Cumberland Ammonia Sensor Owner's manual

Type
Owner's manual
REV 01
QSG 891-00588 REV01
NOTE: Please scan the QR Code to access the electronic version of Installation Guide
or visit the website:
Cumberland: http://www.cumberlandpoultry.com
AP: http://www.automatedproduction.com
GSI Electronics Inc.
5200 Armand Frappier Saint-Hubert, Qc
Canada J3Z 1G5
Phone: 1-877-926-2777
Ammonia Sensor
Only properly trained service personnel may perform installation and service
procedures. (In other words: electricians, service personnel employed by or active
in an organization, business, or service).
All power sources must be disconnected prior to wiring and installing.
Electrostatic discharge (ESD) can damage equipment and impair electrical
circuitry. ESD damage occurs when electronic components are improperly
handled and can result in complete or intermittent failures.
Warranty is void if the Legacy Connect is used in a manner not specied by the
manufacturer.
3 - NOTICES
Functional Ground Terminal. Primarily used for functional earth
terminals which are generally associated with test and measurement
circuits. These terminals are not for safety earthing purposes but provide
an earth reference point.
Protective Earth Ground Terminal. Primarily used for protective earth
terminals. These terminals connect to conductive parts of a device for
the purpose of safety and is intended to be connected to an external
system for protective grounding.
WARNING: Read the following text carefully; it contains important
information which, if ignored, may cause the controller to operate
improperly.
High Voltage. Hazard of electrical shock.
4 - SYMBOLS
EN
ADO824642
Cumberland
AP
Continuous monitoring of ammonia level is now possible with your EDGE system.
The Ammonia Sensor kit includes a signal converter that must be wired between
the output of the sensor and the input of your EDGE system; requires EDGE software
version 2.5 or higher.
For optimum measurements, the sensor should be installed at the center of the
area to be monitored and out-of-reach of animals using the lug at the end of the
housing. It must not be mounted near the fresh air supply, in front of windows or
doors, inlets or exhaust ducts. Protect against direct exposure to dust or splash
water. The sensor must be mounted vertically with the sensor pointing down; ±30°
at a location with low vibration and, as much as possible, stable temperatures.
1 - INTRODUCTION
The sensor contains caustic liquid. Avoid contact with eyes and skin;
rinse thoroughly with water if contact occurs and seek medical help
if required.
2 - ORDERING INFORMATION
GSIE Part
Number
GSI Part
Number Description Lbs Kgs
028-00676 EDG-169 Ammonia Sensor Kit 4.22 1.91
Service Parts
832-00179 EDG-151 Ammonia Sensor 2.79 1.27
028-00655 EDG-168 Voltage Converter Assembly 1.44 0.65
832-00175 EDG-165 Sensor Head - 3 year Shelf Life 0.33 0.15
832-00176 EDG-166 Dust Filter - 5 pcs. 0.08 0.04
Cartridge
Shelf Life
Blinking LED pattern
below indicates service
life has expired.
1. Select the Setup Icon.
2. Select the room you wish to add the alarm to.
3. At the bottom of the page select the Alarm button.
4. Select Generic Input.
5. Select the sensor you want to add the alarm to.
6. Select Use low alarm and/or Use high alarm and enter the specic alarm
threshold you want.
7. Adjust the Recognition time.
8. Select Main alarm relay if you would like this alarm to trigger the alarm system.
9. If congured, the system can trigger an EDGE Alarm relay to perform a
secondary function that responds to the alarm. An example of this might be
closing a relay to start fans based on the high alarm threshold.
7 - CONFIGURING EDGE SOFTWARE ALARMS FOR AMMONIA
SENSOR
5 - WIRING DIAGRAM
NOTES:
If a cables with shields are used, twist both shields from each cable together and use a marrette (twist-on wire connector) to secure the connection.
Make sure that the shield does not touch any other bare wire and the resistor.
AP/Cumberland recommends to add a heat shrink on it.
The maximum diameter of the cable must be less than 6.5 mm.
Cable glands must be correctly tightened to guarantee the sealing of the junction box.
Use the 4 screws included in the kit to close the cover on the junction box.
The wire color used in this drawing is only for reference, it can be dierent on the sensor.
Maximum volts should be set to 3.6V in the EDGE conguration page.
0-10V to 0-3.6V Converter Wiring Diagram
with EDG-151 or 832-00179 Ammonia Probe
R=6.8K
0-10V SENSOR CABLE
EDGE INPUT CABLE
Equivalent Circuit
White - 24V
Brown - OUT+
Green - GND
24V
GND
24V
IN+
GND
GND
24V+
GND
24V+
GND
IN
GND
IN
GND
IN
GND
IN
EDGE Expansion
Box
(EDG-168 or 028-00655)
Signal Convertor
(EDG-151 or
832-00179)
Ammonia Sensor
0-10V Sensor Cable
EDGE INPUT CABLE
R=6.8K
1. Select the Equipment Congifuration Icon.
2. Select the room you wish to add the equipment to.
3. Scroll down and select Generic Input.
4. Select the Add or Copy equipment button.
5. Name the Sensor as you choose and then select the Signal Type, Units and
Precision as shown below.
6. Adjust the Max Value from 5.00V to 3.60V.
6 - CONFIGURING EDGE SOFTWARE FOR AMMONIA SENSOR
NOTE: To complete these steps, you must have Setup Privileges.
NOTE: The Expansion Box, Slot and Input are site-specic and determined by where
the sensor wiring is landed.
7. Select the Home Screen Icon.
8. Scroll to the room you added the equipment to and select the generic
input tile.
9. Select the sensor and check the “Show on tile”. Up to 3 inputs can be shown on a
tile per room.
  • Page 1 1
  • Page 2 2

Cumberland Ammonia Sensor Owner's manual

Type
Owner's manual