Siemens FC901-R3 Control Panel is a compact and powerful standalone fire alarm control panel. It features advanced addressable fire detection, keypad and offline programming, notification circuits, a 160 by 64 dots LCD display, and event history retention capability. Its typical configuration includes a power supply, a signaling addressable device circuit, two notification appliance circuits (NAC), Digital Alarm Communication Transmitter (DACT), four system status relays, and a USB programming port. All the components are mounted in an 18.1" x 16.5" enclosure.

Siemens FC901-R3 Control Panel is a compact and powerful standalone fire alarm control panel. It features advanced addressable fire detection, keypad and offline programming, notification circuits, a 160 by 64 dots LCD display, and event history retention capability. Its typical configuration includes a power supply, a signaling addressable device circuit, two notification appliance circuits (NAC), Digital Alarm Communication Transmitter (DACT), four system status relays, and a USB programming port. All the components are mounted in an 18.1" x 16.5" enclosure.

Building Technologies
Fire safety and security products
FC901-U3 FC901-R3
Specification
One addressable Signaling Line Circuit (SLC) which can be configured as one
Class A Style 6 or 7 or two Class B style 4
50 addressable point capacity system
Powerful, easy-to-use programming capabilities
Fully Field Programmable Via Windows Laptop Computer or by the FACP directly
160×64 dots LCD display
Extremely User-friendly system interface
Universal AC power input - 120/240VAC, 50/60Hz
6.5 amps of system power
Numerous Relays - alarm, trouble, supervisory, programmable…
Polarity insensitive detection circuits(Patented)
Support one Class A or two Class B SLC
Supports FirePrint application specific detection
Detector Sensitivity Readout/Printout per NFPA 72
32 Character Custom messages
Multiple Command Stations
1000 Event History Logging with On Line & Off Line Reports
Multiple Levels of Password Protection
Alarm verification by Device or Zone
firealarmresources.com
2
Building Technologies A6V10343700__en_--
Fire safety and security products 09.2011
Silence inhibit timer
Auto silence timer supported
Logic Controlled Output Functions
City Tie/Leased Line
Built-in DACT (digital alarm communicator transmitter)
Support two Notification Appliance Circuits (NACs) rated at 2.5 amps with up to 2.5
amps (24VDC) per NAC
Two NAC can be configured as style Y(class B) or style Z (class A)
Built-in strobe synchronization protocol
Supports Pre-signal and PAS
Supports Single Person Quick Test
USB interface for local upload/download
Introduction
The FC901 is a compact but powerful standalone fire alarm control panel. It features
advanced addressable fire detection, keypad and offline programming, notification circuits,
a 160 by 64 dots LCD display and event history retention capability. Its typical
configuration includes a power supply, a signaling addressable device circuit, two
notification appliance circuits (NAC), Digital Alarm Communication Transmitter (DACT),
four system status relays and a USB programming port.All the components of the FC2005
control panel are mounted in an 18.1" x 16.5" enclosure.
FC901 main board
The FC901 has only one electronic main board which integrates most functional parts
together (the CPU board is mounted to main board before delivery), including DACT,
System Display, signaling line circuit, NAC, serial interface circuits, system status relays,
programming port and battery charging circuit. The main board is mounted on the
supporting frame, and it provides the connections for external field wiring. An optional city
tie module can be mounted on the backside of the main board. The power supply is
located under the main board and supporting frame.
firealarmresources.com
3
Building Technologies A6V10343700__en_--
Fire safety and security products 09.2011
Power Supply (FP2011-U1)
A 26V (nominal) power supply provides all operating power to the control panel for both
standby and alarm conditions. Sufficient battery charging capability is available to charge
12-18 AH sealed lead-acid batteries within code requirements for up to 24 hours of normal
standby operation plus 5 minutes of alarm operation. The battery will be automatically
disconnected at low battery voltage to prevent deep discharge and battery damage.
Enclosure
All the components of the FC901 control panel are mounted in an 18.1" x 16.5" enclosure.
FC901 supports surface mounting and semi-flush mounting. Semi-flush mounting kits are
available for the enclosure.
The enclosures must be fastened securely to a clean, dry, shock-free, and vibration-free
surface in a protected environment.
firealarmresources.com
Beijing Siemens Cerberus Electronics Limited
No.1,Fengzhidonglu, Xibeiwang, HaiDian District,
Beijing, 100094, China
Tel: +10 6476 8806
Fax: +10 6476 8899
© Data and design subject to change without notice.
Doc No. A6V10343700_a_en_-- Version a
Edition 09.2011
City Tie Module
The city tie module provides local energy and polarity reversal connections. The polarity
reversal connections provide a trouble circuit and an alarm circuit with optional trouble
output. The city tie board mounts onto the main board.
Order Information
Type Description Part No.
FCM901-U3 FCM901-U3 Cerberus main board S54433-B101-A1
FH901-U3 FH901-U3 Cerberus housing (black) S54433-B103-A3
FH901-R3 FH901-R3 Cerberus housing (red) S54433-B103-A4
FX901-U3 FX901-U3 Cerberus configuration kit S54433-S105-A1
FXA901-A1 FXA901-A1 Configuration cable S54433-K108-A1
FHA902-U1 FHA902-U1 Housing trim kit (black) S54433-B106-A1
FHA902-R1 FHA902-R1 Housing trim kit (red) S54433-B106-A2
FHA901-U1 FHA901-U1 Battery bracket S54433-B107-A1
firealarmresources.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Siemens FC901-R3 Control Panel User manual

Category
Fire protection
Type
User manual

Siemens FC901-R3 Control Panel is a compact and powerful standalone fire alarm control panel. It features advanced addressable fire detection, keypad and offline programming, notification circuits, a 160 by 64 dots LCD display, and event history retention capability. Its typical configuration includes a power supply, a signaling addressable device circuit, two notification appliance circuits (NAC), Digital Alarm Communication Transmitter (DACT), four system status relays, and a USB programming port. All the components are mounted in an 18.1" x 16.5" enclosure.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI