of the Wi-Fi kit. If the W-Fi kit is installed prior to
doing this it needs to be tracked again, by pressing SW3 inside the Wi-Fi
kit shortly. (Holding SW3 down for over 5 seconds and releasing sets it
back to factory default). Do not set any RMC- addresses for a single
system or when the same user is to control all units in the same system.
Complete the set up by following instructions in the Smart Home App.
External contact interface MIM-B14 is connected as shown in the picture
below. Installation option codes #Seg14 and 15 set depending on functions
wanted. By using the holder without lid following MIM-B14 it can be fitted
on the inside of the lower cover.