Remarks:
Please avoid applying the over-rated voltage to the output termi-
nal. Power supply may operate incorrectly or fail.In case of oper-
ating a motor etc. , please install an external diode on the output
terminal to protect the unit.
Note:
Overvoltage protection is built-in each output.
If overvoltage protection in V1 or V2 comes into effect, both of out-
put V1 and V2 are not shut down.
Each overvoltage protection is independent of each other.
1.7 Output voltage adjustment range
¡Adjustment of output voltage is possible by using potentiometer
(only available V1 output).
¡Output voltage is increased by turning potentiometer clockwise
and is decreased by turning potentiometer counterclockwise.
1.8 Isolation
¡For a receiving inspection, such as Hi-Pot test gradually increase
(decrease) the voltage for the start (shut down).
Avoid using Hi-Pot tester with the timer because it may generate
voltage a few times higher than the applied voltage, at ON/OFF of
a timer.
If the unit is tested on the isolation between input & output and
output & FG, remote ON/OFF (option) must be shorted to outputs.
d2=5mm min
CN1
d2
d2
d2
d2
2.2 Derating
¡
In the hatched area the specication of Ripple, Ripple Noise is dif-
ferent from other area.
¡
In case2, ventilation must keep the temperature of C119 below
85C. See External View for the location of C119.
¡
The operative ambient temperature is different by with/without
case cover or mounting position.
Please refer to drawings as below.
Please be careful of electric shock or earth leakage in case of
temperature measurement, because C119 is live potential.
¿LEB100F
1Convection
2
Forced air (0.5m
3
/min)
Load factor [%]
Ambient temperature [C]
20
0
-10 0 10 20 30 40 50 60 70
40
60
80
100
1(D), (E), (F) mounting
1(B), (C) mounting
1(A) mounting
2
¿LEB100F-£-SN (requirement: Min. AC90V)
1Convection
2Forced air (0.5m3/min)
Load factor [%]
Ambient temperature [C]
20
0
-10 0 10 20 30 40 50 60 70
40
60
80
100
1(D), (E) mounting
1(B), (C) mounting
1(A) mounting
2
¿LEB150F
Load factor [%]
Ambient temperature [C]
20
0
-10 0 10 20 30 40 50 60 70
40
60
80
100
1(D), (E), (F) mounting
1(B), (C) mounting
1(A) mounting
2
1Convection
2Forced air (0.5m3/min)
2.1 Installation method
¡
When two or more power supplies are used side by side, position
them with proper intervals to allow enough air ventilation. Ambi-
ent temperature around each power supply should not exceed the
temperature range shown in derating curve.
¡
In case of metal chassis, keep the distance between d1 and d2
for to insulate between lead of component and metal chassis. If ti
is less than d1 and d2, insert the insulation sheet between power
supply and metal chassis.
d1=8mm min
CN1
d1
d2
2 Assembling and
Installation Method
AC-DC Power Supplies Open Frame/ Enclosed Type
Instruction Manual