Installation Instructions Section 2
2-10
Part Number 11324 2/08
4. Compare the measured stagger to the stagger
dimension on the blueprint.
NOTE: The stagger dimension on the blueprint is always
a multiple of 11-1/2" (11-1/2", 23", 34-1/2").
5. If the measured stagger is not long enough, loosen
the top wall panel Posi-Locs on the adjacent two
panels. Allow the gasket in the seam to push the two
wall panels apart until the measured stagger
matches the stagger dimension on the blueprint.
6. Engage the Posi-Loc on the ceiling panel at the
stagger end to lock it to the wall panel.
7. Posi-Loc the wall panels together again.
8. Engage all remaining Posi-Locs on the ceiling panel
to lock it to the wall panels.
9. Repeat this process throughout the installation until
all of the ceiling panels are installed.
Multi-Compartment Structures
The procedure for multi-compartment structures is the
same as the procedure for single compartment
structures, except that ceiling construction must begin
over the partition wall. Add ceiling panels in both
directions from the first panels, measuring stagger in
each direction as panels are added.
Finishing Work
DOOR THRESHOLD INSTALLATION
Refer to the Special Installation Instruction Sheet
enclosed with your installation materials for information
on your specific installation.
THERMOMETER BULB INSTALLATION
A coiled length of lead wire with a thermometer bulb is
located on the inside of the door frame panel. Uncoil the
wire. Using the plastic clip and screw provided, fasten
the bulb to a wall panel located away from the door
frame panel, at 42" above the floor.
PANEL PENETRATIONS
In some cases, it will be necessary to penetrate the
walk-in to run electrical and refrigeration lines. When
making a penetration, be careful to avoid panel seams
and Posi-Locs.
Area to Avoid When Making Panel Penetrations
To make a penetration into the walk-in:
1. Determine the exact location and size of the hole
needed.
2. Mark the location and the size on the outside and
inside of the walk-in.
3. Use a drill to make the penetration if a drill bit of the
correct size is available. For holes too large to drill,
use metal shears to cut the panel skin.
4. After making the penetration, carefully remove any
insulation from the hole.
Do not locate the thermometer bulb on the door
frame panel. The thermometer will display a false
reading due to the heater wires in the door jamb,
and warm air entering the walk-in when the door is
opened.
Ceiling penetration may only be made on indoor
walk-ins. Do not make ceiling penetrations on
outdoor walk-ins. Water damage from rain in the
walk-in and/or inside the ceiling panel may result.