Robur GITIE' ACAY Installation, Use And Maintenance Manual

Type
Installation, Use And Maintenance Manual
Gitié ACAY
with absorption chiller and gas condensing boiler
Integrated package for outdoor installation
Installation, use and maintenance manual
Revision: A
Code: D-LBR720GB
This Installation, use and maintenance manual has been drawn up and printed by Robur S.p.A.; whole or partial
reproduction of this Installation, use and maintenance manual is prohibited.
The original is
led at Robur S.p.A.
Any use of this Installation, use and maintenance manual other than for personal consultation must be previously
authorised by Robur S.p.A.
The rights of those who have legitimately led the registered trademarks contained within this publication are not
aected.
With the aim of continuously improving the quality of its products, Robur S.p.A. reserves the right to modify the
data and contents of this Installation, use and maintenance manual without prior notice.
DISPOSAL
The appliance and all its accessories must be disposed of separately in accordance with the regulations in force.
Use of the WEEE symbol (Waste Electrical and Electronic Equipment) indicates that this product cannot be disposed of as household waste.
Proper disposal of this product helps to prevent potential negative consequences for the environment and human health.
Installation, use and maintenance manual – Gitié ACAY
3
I Introduction .............................................................................
p.4
I.1 Recipients ..........................................................................
p.4
I.2 Control device ..................................................................
p.4
II Symbols and denitions ...............................................
p.4
II.1 Key to symbols .................................................................
p.4
II.2 Terms and denitions ....................................................
p.4
III Warnings......................................................................................
p.4
III.1 General and safety warnings ......................................
p.4
III.2 Conformity ........................................................................
p.6
III.3 Exclusions of liability and warranty ..........................
p.6
1 Features and technical data ......................................
p.7
1.1 Features ..............................................................................
p.7
1.2 Dimensions .......................................................................
p.8
1.3 Components ...................................................................
p.10
1.4 Wiring diagrams ............................................................
p.14
1.5 Electronic boards ..........................................................
p.18
1.6 Controls ............................................................................
p.19
1.7 Technical characteristics .............................................
p.20
2 Transport and positioning ........................................
p.22
2.1 Warnings ..........................................................................
p.22
2.2 Handling ...........................................................................
p.22
2.3 Appliance positioning .................................................
p.22
2.4 Minimum clearance distances..................................
p.23
2.5 Mounting base ...............................................................
p.23
3 Heating engineer ...............................................................
p.23
3.1 Warnings ..........................................................................
p.23
3.2 Hydraulic system ...........................................................
p.24
3.3 Hydraulic connections ................................................
p.24
3.4 Water circulation pumps ............................................
p.25
3.5 Antifreeze function .......................................................
p.25
3.6 Antifreeze liquid ............................................................
p.25
3.7 System water quality ...................................................
p.26
3.8 System lling ..................................................................
p.26
3.9 Fuel gas supply ..............................................................
p.26
3.10 AY00-120 unit combustion products exhaust
.............................................................................................
p.27
3.11 AY00-120 Unit ue gas condensate discharge
.............................................................................................
p.28
4 Electrical installer ..............................................................
p.28
4.1 Warnings ..........................................................................
p.28
4.2 Electrical systems ..........................................................
p.28
4.3 Electrical power supply ...............................................
p.29
4.4 Set-up and control ........................................................
p.29
4.5 Water circulation pumps (versions C0) .................
p.31
5 First start-up ..........................................................................
p.32
5.1 Preliminary checks ........................................................
p.32
5.2 Electronic adjustment on the machine - Menus
and parameters of the S61 board and of the
AY10 board ......................................................................
p.33
5.3 Modifying settings ........................................................
p.34
6 Normal operation ..............................................................
p.34
6.1 Warnings ..........................................................................
p.34
6.2 Switch on and o ..........................................................
p.34
6.3 Modifying settings ........................................................
p.35
6.4 Eciency ..........................................................................
p.35
7 Maintenance ..........................................................................
p.35
7.1 Warnings ..........................................................................
p.35
7.2 Pre-emptive maintenance .........................................
p.35
7.3 Scheduled routine maintenance .............................
p.36
7.4 Messages on the display ............................................
p.36
7.5 Restarting a locked-down unit.................................
p.37
7.6 Periods of inactivity ......................................................
p.37
8 Diagnostics ..............................................................................
p.38
8.1 Operative codes.............................................................
p.38
9 Appendices..............................................................................
p.41
9.1 Product che...................................................................
p.41
9.2 Safety devices .................................................................
p.43
INDEX OF CONTENTS
Introduction
4
I
I INTRODUCTION
Installation, use and maintenance manual
This Manual is an integral part of the Gitié ACAY unit
and must be handed to the end user together with the
appliance.
I.1 RECIPIENTS
This Manual is intended for:
End user, for appropriate and safe use of the appliance.
Qualied installer, for correct appliance installation.
Planner, for specic information on the appliance.
I.2 CONTROL DEVICE
In order to be able to work, the ACAY unit needs a control device
(DDC or external requests), which must be connected by the
installer.
II SYMBOLS AND DEFINITIONS
II.1 KEY TO SYMBOLS
DANGER
WARNING
NOTE
PROCEDURE
REFERENCE (to other document)
II.2 TERMS AND DEFINITIONS
Gitié ACAY Appliance / Unit = equivalent terms, both used to
designate the integrated package consisting of a GA ACF unit
and a AY00-120 condensing boiler.
GA Appliance/Unit = equivalent terms, both used to designate
the GA Gas Absorption chiller.
AY00-120 Boiler / Unit = equivalent terms, both used to desig-
nate the AY00-120 condensing boiler.
TAC = Technical Assistance Centre authorised by Robur.
External enable = generic control device (e.g. thermostat, clock
or any other system) equipped with a voltage-free NO contact
and used as control to start/stop the GAHP/GA unit and the
AY00-120 boiler.
DDC Control (Direct Digital Controller) = optional Robur adjust-
ment device to control one or more Robur appliances (GAHP
heat pumps, GA chillers and AY00-120 boilers) in ON/OFF mode.
RB100/RB200 Devices (Robur Box) = optional interface devices
complementary to DDC, which may be used to broaden its func-
tions (heating/cooling/DHW production service demands, and
control of system components such as third party generators,
adjustment valves, circulators, probes).
Thermal generator = equipment (e.g. boiler, heat pump, etc..)
for heat production for heating and/or DHW.
GUE (Gas Utilization Eciency) = eciency index of gas chiller,
equal to the ratio between the chilling energy produced and the
energy of the fuel used (relative to NCV, net caloric value).
First start-up = appliance commissioning operation which may
only and exclusively be carried out by a TAC.
S61 Board = electronic board on the GA unit, to control all func-
tions and to provide interface with other devices and with the
user.
S70/AY10 Boards = electronic boards on the AY00-120 boiler, to
control all functions and to provide interface with other devices
and with the user.
III WARNINGS
III.1 GENERAL AND SAFETY WARNINGS
Installer's qualications
Installation must exclusively be performed by a qualied
rm and by qualied personnel, with specic knowledge
on heating, cooling, electrical systems and gas applianc-
es, in compliance with the laws in force in the Country of
installation.
Declaration of conformity
Upon completing installation, the installing rm shall
issue to the owner/client the appliance's workmanlike
conformity declaration, according to national/local reg-
ulations in force and the manufacturer's instructions/
provisions.
Misuse
The appliance must only be used for the purposes for
which it has been designed. Any other use is deemed
hazardous. Incorrect use may aect operation, duration
and safety of the appliance. Adhere to the manufactur-
er's instructions.
Hazardous situations
Do not start the appliance in hazardous conditions, such
as: gas smell, problems with the plumbing/electrical/gas
system, parts of the appliance under water or damaged,
malfunctioning, disabling or bypassing control and safe-
ty devices.
In case of danger, request intervention by qualied per-
sonnel.
In case of danger, switch o the electrical power and gas
supplies only if this can be done in total safety.
Warnings
Installation, use and maintenance manual – Gitié ACAY
5
III
Do not entrust children, persons with physical, sensory
or mental disabilities or persons with poor knowledge
and experience with use of the appliance.
Gas component tightness
Before performing any operation on gas ducting compo-
nents, close the gas valve.
Upon completing any procedure, perform the tightness
test according to regulations in force.
Gas smell
If you smell gas:
Do not use electrical devices such as telephones, mul-
timeters or other equipment that may cause sparks next
to the appliance.
Shut o the gas supply by turning the valve o.
Switch o the power supply via the external disconnect
switch in the power supply electrical panel.
Use a telephone away from the appliance to ask for inter-
vention from qualied personnel.
Poisoning
Ensure the ue gas ducts are tightness and compliant
with the regulations in force.
Upon completing any procedure, ensure components
are tightness.
Moving parts
The appliance contains moving parts.
Do not remove guards during operation, and in any case
prior to disconnecting the power supply.
Burn hazard
The appliance contains very hot parts.
Do not open the appliance and do not touch internal
components before the appliance has cooled down.
Do not touch the ue gas exhaust before it has cooled
down.
Pressure vessels
The appliance has a sealed circuit classied as pres-
sure vessel, the tightness of which is tested by the
manufacturer.
Do not carry out any intervention on the sealed circuit or
on the appliance's valves.
Water-ammonia solution
The GAHP/GA unit uses the ammonia-water absorption
cycle. The water-ammonia solution is contained in the
sealed circuit. The solution is harmful for health if it is in-
gested, inhaled or comes in contact with the skin.
In the event of coolant leak keep away and disconnect
the power and gas supply (only if it is possible to do so
with no danger).
Ask for TAC intervention.
Electrocution hazard
Disconnect the electrical power supply before any oper-
ation on appliance components.
For electrical connections exclusively use compliant
components and according to the specications provid-
ed by the manufacturer.
Ensure the appliance cannot be accidentally switched
back on.
Earthing
Electrical safety depends on eective earthing system,
correctly connected to the appliance and installed ac-
cording to the regulations in force.
Distance from combustible or ammable materials
Do not deposit ammable materials (paper, diluents,
paints, etc.) near the appliance.
Limescale and corrosion
Depending on the chemical/physical properties of the
system water, limescale or corrosion may damage the
appliance (Paragraph 3.7
p.26
).
Check system sealing.
Avoid frequent top-ups.
Chloride concentration
The concentration of chlorides or free chlorine in the
system water must not exceed the values in Table
3.2
p.26
.
Aggressive substances in the air
Halogenated hydrocarbons containing chlorine and u-
orine compounds cause corrosion. The air of the installa-
tion site must be free from aggressive substances.
Acid ue gas condensate
Discharge the acid condensate of combustion ue gas,
as indicated in Paragraph 3.11
p. 28
, in compliance
with current exhaust regulations.
Switching the appliance o
Disconnecting the power supply while the appliance
is running may cause permanent damage to internal
components.
Except in the case of danger, do not disconnect the pow-
er supply to switch o the appliance, but always and ex-
clusively act through the provided control device (DDC
or external request).
In the event of failure
Operations on internal components and repairs may
exclusively be carried out by a TAC, using only original
parts.
In the event of failure of the appliance and/or breakage
of any component, do not attempt to repair and/or re-
store and immediately contact the TAC.
Routine maintenance
Proper maintenance assures the eciency and good op-
eration of the appliance over time.
Maintenance must be performed according to the man-
ufacturer's instructions (see Chapter 7
p. 35
) and in
Warnings
6
III
compliance with current regulations.
Appliance maintenance and repairs may only be entrust-
ed to rms legally authorised to work on gas appliances
and systems.
Enter into a maintenance contract with an authorised
specialised rm for routine maintenance and for servic-
ing in case of need.
Use only original parts.
Decommissioning and disposal
If the appliance is to be disposed of, contact the manu-
facturer for its disposal.
Keep the Manual
This Installation, use and maintenance manual must al-
ways accompany the appliance and must be handed to
the new owner or installer in the event of sale or removal.
III.2 CONFORMITY
EU directives and standards
I gruppi integrati Gitié sono sono certicati in conformità alla
norma EN 12309 e rispondono ai requisiti essenziali delle seg-
uenti Direttive:
2016/426/EU "Gas Appliances Regulation" as amended and
added.
2014/30/EC "Electromagnetic Compatibility Directive" as
amended and added.
2014/35/EC "Low Voltage Directive" as amended and added.
2006/42/EC "Machine Directive" as amended and added.
2014/68/EU "Pressure Equipment Directive" as amended
and added.
811/2013/EU "Energy-Related Products regulation" as
amended and added.
813/2013/EU "Ecodesign requirements regulation" as
amended and added.
Furthermore, they comply with the requirements of the follow-
ing standards:
EN 677 Specic requirements for condensing boilers with
nominal heat input up to 70 kW.
EN 378 Refrigerating systems and heat pumps.
EN 483 Type C boilers of nominal heat input not exceeding
70 kW.
EN 15502 Gas-red central heating boilers.
Other applicable provisions and standards
The design, installation, operation and maintenance of the sys-
tems shall be carried out in compliance with current applicable
regulations, depending on the Country and location, and in ac-
cordance with the manufacturer's instructions. In particular, reg-
ulations regarding the following shall be complied with:
Gas systems and equipment.
Electrical systems and equipment.
Heating and air conditioning systems, heat pumps and chill-
ers.
Environmental protection and combustion products ex-
haust.
Fire safety and prevention.
Any other applicable law, standard and regulation.
III.3 EXCLUSIONS OF LIABILITY AND
WARRANTY
Any contractual or extra-contractual liability of the man-
ufacturer for any damage caused by incorrect installa-
tion and/or improper use and/or failure to comply with
regulations and with the manufacturer's directions/in-
structions shall be disclaimed.
In particular, the warranty on the appliance may be ren-
dered void by the following conditions:
Incorrect installation.
Misuse.
Failure to comply with the manufacturer's indications on
installation, use and maintenance.
Alteration or modication of the product or any part
thereof.
Extreme operational conditions or however outside of
the operational ranges set forth by the manufacturer.
Damages caused by external agents such as salts, chlo-
rine, sulphur or other chemical substances contained in
the installation water or present in the air of the instal-
lation site.
Abnormal actions transmitted to the appliance by the
plant or installation (mechanical stresses, pressure, vi-
brations, thermal expansion, electrical surges...).
Accidental damages or due to force majeure.
Features and technical data
Installation, use and maintenance manual – Gitié ACAY
7
1
1 FEATURES AND TECHNICAL DATA
The Gitié ACAY group consists of a GA ACF chiller and a AY00-120
condensing boiler.
1.1 FEATURES
1.1.1 GA ACF Unit features
Operation
Based on the thermodynamic water-ammonia absorption cycle
(H
2
0–NH
3
), the appliance produces chilled water using natural
gas (or LPG) as primary energy and dissipating heat directly to
the outside air.
The thermodynamic cycle takes place within a hermetically
sealed circuit, in welded construction, perfectly tight, facto-
ry-tested, which does not require any maintenance or coolant
top-ups.
Mechanical and thermo-hydraulic components
Steel sealed circuit, externally treated with epoxy paint.
Multigas pre-mixing burner equipped with ignition and
ame detection managed by an electronic control unit.
Titanium stainless steel shell-and-tube water exchanger
(evaporator), externally insulated.
Air exchanger (condenser) with nned coil, with steel pipe
and aluminium ns.
Variable-ow microprocessor-controlled helicoidal mo-
tor-fan.
Standard or S silenced fan (reduction of electrical consump-
tion and reduction of sound emission).
Control and safety devices
S61 electronic board with microprocessor, LCD display and
knob.
Circuit water ow switch.
Generator limit thermostat, with manual reset.
automatically resettable ue gas thermostat;
Dierential ue gas pressure switch on the combustion cir-
cuit.
Sealed circuit safety relief valve.
Bypass valve, between high and low-pressure circuits.
Ionization ame control box.
Double shutter electric gas valve.
Antifreeze functions for hydraulic circuit.
1.1.2 AY00-120 Unit features
Operation
The AY00-120 unit is a high eciency condensing boiler suitable
for supply hot water up to 80 °C. The appliance is provided with
an internal heat exchanger to separate internal hydraulic circuit
from system hydraulic circuit.
Mechanical and thermo-hydraulic components
Premixed multigas burner with low NOx and CO emissions.
Stainless steel plate heat exchanger, which also acts as a hy-
draulic separator.
Automatic and manual air vent devices on the appliance in-
ternal circuit.
Flue gas exhaust duct with relevant terminal, for type B53P
conguration.
Condensate discharge siphon (with antifreeze protection).
Control and safety devices
Electronic board with microprocessor.
Automatically resettable water temperature limit thermo-
stat.
Flue gas limit thermostat, for single use (thermal switch).
System circuit water dierential pressure switch (PD1).
Appliance internal circuit water dierential pressure switch
(PD2) with anti-welding function.
Overpressure valve for the appliance internal circuit, set to
trip at 3 bar.
Appliance internal circuit expansion tank.
Ionization ame control box.
Double shutter electric gas valve.
Antifreeze functions for hydraulic circuit.
Antifreezing thermostat for the heating element on the con-
densate siphon.
1.1.3 ACAY Integrated package features
The Gitié group is available in the following versions (Figure
1.6
p.11
):
Basic version (/4 C0)
Version KIT/4 C1
Version KIT/2 C0
Version KIT/2 C1
In 4-pipe versions units operation may be simultaneous or
independent.
The Table 1.1
p. 7
shows the features of the various versions
in detail.
Table1.1 Gitié ACAY package versions
Version Pipes Circulating pumps Motorised 2-way valves Hydraulic circuits Simultaneous operation Fan
/4 C0 4 No No independent Yes standard
/4 C0 S 4 No No independent Yes silenced
/4 C1 4 Yes No independent Yes standard
/4 C1 S 4 Yes No independent Yes silenced
/2 C0 2 No Yes single No standard
/2 C0 S 2 No Yes single No silenced
/2 C1 2 Yes No single No standard
/2 C1 S 2 Yes No single No silenced
Features and technical data
8
1
1.2 DIMENSIONS
Figure1.1 Size (Standard ventilation)
Figure1.2 Dimensions (silenced fan)
Features and technical data
Installation, use and maintenance manual – Gitié ACAY
9
1
Figure1.3 Service plate 2-pipe group (KIT/2 C0 and C1) - Detail of water/gas ttings
A Outlet water tting Ø 1 1/2"F
B Inlet water tting Ø 1 1/2"F
C Boiler condensate drain AY00-120
G Gas tting Ø 3/4"M
Figure1.4 Service plate 4-pipe group (base version and KIT/4 C1) - Detail of water/gas ttings
A AY - Water outlet tting Ø 1 1/4"F
B AY - Water inlet tting Ø 1 1/4"F
C Boiler condensate drain AY00-120
E GAHP/GA - Water outlet tting Ø 1 1/4"F
F GAHP/GA - Water inlet tting Ø 1 1/4"F
G Gas tting Ø 3/4"M
Features and technical data
10
1
1.3 COMPONENTS
Figure1.5 Internal components - front view
1 Fan (silenced version)
2 Gas valve
3 Combustion air hose
4 Combustion blower
5 Ignition transformer
6 Oil pump
7 Water delivery tting: 1 1/4"F
8 Water return tting: 1 1/4"F
9 Gas connection
10 TA outdoor temperature probe

Features and technical data
Installation, use and maintenance manual – Gitié ACAY
11
1
Figure1.6 Version components
1 BASE version (2 independent circuits without circulating pumps)
2 Kit/4 C1 (2 independent circuits with onboard circulating pumps)
3 Kit/2 C0 (single circuit with two 2-way motorised valves)
4 Kit/2 C1 (single circuit with onboard circulating pumps)
Features and technical data
12
1
Figure1.7 Internal components - left side view
1 Flue thermostat
2 Flame sensor / ignition electrodes
3 Electrical panel

Features and technical data
Installation, use and maintenance manual – Gitié ACAY
13
1
Figure1.8 Internal components - right side view
1 TG generator temperature probe
2 Safety valve
3 Flow switch
4 Flow temperature probe
5 Limit thermostat
6 Return temperature probe
7 Teva evaporator temperature probe
8 Air-vent manual valve






Features and technical data
14
1
1.4 WIRING DIAGRAMS
Figure1.9 GA-ACF, ACF-TK, ACF-LB, ACF-HT Unit wiring diagram
TER Power supply terminal block 230 Vac
SCH1 Electronic board (S61)
GV Gas solenoid valve
LS Gas ow warning lamp
PSW Air pressure switch
THMF Outlet water temperature probe
THRF Inlet water temperature probe
TCN Condenser outlet temperature probe
TA Ambient air temperature probe
TG Generator temperature sensor
SRT1 Oil pump rotation sensor
TF Flue gas thermostat
TL Generator limit thermostat (manual reset)
FL Water ow switch
BLW Blower motor
C Blower condenser
FAN Fan motor
C2 Fan condenser
PMP Oil hydraulic pump motor
PWRTR Tansformer 230/24 Vac
CNTBOX Flame controller
IGN Ignition electrodes
IGNTR Ignition transformer
FLS Detection electrode
C2
Features and technical data
Installation, use and maintenance manual – Gitié ACAY
15
1
Figure1.10 Gitié package wiring diagram (unit AY00-120)
SCH5 electronic boards S70+AY10
TA room temperature probe
THPC delivery water temperature probe
(appliance internal circuit)
THMC output water temperature probe
(system circuit)
THRC input water temperature probe
(system circuit)
TH combustion unit limit thermostat
(appliance internal circuit)
TF exhausted gas thermostat
PD dierential water pressure switch
(appliance internal circuit)
A2 dierential water pressure switch
(system circuit)
TL water limit thermostat
P1 water circulator
(appliance internal circuit)
LS gas valve ON signal lamp
GV gas solenoid valve
IGNTR ignition transformer
IGN ignition electrodes
FLS ame sensor
CNTBOX ame control unit
BLW blower
MC 230Vac power supply terminal box
PWRTR board transformer
TG antifreeze thermostat for syphon resistance
RS syphon resistance
Features and technical data
16
1
Figure1.11 Gitié package wiring diagram - base version
MA Terminal block
MOD.0 GAHP or ACF unit
MOD.1 AY00-120 unit
SCH1 Controller S61
SCH5 S70+AY10 electronic boards
TER Package power supply terminal box
J2-J10 Control jumpers of system water pumps ("closed")
Figure1.12 Gitié package wiring diagram with KIT/2 C0
MOD.0 GAHP or ACF unit
MOD.1 AY00-120 unit
SCH1 Controller S61
SCH5 S70+AY10 electronic boards
TER Package power supply terminal box
J2-J10 Control jumpers of system water pump ("open")
MA Terminal block
V2V0-V2V1 Motorised valves
Features and technical data
Installation, use and maintenance manual – Gitié ACAY
17
1
Figure1.13 Gitié package wiring diagram with KIT/2 C1 or with KIT/4 C1
MOD.0 GAHP or ACF unit
MOD.1 AY00-120 unit
SCH1 Controller S61
SCH5 S70+AY10 electronic boards
TER Package power supply terminal box
J2-J10 Control jumpers of system water pumps ("closed")
MA Terminal block
PM0-PM1 System water pumps
A Position of pumps ow rate adjustment screw
Figure1.14 CAN connection between AY10 board and S61 (pre-wired in the factory)
SCH5 S70+AY10 electronic boards
SCH1 Controller S61
J1 Jumpers CAN-BUS on AY10 board and S61 board
A Terminal node connection - (3 wires; J1 jumpers = "closed")
C Terminal node connection - (3 wires; J1 jumpers = "closed")
H,L,GND Data signal wires (ref. cables table)
Features and technical data
18
1
1.5 ELECTRONIC BOARDS
GA-ACF unit electronic board (S61)
GA ACF unit electrical panel contains:
Electronic board S61 (Figure 1.15
p. 18
), with
microprocessor, it controls the appliance and displays data,
messages and operative codes. The appliance is monitored
and programmed by interacting with the display and the
knob.
Figure1.15 Electronic board S61
SCH S61 controller
THMF Water delivery temperature probe input
THRF Water return temperature probe input
TCN Condenser outlet temperature probe input
TA Ambient air temperature probe input
TG Generator temperature probe input
TA1 Evaporator output temperature probe input
TA2 Not used
SRT1 Oil pump rotation sensor input
SRT2 Not used
JP12 Connection for generator ns temperature
probe
SPI Not used
P8 (GND, L, H) CAN bus connector
J1 CAN bus Jumper
A1, A2 Connections for actuators limit switches
TF Not used
TL Generator limit thermostat input
FL Water ow switch input
FS5 Board supply input 24 Vac
P7 (R, W, Y, O) Operation enables inputs
IGN.BOX (L, N) Flame control unit supply input
230 Vac
MAIN 230V (L,N) Board supply input 230 Vac
PUMP 230V (L, N) Oil hydraulic pump supply output
N.O. Contact Circuit water circulating pump
controller terminals
J10 Circuit water circulating pump controller
jumper
FAN (BK, WH, BR) Fan output
JTAG S61 board programming connector
ENC Knob
JP10 6-pole ame controller connector
F1 T 2A fuse
F2 T 10A fuse
F3 T 2A fuse
F4 T 3,15A fuse
AY00-120 Unit electronic boards (S70+AY10)
In the electrical panel on the AY00-120 unit there are:
AY10 electronic board (Figure 1.16
p.19
), with micropro-
cessor, it controls the appliance and displays data, messages
and operative codes. The appliance is monitored and pro-
grammed by interacting with the display and the knob.
S70 auxiliary electronic board (Figure 1.16
p.19
).
Features and technical data
Installation, use and maintenance manual – Gitié ACAY
19
1
Figure1.16 AY10+S70 electronic boards
TL Limit thermostat connector
ENC Knob
EV Gas solenoid valve connector
LS Gas valve ON signal lamp connector
P1 6 pole ame controller connector
TF Exhausted gas thermostat connector
PD System water dierential pressure switch
A1, A2 Auxiliary inputs
J2 System water circulator jumper
N.O. CONTACT System water circulating pump control terminals (max 700 W)
V3V (1-2-N) Appliance circulation pump connecting terminals
MAIN 230V (L, N) Board power supply 230 Vac
IGN.BOX (L, N) Flame controller power supply 230 Vac
P1 Connector for blower drive
THRC Return hot water temperature connector
THMC Delivery hot water temperature connector
TA2-TA1 Auxiliary temperature probes connector
J1 CAN bus Jumper
P8 (GND, L, H) CAN bus connector
P7 (R, W, 0) Enable input
FS5 Board supply connector
F1-F2 Fuses
1.6 CONTROLS
Control device
The appliance may only work if it is connected to a control de-
vice, selected from:
(1) pre-congured DDC control
(2) external enables
1.6.1 Adjustment system (1) with pre-congured
DDC control
The main functions are:
Adjustment and control of the GAHP/GA unit and AY00-120
unit in cascade (ON/OFF mode).
Data display and parameters setting.
Hourly programming.
Climatic curve control.
Diagnostics.
Errors reset.
Possibility to interface with a BMS.
DDC functionality may be extended with auxiliary Robur devices
RB100 and RB200 (e.g. service requests, DHW production, Third
Party generator control, probe control, system valves or circulat-
ing pumps, ...).
1.6.2 Adjustment system (2) with external enables
The appliance may also be controlled via generic enable devic-
es (e.g. thermostats, timers, buttons, contactors...) tted with
voltage-free NO contacts. This system only provides elementary
control (on/o, with xed setpoint temperature), without the
important functions of system (1). Control of the cascade be-
tween GAHP/GA and AY00-120 is left to the user.
For connection of the selected device to the appliance's
electronic board please refer to Paragraph 4.4
p.29
.
Features and technical data
20
1
1.7 TECHNICAL CHARACTERISTICS
1.7.1 ACAY Integrated package technical
specications
Table1.2 Technical data Gitié ACAY
ACAY/4 C0 ACAY/4 C1 ACAY/2 C0 ACAY/2 C1
ACAY/4
C0 S
ACAY/4
C1 S
ACAY/2
C0 S
ACAY/2
C1 S
Heating mode
Heat input
nominal (1013 mbar -
15 °C) (1)
kW 34,9
Ambient air tempera-
ture (dry bulb)
maximum °C 45
minimum °C -20
Heating water ow
maximum l/h 3200
nominal l/h 2950
minimum l/h 1500
Pressure loss at nominal
ow rate
version /4 C0 AY120 bar 0,40 - 0,40 -
version /2 C0 bar - 0,56 - 0,56 -
Residual pressure head
at nominal ow rate
version /4 C1 AY120 bar - 0,60 - 0,60 -
version /2 C1 bar - 0,52 - 0,52
Operation in cooling mode
Heat input
nominal (1013 mbar
- 15 °C)
kW 25,3
real kW 25,0
External air temper-
ature
maximum °C 45
minimum °C 0
Water ow rate
maximum l/h 3500
nominal l/h 2770
minimum l/h 2500
Pressure loss at nominal
ow rate
version /4 C0 ACF bar 0,29 - 0,29 -
version /2 C0 bar - 0,56 - 0,56 -
Residual pressure head
at nominal ow rate
version /4 C1 ACF bar - 0,68 - 0,68 -
version /2 C1 bar - 0,52 - 0,52
Electrical specications
Power supply
voltage V 230
type - single-phase
frequency Hz 50
Electrical power
absorption
nominal kW 1,00 (2) 1,38 (2) 1,00 (2) 1,38 (2) 1,05 (2) 1,43 (2) 1,05 (2) 1,43 (2)
Degree of protection IP - X5D
Installation data
Gas consumption
G20 (maximum) m³/h 6,4 (3)
G25 (maximum) m³/h 7,5 (4)
G30 (maximum) kg/h 4,7 (5)
G30 (maximum) kg/h 4,70 (5)
Water tting delivery/inlet “F 1 1/4 1 1/2 1 1/4 1 1/2
Gas connection thread “M 3/4
Dimensions
width mm 1356
depth mm 1260
height mm 1630
Weight in operation kg 440 465 440 465 460 485 460 485
sound power L
w
(max) dB(A) 82,1 (6) 76,1 (6)
sound pressure L
p
at 5 metres (max) dB(A) 60,1 (7) 54,1 (7)
minimum storage temperature °C -30
maximum water pressure in operation bar 4,0
Water content inside the apparatus l 6
(1) Relative to NCV (net caloric value).
(2) ±10% depending on power voltage and absorption tolerance of electric motors.
(3) PCI (G20) 34,02 MJ/m³ (15 °C - 1013 mbar).
(4) PCI (G25) 29,25 MJ/m³ (15 °C - 1013 mbar).
(5) PCI (G30/G31) 46,34 MJ/kg (15 °C - 1013 mbar).
(6) Sound power values detected in compliance with the intensity measurement methodology set forth by standard EN ISO 9614.
(7) Maximum sound pressure levels in free eld, with directionality factor 2.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48