Raychem PMK-JLP-M Installation guide

Type
Installation guide
PMK-JLP-M
Monitor Wire Power Connection Kit Installation Instructions
nVent.com
nVent.com
nVent.com LLC
DESCRIPTION
The nVent RAYCHEM PMK-JLP-M is a Type 4X-rated power
connection kit designed for use with RAYCHEM BTV-MCT, QTVR-MCT
and XTV-MCT industrial parallel monitor wire heating cables. This kit
may be installed at temperatures as low as –40°F (–40°C). For easier
installation store above freezing until just before installation.
For technical support call nVent at (800)545-6258.
TOOLS REQUIRED
Wire strippers Heat gun or propane torch
Diagonal cutters Utility knife
Needle-nose pliers
Flatblade screwdrivers, 1/8 & 1/4 inch
ADDITIONAL MATERIALS REQUIRED
1 Grommet (see selection chart on page 2)
1 Pipe strap (order separately)
Glass cloth tape
- GT-66 Installation temperature above 40°F (4°C)
- GS-54 Installation temperature above -40°F (-40°C)
This component is an electrical device that must be installed
correctly to ensure proper operation and to prevent shock or
fire. Read these important warnings and carefully follow all of
the installation instructions.
To minimize the danger of fire from sustained electrical
arcing if the heating cable is damaged or improperly
installed, and to comply with the requirements of nVent,
agency certifications, and national electrical codes, ground-
fault equipment protection must be used. Arcing may not
be stopped conventional circuit breakers.
Approvals and performance are based on the use of nVent-
specified parts only. Do not use substitute parts or vinyl
electrical tape.
The black heating cable core and fibers are conductive and
can short. They must be properly insulated and kept dry.
Connection kits and heating cable ends must be kept dry
before and during installation.
Damaged bus wires can overheat or short. Do not break
bus wire strands when scoring the jacket orcore.
Use only fire-resistant insulation materials, such as
fiberglass wrap or flame-retardant foam.
Heat damaged components can short. Use a heat gun or
torch with a soft, yellow, low-heat flame. Keep the flame
moving to avoid overheating, blistering, or charring the heat-
shrinkable tubes. Avoid heating other components. Replace
any damaged parts.
HEALTH HAZARD: Over heating heat-shrinkable tubes
will produce fumes that may cause irritation. Use adequate
ventilation and avoid charring or burning. Consult MSDS
RAY3122 for further information.
CHEMTREC 24-hour emergency telephone:
(800) 424-9300
Non-emergency health and safety information:
(800) 545-6258
WARNING:
CAUTION:
KIT CONTENTS
Item Qty Description
A 1 Junction box lid
B 1 Junction box
C 1 4-pole terminal block
D 2 Black heat-shrinkable tubes
E 1 Green/yellow heat-shrinkable tube
F 1 Clear yellow heat-shrinkable tube
G 1 Locknut
H 1 Sealing ring
I 1 Top (3/4 inch NPS thread)
J 1 Base
D
E
F
G
H
I
J
A
B
C
nVent
.
com
nVent.com
L
L
C
APPROVALS
Class I, Div. 2, Groups B, C, D
Class II, Div. 2, Groups F, G
Class III
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 2, Groups F, G
Class III
Hazardous Locations
-ws
2 | nVent.com
Inner jacket
Braid
Outer jacket
Plastic wrap
Spacer
Conductive fiber
XTV-MCT
Bus wire
BTV-MCT, QTVR-MCT
Bus wire
Conductive core
Inner jacket
Braid
Outer jacket
Monitor
wire
Monitor wire
IDENTIFY HEATING CABLE TYPE
1
Heating cable Grommet
3BTV1-MCT N
3BTV2-MCT N
5BTV1-MCT N
5BTV2-MCT N
10BTV1-MCT F
10BTV2-MCT F
10QTVR1-MCT G
10QTVR2-MCT G
20QTVR1-MCT F
20QTVR2-MCT F
Heating cable Grommet
5XTV1-MCT-T3 N
5XTV2-MCT-T3 N
10XTV1-MCT-T3 N
10XTV2-MCT-T3 N
15XTV1-MCT-T2 N
15XTV2-MCT-T3 N
20XTV1-MCT-T2 N
20XTV2-MCT-T2 N
Determine correct grommet (order separately) from
chartbelow.
WARNING: Use of the wrong grommet can result in
leaks, cracked components, shock or fire, and will
invalidate approvals and certifications.
18 in
(46 cm)
2
Allow approximately 18 in (46 cm) of heating cable
forinstallation.
3
Slide parts onto heating cable.
7 1/2 in
(190 mm)
4
Lightly score
outer jacket.
Bend heating cable to
break jacket at score,
then peel off jacket.
WARNING: Do not cut through braid into inner jacket.
This could result in a short circuit.
nVent.com | 3
7
For XTV-MCT Only:
Remove plastic wrap.
5
Push braid back toward outer jacket
to create a pucker.
At pucker, open braid
using screwdriver.
9 1/2 in
(241 mm)
Monitor wire
Lightly score partially
around inner jacket
as shown. Do not
score jacket over
monitor wire.
WARNING: Damaged monitor wire insulation can cause
a short. Do not score inner jacket next to the monitor
wire.
Bend heating cable to break jacket at score, then peel off
jacket. Use diagonal cutters to remove remaining jacket next
to monitor wire.
9ABTV-MCT AND QTVR-MCT
Go to Page 4, Step 9B
Go to Step 9A
BTV-MCT, QTVR-MCT
XTV-MCT
8
6
Bend heating cable and work it through opening in braid.
Determine heating cable type and continue as shown.
1/4 in
(6 mm)
Notch core.
Peel bus wire from core.
10ABTV-MCT AND QTVR-MCT
4 | nVent.com
6 1/2 in
(165 mm)
WARNING: Do not cut or damage bus wires.
Damaged bus wires can overheat or short.
9BXTV-MCT
Cut and remove fiber strands.
10BXTV-MCT
Go to Step 12
11ABTV-MCT AND QTVR-MCT
Score core between bus wires and
inner jacket.
Bend and snap core.
Peel core from bus wires and remove any
remaining material from bus wires.
Lightly score
around inner
jacket as shown.
Be careful not to
cut monitor wire
insulation.
11BXTV-MCT
1/2 in
(13 mm)
12
Remove insulation from end of monitor
wire. Do not cut wire strands.
Score and remove center spacer.
Remove any remaining fiber
material from bus wires.
Bend heating cable to
break jacket at score,
then peel off jacket.
nVent.com | 5
15
1 in
(25 mm)
16
Seat grommet and
position parts so
that 1 in. (25 mm) of
heating cable outer
jacket extends past
top of threads.
Tighten screws.
Pipe strap
17
Fasten base to pipe with
strap.
Loop and tape extra
heating cable to pipe.
Install sealing ring.
18
Install box with locknut.
Instructions for Using a Heat Gun or Torch:
Read important warnings on Page 1 and follow safety
precautions provided with heat gun or torch.
When using a torch use a soft yellow, low-heat flame. Apply
just enough heat to do the job.
Keep torch or heat gun moving continuously to distribute the
heat evenly to avoid overheating, blistering or charring the
heating cable and heat-shrinkable tubes.
Replace any heat-damaged parts.
13
Slide two black
tubes onto bus
wires and green/
yellow tube onto
braid.
1/2 in
(13 mm)
14
Center clear yellow tube over end of base jacket.
Heat tube until it shrinks and adhesive flows out ends.
While still hot, pinch between wires and hold for 5 seconds.
Use a heat gun or propane torch to heat tubes until they
are fully recovered.
Note: See Step 15 for proper heating
techniques.
120/277 Vac shown
Signal light or other
monitoring device.
Terminal block
Ø
N
Ground
End seal connection
for -MCT heating cable
Braid
Monitor wire
Heating cable bus wires
Connect wires to terminal block.
19
Weather seal
Insulation
Use a conduit drain
to prevent condensation
and water build-up
nVent.com
nVent.com LLC
nVent.com
nVent.com LLC
nVent.com
20
Install lid.
Apply insulation and cladding.
Weather-seal the stand entry.
Leave these installation instructions with the end user for
future reference.
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
Raychem-IM-H54055-PMKJLPM-EN-1805
nVent.com
PN 198417-000
NORTH AMERICA
Tel: +1.800.545.6258
Fax: +1.800.527.5703
EUROPE, MIDDLE EAST, AFRICA
Tel: +32.16.213.511
Fax: +32.16.213.604
ASIA PACIFIC
Tel: +86.21.2412.1688
Fax: +86.21.5426.3167
LATIN AMERICA
Tel: +1.713.868.4800
Fax: +1.713.868.2333
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Raychem PMK-JLP-M Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI