Bryant 355AAV EVOLUTION Troubleshooting guide

Category
Water heaters & boilers
Type
Troubleshooting guide

This manual is also suitable for

- 1 -
troubleshooting guide
355MAV
Variable Speed, Two-Stage Series H & I
Electronic Condensing 355AAV
Gas Furnace 355BAV
Cancels: SM05-5 SM05-07
6-08
INDEX
PAGE
Safety Considerations................................................................................. 1
Instructions.................................................................................................. 1
Example ...................................................................................................... 2
General........................................................................................................ 2
Sequence of Operation ............................................................................... 2
Single-Stage Thermostat and Two-Stage Heating (Adaptive
Mode) ................................................................................................. 2
Two-Stage Thermostat and Two-Stage Heating .............................. 4
Cooling Mode .................................................................................... 4
Single-Speed Cooling ........................................................................ 4
Single-Stage Thermostat and Two-Speed Cooling (Adaptive
Mode) ................................................................................................. 4
Two-Stage Thermostat and Two-Speed Cooling ............................. 5
Thermidistat Mode............................................................................. 5
Super-Dehumidify Mode................................................................... 5
Continuous-Blower Mode ................................................................. 6
Heat Pump Defrost............................................................................. 6
Component Test................................................................................. 6
Service/Status Code Instructions ............................................................... 7
Start Here .................................................................................................... 9
Rapid Flashing AMBER LED................................................................. 10
Improper Cooling Air Flow ..................................................................... 11
High Heat Temperature Rise Too Low ................................................... 12
Status Code 11 - No Previous Code......................................................... 13
Status Code 12 - Blower On After Power Up ......................................... 13
Status Code 13 - Limit Circuit Lockout .................................................. 14
Status Code 14 - Ignition Lockout ........................................................... 15
Status Code 15 – Blower Motor Lockout................................................ 15
Status Code 21 - Gas Heating Lockout.................................................... 15
Status Code 22 - Abnormal Flame-Proving Signal................................. 16
Status Code 23 - Pressure Switch Did Not Open .................................... 16
Status Code 24 - Secondary Voltage Fuse Is Open................................. 17
Status Code 25 – Model Selection or Setup Error................................... 19
Status Code 31 – High-Heat Switch or Relay did not close or
Reopen.............................................................................................. 19
Status Code 32 - Low-Heat Pressure Switch Did Not Close or
Reopened.......................................................................................... 21
Status Code 33 - Limit Circuit Fault........................................................ 23
Status Code 34 - Ignition-Proving Fault.................................................. 25
Status Code 41 – Blower Motor Fault ..................................................... 26
Status Code 42 – Inducer Motor Fault..................................................... 28
Status Code 43 - Low-Heat Pressure Switch Open While High-Heat
Pressure Switch Is Closed................................................................ 30
Status Code 45 – Control Circuitry Lockout........................................... 31
Cleanup and Start-Up Instructions........................................................... 31
APPENDIX A - Board Layout & Wiring Schematic ............................. 32
APPENDIX B - ECM Blower Motor Description & Operation............ 36
APPENDIX C - Pressure Check Diagram .............................................. 37
APPENDIX D - Static Pressure Reading Location Diagrams................ 38
APPENDIX E - Quick Reference Information ....................................... 40
APPENDIX F - Furnace Staging Algorithm........................................... 41
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified personnel
should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as
cleaning coils, or cleaning and replacing filters. All other operations
should be performed by trained service personnel. When working on
heating equipment, observe precautions in literature, on tags, and on
labels attached to or shipped with the unit, and other safety
precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes
including the National Fuel Gas Code (NFGC) NFPA 54-2006/ANSI
Z223.1-2006. In Canada, refer to the National Standard of Canada
Natural Gas and Propane Installation Codes (NSCNGPIC), CSA
B149.1-05.
Wear safety glasses and work gloves. Have a fire extinguisher
available during start-up, adjustment procedures, and service calls.
Recognize safety information. This is the safety-alert symbol .
When you see this symbol on the furnace and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION,
and NOTE. The words DANGER, WARNING, and CAUTION are
used with the safety-alert symbol. DANGER identifies the most
serious hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal injury or
death. CAUTION is used to identify unsafe practices which may
result in minor personal injury, or product and property damage.
NOTE is used to highlight suggestions which will result in enhanced
installation, reliability, or operation.
INSTRUCTIONS
This guide uses your expertise and observations to lead you to the
trouble spot as efficiently as possible. This is only intended as a guide
and should not be used blindly. Your experience and expertise are of
high value when troubleshooting this unit. Do not disregard all of
your instincts.
The variable speed furnace control was designed with diagnostic
capabilities built in. A AMBER LED is used to flash a status code
which will lead you to one of the sections as listed in the Index.
You should ALWAYS begin in the START HERE section (see Index
for page number) which will guide you to the appropriate section
where a minimal number of steps will be used to correct the problem.
Once in a section, read the ACTION. An ACTION may have a
!
- 2 -
number in the GO TO column. Do whatever the ACTION says, then
proceed to the step indicated in the GO TO column.
If the ACTION is a question (a question will have a number in the
YES or NO column), answer it YES or NO. If the answer is YES, go
to the step indicated in the YES column. If the answer is NO, go to
the step indicated in the NO column.
Let’s try our guide out using the EXAMPLE section below, and see
how it works. Suppose that the problem is a defective low heat
pressure switch (for example the contacts will not open). This is an
internal problem and cannot simply be seen. We go to the START
HERE section to Step 1.
EXAMPLE
Start Here Section
STEP ACTION YES NO GO TO
1. Step 1 tells us to remove main furnace door first and NOT TO REMOVE THE BLOWER
ACCESS PANEL. It then asks the question, “Is AMBER LED status light on?”. If the low
heat pressure switch was defective, a pressure switch did not open status code would be
flashing, so the answer is YES. We go to Step 2.
2 19
2. Step 2 asks the question, “Is the AMBER LED status light blinking rapidly without a pause?”.
If the low heat pressure switch was defective, a pressure switch did not open status code would
be flashing, so the answer is NO. We go to Step 4.
3 4
4. Step 4 asks the question, “Is the AMBER LED status light blinking ON/OFF slowly with a
combination of short and long flashes?”. If the low heat pressure switch was defective, a
pressure switch did not open status code would be flashing, so the answer is YES. We go to
Step 5.
5 7
5. Step 5 tells us to determine the status code. The status code is a 2 digit number with the first
digit determined by the number of short flashes and the second digit by the number of long
flashes. So we count the short and long flashes and see that status code 23 is flashing and go to
Step 6.
6
6. Step 6 tells us to go to status code 23 section INDEX
GENERAL
The furnace must have a 115-vac power supply properly connected
and grounded. Correct polarity must be maintained to enable gas
heating operation.
The gas service pressure must not exceed 0.5 psig (14-in.wc), and no
less than 0.16 psig (4.5-in.wc).
Thermostat wire connections to the furnace at R and W/W1 are the
minimum required for gas heating operation. W2 must be connected
for 2-stage heating thermostats. Y/Y2 and G are required to be
connected to the furnace for single-stage cooling and heat pumps. Y1,
Y/Y2, and G are required for two-stage cooling and heat pumps. G is
required for continuous-fan. C
OM-24V is required for some clock
thermostats. These connections must be made at the 24-vac terminal
block on the furnace control. (See Appendix A)
This furnace can be installed with either a single-stage heat/cool or a
two-stage heat/cool thermostat.
CAUTION: This furnace is equipped with a manual
reset switch in the gas control area. The switch will open
and shut off power to the gas valve, if a flame rollout or
overheating condition occurs in the gas control area. DO
NOT bypass the switch. Correct inadequate combustion-
air supply, component failure before resetting the switch.
Before operating the furnace, check each manual reset switch for
continuity. If necessary, press and release the button to reset the
switch.
SEQUENCE OF OPERATION
Using the schematic diagram in Appendix A, follow the sequence of
operation through the different modes. Read and follow the wiring
diagram very carefully.
Note: If a power interruption occurs during a call for heat (W/W1 or
W/W1-and-W2), the control will start a 90-second blower-only ON
period two seconds after power is restored, if the thermostat is still
calling for gas heating. The amber LED light will flash code 12
during the 90-second period, after which the LED will be ON
continuous, as long as no faults are detected. After the 90-second
period, the furnace will respond to the thermostat normally.
The blower access panel must be installed for power to be conducted
through the blower door interlock switch ILK to the furnace control
CPU, transformer TRAN, inducer motor IDM, blower motor BLWM,
hot-surface igniter HSI, and gas valve GV.
1. SINGLE-STAGE THERMOSTAT AND TWO-STAGE
HEATING (ADAPTIVE MODE)
Note: The low-heat only switch SW1-2 selects either the low-
heat only operation mode when ON, (see item 2. below) or the
adaptive heating mode when OFF in response to a call for heat.
(See Fig. 1.) When the W2 thermostat terminal is energized it
will always cause high-heat operation when the R to W circuit
is closed, regardless of the setting of the low-heat only switch.
This furnace can operate as a two-stage furnace with a single-
stage thermostat because the furnace control CPU includes a
programmed adaptive sequence of controlled operation, which
selects low-heat or high-heat operation. This selection is based
upon the stored history of the length of previous gas-heating
periods of the single-stage thermostat.
!
- 3 -
The furnace will start up in either low- or high-heat. If the
furnace starts up in low-heat, the control CPU determines the
low-heat on-time (from 0 to 16 minutes) which is permitted
before switching to high-heat.
If the power is interrupted, the stored history is erased and the
control CPU will select low-heat for up to 16 minutes and then
switch to high-heat, as long as the thermostat continues to call
for heat. Subsequent selection is based on stored history of the
thermostat cycle times.
The wall thermostat "calls for heat", closing the R to W circuit.
The furnace control performs a self-check, verifies the low-heat
and high-heat pressure switch contacts LPS and HPS are open.
a. Inducer Prepurge Period - The furnace control CPU
turns on inducer motor IDM and slowly increases the
inducer motor speed. When the low-heat pressure switch
LPS closes, inducer motor RPM is noted by the furnace
control CPU, and a 25-second prepurge period begins. The
RPM is used to evaluate vent system resistance. This
evaluation is then used to determine the required RPM
necessary to operate the inducer motor during the low-heat
prepurge period and low-heat mode.
Note: The heat cycle can start in either high- or low-heat.
If a high-heat cycle is initiated, the furnace control CPU
will de-energize the high-heat pressure switch relay HPSR
to close the NC contact and continues to increase the
inducer motor speed after the low-heat pressure switch LPS
closes. When the high-heat pressure switch closes, inducer
motor RPM is noted by the furnace control CPU, and a 25-
second prepurge period begins. The RPM is used to
evaluate vent system resistance. This evaluation is then
used to determine the required RPM necessary to operate
the inducer motor in high-heat mode.
b. Igniter Warm-Up - At the end of the prepurge period, the
Hot-Surface Igniter HSI is energized for a 17-second igniter
warm-up period.
c. Trial-For-Ignition Sequence - When the igniter warm-up
period is completed the main gas valve relay contact GVR
closes to energize the gas valve solenoid GV-M. The gas
valve solenoid GV-M permits gas flow to the burners where
it is ignited. After 5 seconds, the igniter HSI is de-
energized and a 2-second Flame-Proving period begins.
If the furnace control CPU selects high-heat operation, the
high-heat gas valve solenoid GV-HI is also energized.
d. Flame-Proving - When the burner flame is proved at the
flame-proving sensor electrode FSE, the furnace control
CPU begins the blower-ON delay period and continues to
hold the gas valve GV-M open. If the burner flame is not
proved within two seconds, the control CPU will close the
gas valve GV-M, and the control CPU will repeat the
ignition sequence for up to three more Trials-For-Ignition
before going to Ignition-Lockout. Lockout will be reset
automatically after three hours, by momentarily interrupting
115 vac power to the furnace, or by interrupting 24 vac
power at SEC1 or SEC2 to the furnace control CPU (not at
W/W1, G, R, etc.).
If flame is proved when flame should not be present, the
furnace control CPU will lock out of Gas-Heating mode
and operate the inducer motor IDM at full speed until
flame is no longer proved.
e. Inducer Speed Change – If the cycle starts in low-heat, the
furnace control CPU reduces the inducer speed slightly
after flame sense. If the cycle starts in high-heat, the
furnace control CPU increases the inducer speed 15
seconds after flame sense. The reduction in speed in low-
heat is to optimize combustion for maximum efficiency.
f. Blower-On delay – If the burner flame is proven the
blower-ON delay for low-heat and high-heat are as follows:
Low-heat:
355MAV and 355AAV – 60 seconds after the gas valve
GV-M is opened the blower motor BLWM is turned ON at
low-heat airflow.
355BAV – 30 seconds after the gas valve GV-M is opened
the blower motor BLWM is turned ON at low-heat
airflow.
High-heat – 35 seconds after the gas valve GV-M is
opened the BLWM is turned ON at high-heat airflow.
Simultaneously, the humidifier terminal HUM and
electronic air cleaner terminal EAC-1 are energized and
remain energized throughout the heating cycle.
g. Switching from Low- to High-Heat - If the furnace
control CPU switches from low-heat to high-heat, the
furnace control CPU will de-energize the high-heat
pressure switch relay HPSR to close the NC contact and
slowly increase the inducer motor speed until the high-heat
pressure switch HPS closes. When the high-heat pressure
switch HPS closes, the high-heat gas valve solenoid GV-
HI is energized and the inducer motor RPM is noted by the
furnace control CPU. The RPM is used to evaluate vent
system resistance. This evaluation is then used to
determine the required RPM necessary to operate the
inducer motor in high-heat mode. The blower motor
BLWM will transition to high-heat airflow five seconds
after the furnace control CPU switches from low-heat to
high-heat.
Switching from High- to Low-Heat – The furnace
control CPU will not switch from high-heat to low-heat
while the thermostat R to W circuit is closed when using a
single-stage thermostat.
h. Blower-Off Delay - When the thermostat is satisfied, the
R to W circuit is opened, de-energizing the gas valve GV-
M, stopping gas flow to the burners, and de-energizing the
humidifier terminal HUM. The inducer motor IDM will
remain energized for a 15-second post-purge period. The
blower motor BLWM and air cleaner terminal EAC-1 will
remain energized at low-heat airflow or transition to low-
heat airflow for 90, 120, 150, or 180 seconds (depending on
selection at blower-OFF delay switches). The furnace
control CPU is factory-set for a 120-second blower-OFF
delay.
- 4 -
2. TWO-STAGE THERMOSTAT AND TWO-STAGE
HEATING
Note: In this mode the low-heat only switch SW1-2 must be
ON to select the low-heat only operation mode in response to
closing the thermostat R to W1 circuit. Closing the thermostat
R to W1-and-W2 circuits always causes high-heat operation,
regardless of the setting of the low-heat only switch.
The wall thermostat "calls for heat", closing the R to W1 circuit
for low-heat or closing the R to W1-and-W2 circuits for high-
heat. The furnace control performs a self-check, verifies the
low-heat and high-heat pressure switch contacts LPS and HPS
are open, and starts the inducer motor IDM in high-speed.
The start up and shut down functions and delays described in
item 1. above apply to the 2-stage heating mode as well, except
for switching from low- to high-Heat and vice versa.
a. Switching from Low- to High-Heat - If the thermostat
R to W1 circuit is closed and the R to W2 circuit closes, the
furnace control CPU will de-energize the high-heat
pressure switch relay HPSR to close the NC contact and
slowly increase the inducer motor speed until the high-heat
pressure switch HPS closes. When the high-heat pressure
switch HPS closes, the high-heat gas valve solenoid GV-
HI is energized and the inducer motor RPM is noted by the
furnace control CPU. The RPM is used to evaluate vent
system resistance. This evaluation is then used to
determine the required RPM necessary to operate the
inducer motor in high-heat mode. The blower motor
BLWM will transition to high-heat airflow five seconds
after the furnace control CPU switches from low-heat to
high-heat.
b. Switching from High- to Low-Heat - If the thermostat
R to W2 circuit opens, and the R to W1 circuit remains
closed, the furnace control CPU will energize the high-heat
pressure switch relay HPSR to open the NC contact and
slowly decrease the inducer motor speed to the required
low-heat RPM . When the high-heat pressure switch HPS
opens, the high-heat gas valve solenoid GV-HI is de-
energized. When the inducer motor IDM reduces pressure
sufficiently, the high-heat pressure switch HPS will open.
The gas valve solenoid GV-M will remain energized as
long as the low-heat pressure switch LPS remains closed.
The blower motor BLWM will transition to low-heat
airflow five seconds after the R to W2 circuit opens.
3. COOLING MODE
The thermostat "calls for cooling".
a. Single-Speed Cooling
The thermostat closes the R to G-and-Y circuits. The R to
Y circuit starts the outdoor unit, and the R to G-and-Y/Y2
circuits start the furnace blower motor BLWM on cooling
airflow. Cooling airflow is based on the A/C selection
shown in Table 1.
The electronic air cleaner terminal EAC-1 is energized
with 115 vac when the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y circuits
are opened. The outdoor unit will stop, and the furnace
blower motor BLWM will continue operating at cooling
airflow for an additional 90 seconds. Jumper Y/Y2 to
DHUM to reduce the cooling off-delay to 5 seconds. (See
Fig. 1.)
b. Single-Stage Thermostat and Two-Speed Cooling
(Adaptive Mode)
This furnace can operate a two-speed cooling unit with a
single-stage thermostat because the furnace control CPU
includes a programmed adaptive sequence of controlled
operation, which selects low-cooling or high-cooling
operation. This selection is based upon the stored history
of the length of previous cooling period of the single-stage
thermostat.
Note: The air conditioning relay disable jumper ACRDJ
must be connected to enable the adaptive cooling mode in
response to a call for cooling. (See Fig. 1.) When in place
the furnace control CPU can turn on the air conditioning
relay ACR to energize the Y/Y2 terminal and switch the
outdoor unit to high-cooling.
The furnace control CPU can start up the cooling unit in
either low- or high-cooling. If starting up in low-cooling,
the furnace control CPU determines the low-cooling on-
time (from 0 to 20 minutes) which is permitted before
switching to high-cooling.
If the power is interrupted, the stored history is erased and
the furnace control CPU will select low-cooling for up to
20 minutes and then energize the air conditioning relay
ACR to energize the Y/Y2 terminal and switch the
outdoor unit to high-cooling, as long as the thermostat
continues to call for cooling. Subsequent selection is
based on stored history of the thermostat cycle times.
The wall thermostat “calls for cooling”, closing the
R to G-and-Y circuits. The R to Y1 circuit starts the
outdoor unit on low-cooling speed, and the R to G-and-Y1
circuits starts the furnace blower motor BLWM at low-
Table 1 - Cooling Tonnage vs. Airflow (CFM)
525
2
700
2
700
875 1050
875
700 875
2
1050
1050
1
1225
1225
1225
1400
1400
1225
1750
1
1750
1
1225
1750
2100
DEF.
DEF.
DEF.
040, 060, 3T-080
5T-080, 100
120
BASED ON 350 CFM/TON (SETUP SWITCH SW1-5 OFF)
SETUP SWITCH SW3 POSITIONS
MODEL
SIZE
600
2
800
2
800
1000 1200
1000
800 1000
2
1200
1200
1
1400
1400
1400
1600
1600
1400
2000
1
2000
1
1400
2000
2100
DEF.
DEF.
DEF.
040, 060, 3T-080
5T-080, 100
120
BASED ON 400 CFM/TON (SETUP SWITCH SW1-5 ON)
1. DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2. DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
3. SWITCH POSITIONS ARE ALSO SHOWN ON FURNACE WIRING DIAGRAM
SETUP SWITCH SW3 POSITIONS
MODEL
SIZE
AIR CONDITIONING (A/C) OR CONTINUOUS-FAN (CF)
AIRFLOW SELECTION CHART
- 5 -
cooling airflow which is the true on-board CF selection as
shown in Table 1.
If the furnace control CPU switches from low-cooling to
high-cooling, the furnace control CPU will energize the air
conditioning relay ACR. When the air conditioning relay
ACR is energized the R to Y1-and-Y2 circuits switch the
outdoor unit to high-cooling speed, and the R to G-and-
Y1-and-Y/Y2 circuits transition the furnace blower motor
BLWM to high-cooling airflow. High-cooling airflow is
based on the A/C selection shown in Table 1.
Note: When transitioning from low-cooling to high-
cooling the outdoor unit compressor will shut down for 1
minute while the furnace blower motor BLWM transitions
to run at high-cooling airflow.
The electronic air cleaner terminal EAC-1 is energized
with 115 vac whenever the blower motor BLWM is
operating.
When the thermostat is satisfied, the R to G-and-Y circuit
are opened. The outdoor unit stops, and the furnace
blower BLWM and electronic air cleaner terminal EAC-1
will remain energized for an additional 90 seconds.
Jumper Y1 to DHUM to reduce the cooling off-delay to 5
seconds. (See Fig. 1.)
c. Two-Stage Thermostat and Two-Speed Cooling
Note: The air conditioning relay disable jumper ACRDJ
must be disconnected to allow thermostat control of the
outdoor unit staging. (See Fig. 1.)
The thermostat closes the R to G-and-Y1 circuits for low-
cooling or closes the R to G-and-Y1-and-Y2 circuits for
high-cooling. The R to Y1 circuit starts the outdoor unit
on low-cooling speed, and the R to G-and-Y1 circuit starts
the furnace blower motor BLWM at low-cooling airflow
which is the true on-board CF selection as shown in Table
1. The R to Y1-and-Y2 circuits start the outdoor unit on
high-cooling speed, and the R to G-and-Y/Y2 circuits start
the furnace blower motor BLWM at high-cooling airflow.
High-cooling airflow is based on the A/C selection shown
in Table 1.
The electronic air cleaner terminal EAC-1 is energized
with 115 vac whenever the blower motor BLWM is
operating.
When the thermostat is satisfied, the R to G-and-Y1 or
R to G-and-Y1-and-Y2 circuits are opened. The outdoor
unit stops, and the furnace blower BLWM and electronic
air cleaner terminal EAC-1 will remain energized for an
additional 90 seconds. Jumper Y1 to DHUM to reduce the
cooling off-delay to 5 seconds. (See Fig. 1.)
4. THERMIDISTAT MODE
The dehumidification output, DHUM on the Thermidistat
should be connected to the furnace control thermostat terminal
DHUM. When there is a dehumidify demand, the DHUM input
is activated, which means 24 vac signal is removed from the
DHUM input terminal. In other words, the DHUM input logic
is reversed. The DHUM input is turned ON when no
dehumidify demand exists. Once 24 vac is detected by the
furnace control on the DHUM input, the furnace control
operates in Thermidistat mode. If the DHUM input is low for
more than 48 hours, the furnace control reverts back to non-
Thermidistat mode.
The cooling operation described in item 3. above also applies to
operation with a Thermidistat. The exceptions are listed below:
a. When the R to G-and-Y1 circuit is closed and there is a
demand for dehumidification, the furnace blower motor
BLWM will drop the blower airflow to 86% of low-cooling
airflow which is the true on-board CF selection as shown in
Table 1.
b. When the R to G-and Y/Y2 circuit is closed and there is a
demand for dehumidification, the furnace blower motor
BLWM will drop the blower airflow to 86% of high-
cooling airflow. High-cooling airflow is based on the A/C
selection shown in Table 1.
c. When the “call for cooling” is satisfied and there is a
demand for dehumidification, the cooling blower-off delay
is decreased from 90 seconds to 5 seconds.
5. SUPER-DEHUMIDIFY MODE
Super-Dehumidify mode can only be entered if the furnace
control is in the Thermidistat mode and there is a demand for
dehumidification. The cooling operation described in item 3.
above also applies to operation with a Thermidistat. The
exceptions are listed below:
a. When the R to Y1 circuit is closed, R to G circuit is open,
and there is a demand for dehumidification, the furnace
blower motor BLWM will drop the blower airflow to 65%
of low-cooling airflow for a maximum of 10 minutes each
cooling cycle or until the R to G circuit closes or the
demand for dehumidification is satisfied. Low-cooling
airflow is the true on-board CF selection as shown in Table
1.
b. When the R to Y/Y2 circuit is closed, R to G circuit is open,
and there is a demand for dehumidification, the furnace
blower motor BLWM will drop the blower airflow to 65%
of high-cooling airflow for a maximum of 10 minutes each
cooling cycle or until the R to G circuit closes or the
demand for dehumidification is satisfied. High-cooling
airflow is based on the A/C selection shown in Table 1.
c. When the “call for cooling” is satisfied and there is a
demand for dehumidification, the cooling blower-off delay
is decreased from 90 seconds to 5 seconds.
6. Continuous Blower Mode
When the R to G circuit is closed by the thermostat, the blower
motor BLWM will operate at continuous blower airflow.
Continuous blower airflow selection is initially based on the CF
selection shown in Table 1. Factory default is shown in Table
1. Terminal EAC-1 is energized as long as the blower motor
BLWM is energized.
During a call for heat, the furnace control CPU will transition
the blower motor BLWM to continuous blower airflow, low-
heat airflow, or the midrange airflow, whichever is lowest. The
- 6 -
blower motor BLWM will remain ON until the main burners
ignite then shut OFF and remain OFF for the blower-ON delay
(60 seconds in low-heat, and 35 seconds in high-heat), allowing
the furnace heat exchangers to heat up more quickly, then
restarts at the end of the blower-ON delay period at low-heat or
high-heat airflow respectively.
The blower motor BLWM will revert to continuous-blower
airflow after the heating cycle is completed. In high-heat, the
furnace control CPU will drop the blower motor BLWM to
low-heat airflow during the selected blower-OFF delay period
before transitioning to continuous-blower airflow.
When the thermostat "calls for low-cooling", the blower motor
BLWM will switch to low-cooling airflow. When the
thermostat is satisfied, the blower motor BLWM will operate an
additional 90 seconds at low-cooling airflow before
transitioning back to continuous-blower airflow.
When the thermostat "calls for high-cooling", the blower motor
BLWM will switch to high cooling airflow. When the
thermostat is satisfied, the blower motor BLWM will operate an
additional 90 seconds at high-cooling airflow before
transitioning back to continuous-blower airflow.
When the R to G circuit is opened, the blower motor BLWM
will continue operating for an additional 5 seconds, if no other
function requires blower motor BLWM operation.
a. Continuous Blower Speed Selection from Thermostat
To select different continuous-blower airflows from the
room thermostat, momentarily turn off the FAN switch or
push-button on the room thermostat for 1-3 seconds after
the blower motor BLWM is operating. The furnace
control CPU will shift the continuous-blower airflow from
the factory setting to the next highest CF selection airflow
as shown in Table 1. Momentarily turning off the FAN
switch again at the thermostat will shift the continuous-
blower airflow up one more increment. If you repeat this
procedure enough you will eventually shift the continuous-
blower airflow to the lowest CF selection as shown in
Table 1. The selection can be changed as many times as
desired and is stored in the memory to be automatically
used following a power interruption.
7. HEAT PUMP DEFROST
When installed with a heat pump, the furnace control
automatically changes the timing sequence to avoid long blower
off times during demand defrost cycles. Whenever W/W1 is
energized along with Y1 or Y/Y2, the furnace control CPU will
transition to or bring on the blower motor BLWM at cooling
airflow, low-heat airflow, or the midrange airflow, whichever is
lowest. The blower motor BLWM will remain on until the
main burners ignite then shut OFF and remain OFF for 25
seconds before coming back on at heating airflow. When the
W/W1 input signal disappears, the furnace control begins a
normal inducer post-purge period while changing the blower
airflow. If Y/Y2 input is still energized the furnace control
CPU will transition the blower motor BLWM airflow to cooling
airflow. If Y/Y2 input signal disappears and the Y1 input is still
energized the furnace control CPU will transition the blower
motor BLWM to low-cooling airflow. If both the Y1 and Y/Y2
signals disappear at the same time, the blower motor BLWM
will remain on at low-heat airflow for the selected blower-OFF
delay period. At the end of the blower-OFF delay, the blower
motor BLWM will shut OFF unless G is still energized, in
which case the blower motor BLWM will operate at continuous
blower airflow.
8. COMPONENT TEST
The furnace features a component test system to help diagnose
a system problem in the case of a component failure. To initiate
the component test procedure, ensure that there are no
thermostat inputs to the control and all time delays have
expired. Turn on setup switch SW1-6. (See Appendix A)
Note: The component test feature will not operate if the control
is receiving any thermostat signals or until all time delays have
expired.
The component test sequence is as follows:
a. The furnace control CPU turns the inducer motor IDM ON
at medium speed and keeps it ON through step c.
b. After waiting 10 seconds the furnace control CPU turns
the hot surface igniter ON for 15 seconds, then OFF.
c. The furnace control CPU then turns the blower motor
BLWM on at midrange airflow for 15 seconds, then OFF.
d. After shutting the blower motor OFF the furnace control
CPU shuts the inducer motor IDM.
Note: The EAC terminals are energized when the blower is
operating.
After the component test is completed, 1 or more status codes
(11, 25, 41, or 42) will flash. See Service Label on blower
access panel or Service/Status Code Instructions for explanation
of status codes.
Note: To repeat component test, turn setup switch SW1-6 to
OFF and then back ON.
- 7 -
SERVICE/STATUS CODE INSTRUCTIONS
If status code recall is needed disconnect the “R” thermostat lead, reset power, and put setup switch “SW1-1” in the ON position. To clear the status
code history put setup switch “SW1-1” in the ON position and jumper thermostat terminals “R”, “W/W1”, and “Y/Y2” simultaneously until status code
#11 is flashed.
LED CODE STATUS
CONTINUOUS OFF - Check for 115 VAC at L1 and L2, and 24 VAC at SEC-1 and SEC-2.
CONTINUOUS ON - Control has 24 VAC power.
RAPID FLASHING - Line voltage (115 VAC) polarity
reversed.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE
NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11 NO PREVIOUS CODE – Stored status codes are erased automatically after 72 hours or as specified above.
12 BLOWER ON AFTER POWER UP – (115 VAC or 24 VAC) – Blower runs for 90 seconds, if unit is powered up during a call for heat (R-
W/W1 closed) or (R-W/W1 opens) during the blower on-delay period.
13 LIMIT CIRCUIT LOCKOUT – Lockout occurs if the limit, or flame rollout switch is open longer than 3 minutes or 10 successive limit trips
occurred during high-heat. Control will auto reset after 3 hours. Refer to status code #33.
14 IGNITION LOCKOUT – Control will auto reset after 3 hours. Refer to status code #34.
15 BLOWER MOTOR LOCKOUTIndicates the blower failed to reach 250 RPM or the blower failed to communicate within 30 seconds after
being turned ON in two successive heating cycles. Control will auto reset after 3 hours. Refer to status code #41.
21 GAS HEATING LOCKOUT – Control will NOT auto reset. Check for:
- Mis-wired gas valve.
- Defective control (valve relay).
22 ABNORMAL FLAME-PROVING SIGNAL – Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check
for:
- Leaky gas valve.
- Stuck-open gas valve.
23 PRESSURE SWITCH DID NOT OPEN – Check for:
- Obstructed pressure tubing.
- Pressure switch stuck closed.
24 SECONDARY VOLTAGE FUSE IS OPEN – Check for :
- Short circuit in secondary voltage (24 VAC) wiring.
25 MODEL SELECTION OR SETUP ERROR – Either Indicates the model plug (PL4) is missing or incorrect or setup switch “SW1-1” or
“SW1-6” is positioned improperly. If code flashes only 4 times on power-up control is defaulting to model selection stored in memory. Check
the following:
- Thermostat call with “SW1-1” ON.
- Thermostat call with “SW1-6” ON.
- “SW1-1” and “SW1-6” both ON together.
- Two different furnace models twinned.
- Wiring diagram for model plug number and resistance values if code flashes continuously.
- Board does not recognize 355BAV model plugs HK70EZ057 – 061. Furnace board date code 4106 or later required.
31 HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED – Indicates the high-heat pressure switch input
failed to close on a call for high-heat, or opened during high-heat. Control relay may be defective or gas valve is mis-wired. Refer to status code
#32.
32 LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED – Indicates the low-heat pressure switch input failed to close on a
call for low-heat, or opened during low-heat. If opens during blower on-delay period , blower will come on for the selected blower off-delay. If
opens within 5 minutes after ignition the next heating cycle will be restricted to high-heat. Check for:
- Proper vent sizing.
- Plugged condensate drain.
- Low inlet gas pressure (if LGPS used).
- Excessive wind.
- Restricted combustion air supply.
- Improper pressure switch wiring.
- Failed or “Out-of-Calibration” pressure switches.
- Water in vent piping, possible sagging pipe.
- Disconnected or obstructed pressure tubing.
- 8 -
33 LIMIT CIRCUIT FAULT – Indicates the limit, or flame rollout is open or the furnace is operating in high-heat only mode due to 2 successive
low heat limit trips. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes
to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts off. Flame rollout switch requires manual reset.
Check for:
- Proper rear air baffle.
- Loose blower wheel.
- Defective switch or connections.
- Improper low-heat gas input adjustment.
- Stuck high-heat solenoid in gas valve
- Improper or misaligned limit and/or limit shield.
34 IGNITION PROVING FAILURE – Control will try three more times before lockout #14 occurs. If flame signal is lost during blower on-delay
period, blower will come on for the selected blower off-delay. Check for:
- Low inlet gas pressure.
- Control ground continuity.
- Gas valve defective or turned off.
- Defective Hot Surface Igniter.
- Manual valve shut off.
- Oxide buildup on flame sensor (clean with fine steel wool).
- Proper flame sense micro amps (.5 micro amps DC min., 4.0 – 6.0 nominal).
- Green/Yellow wire MUST be connected to furnace sheet metal.
- Inadequate flame carryover or rough ignition.
- Flame sensor must not be grounded.
41 BLOWER MOTOR FAULT – Indicates the blower failed to reach 250 RPM or the blower failed to communicate within the prescribed time
limits. Thirty seconds after being turned ON or ten seconds during steady-state operation.
42 INDUCER MOTOR FAULT – Indicates the inducer has not started within 20 seconds after a call for heat, the inducer motor RPM is outside its
valid range of operation, or the inducer RPM signal was lost for 5 seconds during operation. Check for:
- Proper vent sizing.
- Restricted combustion air supply.
- Failed inducer motor.
- Improper motor wiring.
43 LOW-HEAT PRESSURE SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS CLOSED – Check for:
- Low inlet gas pressure (if LGPS used).
- Plugged condensate drain.
- Improper pressure switch wiring.
- Water in vent piping, possible sagging pipe.
- Stuck open low-heat pressure switch.
- Disconnected or obstructed pressure tubing.
45 CONTROL CIRCUITRY LOCKOUT – Auto-reset after 1 hour lockout due to:
- Flame sense circuit failure.
- Gas valve relay stuck open.
- Software check error.
Reset power to clear lockout. Replace control if status code repeats.
COMPONENT TEST
To initiate the component test sequence, shut “OFF” the room thermostat or disconnect the “R” thermostat lead. Reset power and then put setup switch
“SW1-6” in the ON position to start the component test sequence. Once initiated the furnace control will turn the inducer ON at high-heat speed. The
inducer motor will run for the entire test. The hot surface igniter and blower motor will be turned ON for 15 seconds each. When the blower is turned
OFF the inducer will be turned OFF. When the component test is completed one or more of the following codes will flash.
LED CODE DESCRIPTION
11 Indicates the blower motor tested OK. Visual check of inducer motor and hot surface igniter required.
25 SETUP ERROR – Same as code 25 above.
41 BLOWER MOTOR FAULT – Indicates blower motor failed test. Check blower, wiring, and furnace control.
42 INDUCER MOTOR FAULT – Indicates inducer motor failed test. Check inducer, wiring, and furnace control.
To repeat component test turn setup switch “SW1-6” OFF and then back ON. After component test is completed put setup switch “SW1-6” in the OFF
position and reconnect the “R” thermostat lead.
- 9 -
START HERE - If a problem exists, the service technician should always begin
troubleshooting here.
SPECIAL NOTE: ALL VOLTMETERS ARE NOT THE SAME - YOUR VOLTAGE READINGS WILL VARY. THIS APPLIES TO THE
ENTIRE CONTENT OF THIS TROUBLESHOOTING MANUAL. THEY ARE NOT ABSOLUTE VALUES. CORRECT 115-VAC VOLTAGE,
CURRENT, AND POWER MEASUREMENTS CANNOT BE TAKEN ON VARIABLE SPEED FURNACES UNLESS USING A TRUE RMS
METER.
STEP ACTION YES NO GO TO
1. Remove main furnace door first. DO NOT REMOVE BLOWER ACCESS PANEL! Record
status of AMBER LED. See Service/Status Code Instructions.
Is AMBER LED status light on?
2 19
2. Is the AMBER LED status light blinking rapidly without a pause? 3 4
3. Go to the page number indicated in the Index for RAPID FLASHING LED. INDEX
4. Is the AMBER LED status light blinking ON/OFF slowly with a combination of short and
long flashes?
5 7
5. Determine status code. The status code is a 2 digit number with the first digit determined by
the number of short flashes and the second digit by the number of long flashes.
6
6. Go to page number indicated in the Index for the section covering the status code. INDEX
7. To retrieve previous codes, disconnect the User Interface ABCD connector (if used) or the R
thermostat lead (if used) from the furnace control board and wait for the blower to turn off if it
is running. Put setup switch SW1-1 in the ON position and record the status codes listed in the
status code history. The status codes will flash in the order of occurrence. Read status codes
until an 11 code flashes. After the 11 code flashes the status codes will repeat.
8
8. Was there a previous status code other than code 11?
Note: Status codes are erased after 72 hours or can be manually erased by putting setup switch
SW1-1 in the ON position and jumpering R, W/W1, and Y/Y2 simultaneously until status
code 11 is flashed.
9 10
9. Go to page number indicated in the Index for the section covering the first previous status
code.
INDEX
10. Does the problem appear to be low cooling airflow? 11 12
11. Go to page number indicated in Index for the section covering IMPROPER COOLING
AIRFLOW.
INDEX
12. Set thermostat to call for heat and set the thermostat fan control to AUTO position if equipped. 13
13. Does the furnace respond to the call for heat? 14 28
14. Observe operation of furnace for 20 minutes or until AMBER LED status light starts blinking. 15
15. Does the AMBER LED status light blink ON/OFF slowly with a combination of short and
long flashes?
5 16
16. Is the temperature rise below the range specified on the rating plate when the unit is operating
in high heat?
Note: If the temperature rise is above the range specified on the rating plate refer to the Start-
Up and Adjustment section in the Installation, Start-Up, and Operating Instructions.
17 18
17. Go to page number indicated in Index for the section covering HIGH HEAT
TEMPERATURE RISE TOO LOW (COLD BLOW).
INDEX
18. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
19. Make sure power is being supplied to the furnace. 20
20. Check fuses, breakers, or manual disconnects to be sure they are correctly set. If not, reset
them and go back to step 1.
21
21. Remove blower access panel and depress door switch. Use a piece of tape to hold switch
closed.
22
22. Is 115-vac across L1 and L2? 24 23
23. Turn power off. Check continuity of power leads and door switch. If necessary repair power
leads and/or replace door switch.
18
24. Is 24-vac across SEC-1 and SEC-2? 25 26
25. Replace the variable speed furnace control. 18
- 10 -
STEP ACTION YES NO GO TO
26. Is 115-vac across the transformer leads? 27 25
27. Replace the transformer. 18
28. Is 24-vac across W/W1 and COM-24V on the variable speed furnace control?
You will not be able to check for voltage across W/W1 and C
OM-24V if the furnace is
connected to a User Interface at the ABCD connector. Go to step 29.
30 29
29. You have a defective thermostat, or a break in wiring between thermostat and furnace. Fix
problem.
18
30. Disconnect all thermostat leads from the thermostat terminal block and jumper R to W/W1.
Does the furnace respond to the call for heat?
31 25
31. You have an incompatible thermostat. Do any of the following:
1. Wire the thermostat C terminal to C
OM-24V.
2. Isolate the W/W1 input with a relay.
3. Install ballast resistor across W/W1 and C
OM-24V.
4. Replace the thermostat with a compatible model.
18
RAPID FLASHING AMBER LED - Indicates line voltage polarity is reversed, or the
transformers are out of phase in twinned units.
STEP ACTION YES NO GO TO
1. Is this furnace twinned with another furnace? 7 2
2. Remove blower access panel and depress door switch. Use a piece of tape to hold switch
closed.
3
3. Is 115-vac across NEUTRAL-L2 and chassis ground? 4 6
4. Line voltage polarity is reversed. Fix problem. 5
5. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
6. Replace the variable speed furnace control. 5
7. Remove blower access panels and depress door switch in each unit. Use tape to hold switches
closed.
8
8. Is the AMBER LED status light blinking rapidly in only one of the twinned units? 9 16
9. Are the fuses, breakers, or manual disconnects to the problem unit correctly set? 11 10
10. Fix problem. 5
11. Are the Auxiliary Limit switches properly set? 12 10
12. Do you have 115-vac across L1 and NEUTRAL-L2 in the problem unit? 13 15
13. Do you have 24-vac across SEC-1 and SEC-2 in the problem unit? 6 14
14. Replace the transformer. 5
15. Turn power off to both units. Check continuity of power leads and door switch in the problem
unit. If necessary repair power leads and/or replace door switch in the problem unit.
5
16. Check the furnace circuit breaker location in the service panel.
On single-phase (residential) systems, each furnace circuit breaker should be located directly
across from each other in service panel, or each furnace circuit breaker should be located on
the same side of service panel, but must skip 1 space to be connected to the same leg of the 1-
phase power supply.
On 3-phase (commercial) systems, each furnace circuit breaker should be located directly
across from each other in service panel, or each furnace circuit breaker should be located on
the same side of service panel, but must skip 2 spaces to be connected to the same leg of the 3-
phase power supply.
17
17. Check the 115-vac power lead connections at the variable speed furnace control of each
furnace. The BLACK lead goes to L1 and the WHITE lead goes to NEUTRAL-L2.
18
18. Check the 115-vac transformer lead connections at the variable speed furnace control of each
furnace. The BLACK lead goes to L1 and the WHITE lead goes to NEUTRAL-L2.
19
19. If the circuit breaker location and the 115-vac wiring is correct reverse the transformer
secondary lead connections SEC-1 and SEC-2 in the MAIN furnace.
5
- 11 -
IMPROPER COOLING AIR FLOW - Generally, this indicates the Y/Y2 thermostat lead is not
properly connected. If User Interface is connected to ABCD connector then the wrong size
outdoor unit could be configured in the User Interface.
STEP ACTION YES NO GO TO
1. Remove blower access panel and depress door switch. Use a piece of tape to hold switch
closed.
27
2. Set thermostat to call for cooling. If thermostat does not have G connection jumper across
thermostat terminals R and G.
3
3. Make sure thermostat fan control is in the AUTO position if equipped. 4
4. Do you have 24-vac across Y/Y2 and COM-24V on the variable speed furnace control? 8 5
5. You have a defective thermostat, or a break in the wiring between the thermostat and the
furnace, or the Y/Y2 thermostat terminal is not wired to the thermostat.
6
6. Fix the problem. 7
7. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
8. Are the air conditioning airflow select switches A/C set to the proper airflow as required by the
condensing unit? Typical airflow is based on 350 CFM/TON (See Table 2.)
10 9
9. Set the air conditioning airflow select switches A/C to the proper airflow as required by the
condensing unit. (See Table 2.)
7
10. Disconnect the G thermostat lead or jumper if used. 11
11. Does the blower motor turn off in 5 seconds when the G thermostat lead is disconnected?
Note: When using a Thermidistat the blower may change airflow when the G thermostat lead
is disconnected and a call to dehumidify is active.
12 13
12. Replace the variable speed furnace control. 7
13. Reconnect the G thermostat lead or jumper and observe operation of furnace in cooling mode
for 10 minutes.
14
14. Does the furnace operate properly in cooling mode? 15 16
15. - Check outdoor unit for correct suction pressure and verify charge.
- Check filter(s) and ductwork for restrictions.
- Check furnace coil.
INDEX
16. Does the AMBER LED abruptly shut off as the blower comes up to speed? 17 24
17. Do you have less than 17 vac between R and COM-24V on the variable speed furnace control? 18 24
18. Do you have less than 90 vac between L1 and NEUTRAL-L2 on the variable speed furnace
control?
19 20
19. Make sure the wire gage between main fuse box and furnace complies with wire size
specification in Installation, Start-Up, and Operating Instructions.
6
20. Disconnect the R thermostat lead. 21
21. Do you have less than 17 vac between R and COM-24V on the variable speed furnace control? 22 23
22. Replace transformer. 7
23. Check the thermostat wire gage between furnace and thermostat, and furnace and outdoor unit.
It is recommended that AWG No. 18 color-coded copper thermostat wire be used for lengths
up to 100 ft. For wire lengths over 100 ft, use AWG No. 16 wire.
6
24. Is Status Code 41 flashing? 25 26
25. Go to the page number indicated in the Index for Status Code 41. INDEX
26. - Check outdoor unit for correct suction pressure and verify charge.
- Check furnace coil.
7
27. Is a User Interface connected to the ABCD connector? 28 2
28. The wrong size outdoor unit may have been selected in the User Interface. You will need to
set the proper size of the outdoor unit in the User Interface. If set properly then the User
Interface may be reducing the airflow for dehumidification.
7
- 12 -
Table 2 – Cooling Tonnage vs. Airflow (CFM)
AIR CONDITIONING TONS
(12,000 BTU/HR)
AIRFLOW
(CFM)
040, 060, & 3T-
080 MODEL
5T-080 & 100
MODEL
120 MODEL
1-1/2
525 X
2
700 X X X
2-1/2
875 X X X
3
1050 X X X
3-1/2
1225 X X X
4
1400 X X
5
1750 X X
6
2100 X
HIGH HEAT TEMPERATURE RISE TOO LOW - Generally, this indicates the HI solenoid in gas
valve GV has failed or the furnace is extremely underfired.
STEP ACTION YES NO GO TO
1. Remove the blower access panel. Disconnect User Interface ABCD connector (if used) or the
R thermostat lead (if used) from the furnace control board. If setup switch SW1-2 is ON then
set it to OFF.
2
2. Depress the door switch. Use piece of tape to hold it closed. 3
3. Jumper R and W/W1 thermostat terminals. 4
4. When the furnace is running in low heat, clock the low heat gas rate. You have 16 minutes on
this first call for heat before unit switches to high heat. On propane installations check the
manifold pressure.
5
5. When the furnace is running in high heat, clock the high heat gas rate. On propane
installations check the manifold pressure.
6
6. Is the high heat rate approximately the same as the low heat rate? 7 11
7. Do you have 24 vac across gas valve terminals HI and COM-24V on 2-stage gas valve during
high heat?
10 8
8. You have an open wire or bad terminal on the BROWN wire from the high heat pressure
switch HPS to the gas valve GV. Repair it or replace the harness.
9
9. Go to the page number indicated in Index for the CLEANUP AND STARTUP
INSTRUCTIONS.
INDEX
10. Replace the gas valve. 9
11. Is the high heat rate within 2% of that specified on the rating plate? 13 12
525
2
700
2
700
875 1050
875
700 875
2
1050
1050
1
1225
1225
1225
1400
1400
1225
1750
1
1750
1
1225
1750
2100
DEF.
DEF.
DEF.
040, 060, 3T-080
5T-080, 100
120
BASED ON 350 CFM/TON (SETUP SWITCH SW1-5 OFF)
SETUP SWITCH SW3 POSITIONS
MODEL
SIZE
600
2
800
2
800
1000 1200
1000
800 1000
2
1200
1200
1
1400
1400
1400
1600
1600
1400
2000
1
2000
1
1400
2000
2100
DEF.
DEF.
DEF.
040, 060, 3T-080
5T-080, 100
120
BASED ON 400 CFM/TON (SETUP SWITCH SW1-5 ON)
1. DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2. DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
3. SWITCH POSITIONS ARE ALSO SHOWN ON FURNACE WIRING DIAGRAM
SETUP SWITCH SW3 POSITIONS
MODEL
SIZE
AIR CONDITIONING (A/C) OR CONTINUOUS-FAN (CF)
AIRFLOW SELECTION CHART
- 13 -
STEP ACTION YES NO GO TO
12. Ensure the gas inlet pressure and burner orifice are correct. Then adjust the gas valve to the
proper rate. If it cannot be adjusted to the proper rate, replace the gas valve.
9
13. Is outdoor condensing unit operating during heating cycle? 16 14
14. Check temperature rise and external static pressure with blower access panel in place.
Temperature rise should be mid range or higher than midpoint of range stated on furnace rating
plate. External static pressure must not exceed .7 in.w.c. If return temperature is below 60
deg. F condensation may form on heat exchangers. If left uncorrected failure will result.
15
15. Check return air ducts in unheated spaces for leaks. 9
16. Fix problem. 9
Status Code 11
NO PREVIOUS CODE - Stored status codes are erased after 72 hours or can be cleared by jumpering R, W/W1, and Y/Y2
thermostat leads while setup switch SW1-1 is ON. Run system through a heating or cooling cycle to check system.
This usually indicates one of the following:
- The status history has been cleared and setup switch SW1-1 is in the ON position.
- Component test was successfully completed and setup switch SW1-6 is in the ON position.
STEP ACTION YES NO GO TO
1. Remove the blower access panel, depress the door switch. Use piece of tape to hold it closed. 2
2. Is setup switch SW1-1 in the ON position. 3 5
3. Put setup switch SW1-1 in the OFF position. 4
4. Go to the page number indicated in Index for the CLEANUP AND STARTUP
INSTRUCTIONS.
INDEX
5. Is setup switch SW1-6 in the ON position. 6 7
6. Put setup switch SW1-6 in the OFF position. 4
7. Jiggle setup switches SW1-1 and SW1-6 back and forth. If status code 11 continues to flash
replace the variable speed furnace control
4
Status Code 12
BLOWER ON AFTER POWER UP - Blower will run for 90 seconds when furnace power is interrupted and later restored during
a call for heat (R-W/W1 closed) or if the call for heat is interrupted (R-W/W1 opens) during the blower on-delay period. If this
status code repeats every couple of minutes it is probably caused by a direct short in the pressure switch circuits, gas valve
GV, wiring to gas valve GV, or humidifier coil.
STEP ACTION YES NO GO TO
1. Remove the blower access panel and disconnect User Interface ABCD connector
(if used) or the R thermostat lead (if used) from the furnace control board.
2
2. Depress the door switch. Use piece of tape to hold it closed. 3
3. Jumper R and W/W1 thermostat terminals. 4
4. Does the furnace keep repeating the following cycle?
Induced draft motor IDM runs, induced draft motor IDM stops, blower motor
BLWM runs for 90 seconds while AMBER LED status light flashes status code 12.
5 20
5. Do you have less than 17-vac across R and COM-24V on the variable speed furnace
control?
6 14
6. Do you have less than 90-vac across L1 and NEUTRAL-L2 on the variable speed
furnace control?
7 10
7. Make sure wire gage between main fuse box and furnace complies with wire size
specification in Installation, Start-Up, and Operating Instructions.
8
8. Fix problem. 9
9. Go to the page number indicated in Index for the CLEANUP AND STARTUP
INSTRUCTIONS.
INDEX
- 14 -
STEP ACTION YES NO GO TO
10. Disconnect the R thermostat lead. 11
11. Do you have less than 19-vac across R and COM-24V on the variable speed furnace control? 12 13
12. Replace transformer. 9
13. The thermostat and/or thermostat wires are loading down the transformer. Replace the
thermostat or repair thermostat wires.
9
14. Does the hot surface ignitor HSI come on during the cycle? 15 19
15. Disconnect the humidifier lead from HUM terminal on variable speed furnace control. 16
16. Does the furnace still alternately cycle induced draft motor IDM and blower motor BLWM as
described in Step 4.
18 17
17. There is a direct short in wiring to humidifier solenoid coil, diode bridge(if used), or humidifier
solenoid coil.
8
18. There is a short in the gas valve GV or wiring to gas valve GV. Refer to Appendix E to check
gas valve GV.
8
19. There is a direct short in the ORANGE wire from the low heat pressure switch LPS. 8
20. While the unit is operating in low heat jumper R and W2 thermostat terminals. 21
21. Does the furnace abruptly shut down with no inducer post purge and then run blower motor
BLWM for 90 seconds while AMBER LED status light flashes status code 12.
22 26
22. Disconnect BROWN wire to gas valve GV. 23
23. Does the furnace still abruptly shut down as described in Step 21. 25 24
24. Replace gas valve. 9
25. There is a direct short to ground in the GRAY or BROWN wires connected to the high heat
pressure switch HPS.
8
26. Power to the furnace was probably interrupted or line voltage was too low during a call for
heat. This is normal operation. Go to the page number indicated in Index for the CLEANUP
AND STARTUP INSTRUCTIONS.
INDEX
Status Code 13
LIMIT CIRCUIT LOCKOUT – Lockout occurs if the limit or flame rollout switch is open longer than 3 minutes or 10 successive
limit trips occurred during high-heat. The variable speed furnace control will auto-reset in 3 hours. Flame roll-out switch FRS
requires manual-reset.
STEP ACTION YES NO GO TO
1. Remove the blower access panel. Disconnect User Interface ABCD connector (if used) or the
R thermostat lead (if used) from the furnace control board.
2
2. Depress the door switch. Use piece of tape to hold it closed. 3
3. Does status code 33 flash? 11 4
4. Does a different status code flash? 5 6
5. Go to page number indicated in the Index for the section covering the status code. INDEX
6. Jumper R and W/W1 thermostat terminals. 7
7. Observe the furnace operation for 25 minutes or until status code starts flashing. 8
8. Does status code 33 flash? 26 9
9. Does a different status code flash? 5 10
10. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
11. Is 24-vac across connector terminal PL1-6 and COM-24V on variable speed furnace control? 13 12
12. Replace the variable speed furnace control. 10
13. Is 24-vac across connector terminal PL1-8 and COM-24V on variable speed furnace control? 12 14
14. Turn power off. 15
15. Do you have continuity across limit switch LS? 17 16
16. Replace limit switch LS. 10
17. Do you have continuity across the flame rollout switch FRS? 25 18
18. Can flame rollout switch FRS be reset? 20 19
- 15 -
STEP ACTION YES NO GO TO
19. Replace flame rollout switch FRS. 10
20. Reset flame rollout switch FRS, turn power on, and observe furnace operation for (2) 15
minute cycles.
21
21. Does the flame rollout switch FRS trip again? 23 22
22. Does a different status code flash? 5 10
23. You have inadequate combustion-air supply. This may be caused by:
- Reversed vent and combustion-air pipes.
- Poor burner, manifold, or orifice alignment.
- Blocked heat exchanger.
- Leak somewhere between primary and secondary heat exchangers.
- Leak in secondary heat exchanger.
24
24. Fix problem 10
25. You have an open RED wire or bad terminal in limit circuit. Repair wire or replace harness. 10
26. Does furnace have the proper limit switch, limit shield, blower baffle (if used), and rear air
baffle (if used)? If so, are the limit switch, limit shield, and heat exchangers properly aligned?
27 24
27. Remove tape from door switch, turn power off at main disconnect, and remove jumper across
R and W/W1.
28
28. Is blower wheel firmly mounted on motor shaft? 29 24
29. Does the model plug PL4 match the part number specified on the Model Plug Chart in upper
left hand corner of wiring schematic?
31 30
30. Replace model plug. 10
31. Lockout may have been caused by excessive return-air restriction. Check all dampers, filters,
and return-air grilles for blockage. Add more return-air openings if necessary. Use Appendix
D to evaluate external static pressure. Reference status code 33 for additional troubleshooting
steps.
10
Status Code 14
IGNITION LOCKOUT - This status code indicates the furnace failed to ignite gas and/or prove flame in 4 attempts. The variable
speed furnace control will auto-reset in 3 hours. If the inducer motor is not running during lockout refer to status code 34.
If the inducer motor is running at full speed during lockout this indicates that flame sense was lost 3 times within 60 minutes of
cumulative gas valve operating time after the gas valve was already ON for 70 seconds. It is usually caused by flame rollout
that causes loss of flame sense before the flame rollout switch can trip.
Status Code 15
BLOWER MOTOR LOCKOUT - This status code indicates the blower failed to reach 250 RPM or the blower failed to
communicate to the variable speed furnace control within 30 seconds after being turned ON in two successive heating cycles.
Control will auto reset after 3 hours. Refer to status code 41.
Status Code 21
GAS HEATING LOCKOUT - This status code indicates the main gas valve relay MGVR on the variable speed furnace control is
stuck closed or there is a miswire/short to gas valve wiring. Make sure the BLUE wire goes to the gas valve M terminal and the
GREEN/YELLOW wire goes to the gas valve C terminal. The variable speed furnace control will NOT auto-reset.
STEP ACTION YES NO GO TO
1. Turn power off and disconnect User Interface ABCD connector (if used) or the R thermostat
lead (if used) from the furnace control board. Then turn power back on.
2
2. Does status code 21 flash? 3 6
3. There is a miswire or short to gas valve wiring. 4
4. Fix problem 5
5. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
6. Does a different status code flash? 7 8
- 16 -
STEP ACTION YES NO GO TO
7. Go to page number indicated in the Index for the section covering the status code. INDEX
8. Remove blower access panel and depress door switch. Use a piece of tape to hold switch
closed.
9
9. Jumper R and W/W1 thermostat terminals. 10
10. Does status code 21 start flashing when the low heat pressure switch LPS makes? 11 12
11. Replace the variable speed furnace control. 5
12. Does a different status code flash? 7 13
13. Disconnect the jumper wire across R and W/W1 thermostat terminals and wait until the blower
stops.
14
14. Jumper R, W/W1, and W2 thermostat terminals on the variable speed furnace control. 15
15. Does status code 21 start flashing when the high heat pressure switch HPS makes? 16 17
16. The BLUE and GREEN wires to gas valve GV are reversed. 4
17. Cycle the furnace several times to check for intermittent operation. 18
18. Does status code 21 ever flash? 11 19
19. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. If
the problem persists on an intermittent basis, replace the variable speed furnace control. If
problem still persists on an intermittent basis after replacing the variable speed furnace control,
contact your distributor.
INDEX
Status Code 22
ABNORMAL FLAME-PROVING SIGNAL - This status code indicates the flame signal was sensed while gas valve GV was de-
energized. The inducer will run until the fault is cleared.
STEP ACTION YES NO GO TO
1. Turn off gas to the furnace by shutting off the external manual shut-off valve. 2
2. Does status code 22 stop flashing? 3 4
3. Replace the gas valve. 8
4. Disconnect wire from the flame-proving sensor electrode FSE. 8
5. Does status code 22 stop flashing? 6 7
6. Clean flame sensor with fine steel wool. Inspect burner box assembly and remove any carbon
deposits near the flame sensor opening.
8
7. Replace the variable speed furnace control. 8
8. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
Status Code 23
PRESSURE SWITCH DID NOT OPEN - This status code indicates the low or high heat pressure switch LPS or HPS is made
when a call for heat is initiated. The variable speed furnace control will flash status code 23 until the switch opens, then cycle
begins.
STEP ACTION YES NO GO TO
1. Turn power off, remove blower access panel, and disconnect User Interface ABCD connector
(if used) or the R thermostat lead (if used) from the furnace control board.
2
2. Turn power on and depress door switch. Use a piece of tape to hold switch closed. 3
3. Jumper R and W/W1 thermostat terminals. 4
4. Does status code 23 flash? 8 5
5. Does a different status code flash? 6 7
6. Go to page number indicated in the Index for the section covering the status code. INDEX
7. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
8. Is the inducer motor ON? 21 9
9. Is 24-vac across ORANGE wire on the low heat pressure switch LPS and COM-24V on
variable speed furnace control?
16 10
10. Is 24-vac across connector terminal PL1-4 and COM-24V on variable speed furnace control? 11 13
11. The main harness is miswired. 7
12. Rewire low heat pressure switch LPS per the wiring diagram. 7
13. Is 24-vac across BROWN wire on the high heat pressure switch HPS and COM-24V on
variable speed furnace control?
18 14
14. Is 24-vac across connector terminal PL1-3 and COM-24V on variable speed furnace control? 11 15
- 17 -
STEP ACTION YES NO GO TO
15. Replace variable speed furnace control. 7
16. Is the low heat pressure switch LPS wired correctly? 17 12
17. Replace the pressure switch assembly. 7
18. Is the high heat pressure switch HPS wired correctly? 20 19
19. Rewire high heat pressure switch HPS per wiring diagram. 7
20. Replace the pressure switch assembly and replace the variable speed furnace control. 7
21. Check the inducer PWM line. To do this disconnect PL11 from the inducer motor and connect
a DC voltmeter across terminals PL11-2 BROWN (+) and PL11-10 YELLOW (-) then run
COMPONENT TEST by turning setup switch SW1-6 ON. Does voltage across PL11-2 and
PL11-10 change between states as shown below?
- State 1 – OFF (1.0 – 4.0 vdc)
- State 2 – MED (7.0 – 10.0 vdc)
22 15
22. Replace inducer motor or inducer motor assembly. 7
Status Code 24
SECONDARY VOLTAGE FUSE IS OPEN - Indicates fuse is open and there is a short in low-voltage wiring.
STEP ACTION YES NO GO TO
1. Turn power off and remove the blower access panel. 2
2. Is secondary voltage fuse blown? Check continuity to make sure. 5 3
3. Replace variable speed furnace control. 4
4. Replace secondary voltage fuse if necessary then go to page number indicated in Index for
CLEANUP AND START-UP INSTRUCTIONS.
INDEX
5. Disconnect User Interface ABCD connector (if used), or all thermostat leads (if used) from the
variable speed furnace control (including all wires connected to the HUM terminal) and
replace secondary voltage fuse.
6
6. Turn power on and depress door switch. Use a piece of tape to hold switch closed. 7
7. Does status code 24 flash? 8 12
8. Turn power off and disconnect PL1 from variable speed furnace control. 9
9. Do you have continuity between either RED wire connected to the limit circuit and chassis
ground?
10 3
10. You have a short circuit in the limit switch circuit. This includes limit switch LS, and flame
roll-out switch FRS.
11
11. Fix problem. 4
12. Disconnect the pressure tube from the collector box and jumper R and W/W1 thermostat
terminals.
13
13. Does status code 24 begin flashing when W/W1 is energized? 14 21
14. Turn power off and disconnect PL1 from variable speed furnace control. 15
15. Do you have continuity between the YELLOW wire connected to the low heat pressure switch
LPS and chassis ground?
16 3
16. You have a short circuit in the low heat pressure switch circuit. 11
17. Does status code 24 begin flashing when the HUM terminal is energized?
Note: On the variable speed furnace control the HUM terminal is energized when the blower
turns ON.
3 18
18. Disconnect jumper wire across R and W/W1 thermostat terminals and wait until inducer stops. 19
19. Disconnect the pressure tube from the collector box and jumper R, W/W1, and W2 thermostat
terminals.
20
20. Does status code 24 begin flashing when W/W1 is energized? 34 37
21. Reconnect the pressure tube from the pressure switch assembly back to the collector box. 22
22. Does status code 24 begin flashing when the low heat pressure switch LPS is energized? 23 26
23. Turn power off and disconnect PL1 from variable speed furnace control. 24
24. Do you have continuity between the ORANGE wire connected to the low heat pressure switch
LPS and chassis ground?
25 3
25. The ORANGE wire from low heat pressure switch LPS is shorting to ground. Replace or
repair it.
11
26. Does status code 24 begin flashing when the gas valve GV is energized? 27 17
- 18 -
STEP ACTION YES NO GO TO
27. Disconnect jumper wire across R and W/W1 thermostat terminals and replace secondary
voltage fuse.
28
28. Disconnect BLUE wire to gas valve GV and jumper R and W/W1 thermostat terminals. 29
29. Does status code 34 flash? If not, status code 24 should occur when BLUE wire is energized. 33 30
30. Turn power off and disconnect PL1 from variable speed furnace control. 31
31. Do you have continuity between the BLUE wire and chassis ground? 32 3
32. The BLUE wire to gas valve GV is shorting to ground. Replace or repair it. 11
33. Replace gas valve GV. 4
34. Turn power off and disconnect PL1 from variable speed furnace control. 35
35. Do you have continuity between the GRAY wire connected to the high heat pressure switch
HPS and chassis ground?
36 3
36. You have a short circuit in the high heat pressure switch circuit. 11
37. Reconnect the pressure tube from the pressure switch assembly back to the collector box. 38
38. Does status code 24 begin flashing when the high heat pressure switch HPS is energized? 39 56
39. Disconnect jumper wire across R, W/W1, and W2 thermostat terminals and replace secondary
voltage fuse.
40
40. Disconnect BROWN wire to gas valve GV and jumper R, W/W1, and W2 thermostat
terminals.
41
41. Does status code 24 begin flashing when the high heat pressure switch HPS is energized? 42 33
42. Turn power off and disconnect PL1 from variable speed furnace control. 43
43. Do you have continuity between the BROWN wire and chassis ground? 44 3
44. The BROWN wire to high heat pressure switch HPS and gas valve GV is shorting to ground.
Replace or repair it.
11
45. Disconnect jumper wire across R, W/W1, and W2 thermostat terminals and wait until blower
stops.
46
46. Jumper R, G, and Y/Y2 thermostat terminals. 47
47. Does status code 24 begin flashing when G and Y/Y2 are energized? 3 48
48. Reconnect User Interface ABCD connector (if used) or all thermostat leads (if used) to the
variable speed furnace control. Do not reconnect the humidifier lead to HUM terminal.
Operate the furnace in heating and cooling mode from thermostat.
49
49. Does status code 24 occur during heating cycle? 50 51
50. You have a defective thermostat or a short circuit in the wiring between thermostat and
furnace. If the furnace is twinned, also check the twinning kit relay TKR.
11
51. Does status code 24 occur during cooling cycle? 52 53
52. You have a defective thermostat or a short circuit in the wiring between thermostat and
outdoor unit, or a short circuit in the outdoor unit contactor or reversing valve(heat pump
only).
11
53. Does problem usually occur in cooling mode? 54 55
54. Check outdoor unit contactor. Failure to pull in can cause excessive current draw on low-
voltage circuit. This can be an intermittent problem.
11
55. Reconnect humidifier and check for excessive current draw when the blower turns ON. If
current draw is excessive check wiring to humidifier solenoid, diode bridge(if used), and
humidifier solenoid.
11
56. Continue to observe the furnace operation for 10 minutes. 57
57. Does status code 24 flash after the blower comes on? 58 59
58. The insulation is loose and has shorted against the limit switch(es). 11
59. Check for loose or torn insulation because it can cause intermittent occurrences of status code
24.
45
- 19 -
Status Code 25
MODEL SELECTION OR SETUP ERROR – If status code 25 only flashes 4 times on power-up the variable speed furnace
control is missing its model plug (PL4) and is defaulting to the model selection stored in memory.
If status code 25 flashes continuously it could indicate any of the following:
1. Model plug (PL4) is missing and there is no valid model stored in permanent memory. This will happen if you forget to
install the model plug (PL4) on a service replacement board.
2. Thermostat call with SW1-1 ON.
3. Thermostat call with SW1-6 ON.
4. SW1-1 and SW1-6 both ON together.
5. Two different furnace models twinned.
6. Board does not recognize 355BAV model plugs HK70EZ057 – 061. Furnace board date code 4106 or later required.
STEP ACTION YES NO GO TO
1. Turn power off, remove the blower access panel, and disconnect User Interface ABCD
connector (if used) or the R thermostat lead (if used) from the furnace control board.
2
2. Turn power on and depress door switch. Use a piece of tape to hold switch closed. 3
3. Does status code 25 flash only 4 times on power-up? 4 6
4. The model plug is missing or invalid but the control will default to the model stored in
memory. The furnace will operate properly as if the model plug was installed. If you have the
APM program you can confirm the setting in memory.
5
5. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
6. Is setup switch SW1-1 in the ON position? 7 8
7. Put setup switch SW1-1 in the OFF position. 5
8. Is setup switch SW1-6 in the ON position? 9 10
9. Put setup switch SW1-6 in the OFF position. 5
10. Is this a new service replacement control? 19 13
11. You need to remove the model plug PL4 from the old control and install it on the new
replacement control. Once you install the model plug the power to the furnace needs to be
reset because the model plug is only read on power-up.
12
12. If the model plug is not available from the old control, reference the model plug chart on the
wiring schematic for the correct part number. If absolutely necessary you can install two
resistors into the PL4 connection on the control board. R1 goes across the middle 2 pins and
R2 goes across the outer 2 pins. Reference the model plug chart on the schematic for the
correct resistance values. Resistors can be purchased at a nearby Radio Shack. The resistors
need to be within 10% of the stated value. Check with an ohm meter before installing.
5
13. Is this furnace twinned with another furnace? 14 17
14. Is the MAIN furnace flashing the status code? 15 17
15. Do the furnaces have the same model number on the rating plate? 18 16
16. Replace one of the furnaces because you cannot twin different size furnaces. 5
17. Replace the variable speed furnace control. 5
18. One of the model plugs is bad. Ohm out each one and replace the one that does not match the
model plug chart on the wiring schematic.
5
19. Is the model plug PL4 from the old control installed? 20 11
20. On 355BAV furnaces make sure you have installed a furnace control date code 4106 or later.
The date code is the last 4 digits printed after the board part number in the WHITE box near
the L2 terminals on the right side of the furnace control. Reference Figure 1 in Appendix A for
the location of the board date code.
5
Status Code 31
HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED - This status code can occur under the
scenarios shown below. Keep in mind that whenever the variable speed furnace control shuts unit down, gas remains off or
shuts off immediately, inducer continues running for 15 seconds, and if the blower is running, it remains running at low heat
airflow or reduces to low heat airflow for the selected off-delay. A miswired gas valve can cause this problem so make sure the
BLUE wire goes to the gas valve M terminal and the GREEN/YELLOW wire goes to the gas valve C terminal.
- LOW HEAT
1. PREPURGE OR STEADY-STATE - If the high heat pressure switch input turns ON the variable speed begins flashing status code 31 and
transitions to high heat. After the call for heat is satisfied and the blower off-delay is completed the control will stop displaying status code
31.
- 20 -
- HIGH HEAT
1. PREPURGE - If the high heat pressure switch HPS does not make within 45 seconds after the low-heat pressure switch LPS made the
variable speed begins flashing status code 31, shuts unit down, waits 2 minutes, stops flashing status code 31, and restarts heating cycle.
If high heat pressure switch HPS opens before ignition, the variable speed starts flashing status code 31 and ramps inducer RPM up until the
high heat pressure switch HPS remakes. When the high heat pressure switch HPS remakes the variable speed stops flashing status code 31
and continues heating cycle. If high heat pressure switch HPS does not remake within 45 sec after opening, the variable speed continues
flashing status code 31, shuts unit down, waits 2 minutes, stops flashing status code 31, and restarts heating cycle.
2. LOW HEAT TO HIGH HEAT TRANSITION - If the high heat pressure switch HPS fails to make within 45 seconds after high heat was
requested the variable speed furnace control shuts unit down and begins flashing status code 31. After the blower off-delay is completed the
variable speed will stop displaying status code 31 and if there is a call for heat, begin a new heating cycle. This new heating cycle will be
restricted to high heat.
3. STEADY-STATE - If the high heat pressure switch HPS opens the variable speed starts flashing status code 31 and ramps inducer RPM up
until the high heat pressure switch HPS remakes. When the high heat pressure switch HPS remakes the variable speed stops flashing status
code 31 and continues heating cycle. If high heat pressure switch HPS does not remake within 45 sec after opening, the variable speed shuts
the unit down and continues flashing status code 31. After the blower off-delay is completed the variable speed will stop displaying status
code 31 and if there is a call for heat, begin a new heating cycle. This new heating cycle will be restricted to high heat.
4. HIGH HEAT TO LOW HEAT TRANSITION – When using a 2-stage thermostat and W2 is de-energized, the high heat pressure switch
HPS must open within 5 seconds. If the high heat pressure switch HPS does not open within 5 seconds after W2 is de-energized, the variable
speed switches back to high heat and starts flashing status code 31. After the call for heat is satisfied and the blower off-delay is completed
the variable speed will stop displaying status code 31.
STEP ACTION YES NO GO TO
1. Turn power off, remove blower access panel, and disconnect User Interface ABCD connector
(if used) or the R thermostat lead (if used) from the furnace control board.
2
2. Turn power on and depress door switch. Use a piece of tape to hold switch closed. 3
3. Jumper R, W/W1, and W2 thermostat terminals. 4
4. Wait 90 seconds before proceeding to the next step. 5
5. Does status code 31 flash? 9 6
6. Does a different status code flash? 7 34
7. Go to page number indicated in the Index for the section covering the status code. INDEX
8. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
9. Is 24-vac across GRAY wire on the high heat pressure switch HPS and COM-24V on variable
speed furnace control?
15 10
10. Is 24-vac across connector terminal PL1-12 and COM-24V on variable speed furnace control? 11 13
11. You have an open wire or bad terminal on the GRAY wire from the variable speed furnace
control to the high heat pressure switch HPS.
12
12. Repair or replace the main wire harness. 8
13. Replace the variable speed furnace control. 8
14. The problem is caused by reversed vent and combustion-air pipes or some other moist air
entering combustion-air pipe.
32
15. Does the high heat pressure switch HPS make, then break several times at start of cycle before
faulting out?
16 17
16. The problem is either a sag in vent pipe or a clogged drain trap or line. Also check for
improperly plumbed drainage tubing within furnace.
32
17. Is 24-vac across BROWN wire on the high heat pressure switch HPS and COM-24V on
variable speed furnace control?
18 20
18. Is 24-vac across connector terminal PL1-3 and COM-24V on variable speed furnace control? 13 19
19. You have an open wire or bad terminal on the BROWN wire from the high heat pressure
switch HPS to the variable speed furnace control.
12
20. Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals. 21
21. Connect 1 side of slope manometer with a tee to collector box pressure tap. Connect other side
with a tee to gas valve pressure fitting. Refer to pressure check diagram in Appendix C.
22
22. Turn power on and jumper R, W/W1, and W2 thermostat terminals. 23
23. Do you have atleast 1.90 in. wc pressure drop across heat exchangers when status code 31
flashes?
24 25
24. Replace the pressure switch assembly. 8
25. Is inducer motor rotating in direction indicated on inducer housing? 27 26
26. Replace inducer motor or inducer motor assembly. 8
27. Turn power off. 28
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Bryant 355AAV EVOLUTION Troubleshooting guide

Category
Water heaters & boilers
Type
Troubleshooting guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI