  • Hello! I am an AI chatbot trained to assist you with the Dell PowerEdge PDU Managed LED Owner's manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!

Cabling the Dell™
PowerEdge™ R610
ADellTechnicalWhitePaper
By Chris M. Kitten and Jose L. Flores
Dell Datacenter Infrastructure Engineering
March 2009
CablingtheDell™PowerEdge™R610
Pageii
THISWHITEPAPERISFORINFORMATIONALPURPOSESONLY,ANDMAYCONTAINTYPOGRAPHICALERRORSAND
TECHNICALINACCURACIES.THECONTENTISPROVIDEDASIS,WITHOUTEXPRESSORIMPLIEDWARRANTIESOF
ANYKIND.
©2009DellInc.Allrightsreserved.Reproductionofthis
materialinanymannerwhatsoeverwithouttheexpress
writtenpermissionofDellInc.isstrictlyforbidden.Formoreinformation,contactDell.
Dell,theDELLlogo,theDELLbadge,andPowerEdge,aretrademarksofDellInc.
CablingtheDell™PowerEdge™R610
Page1
Table of Contents
Introduction...............................................................................................................................................................2
CablingaPowerEdgeR610withCMA.......................................................................................................................2
2.1InstallingtheCablestotheSystem..........................................................................................................2
Figure1:SystemwithCablesInstalled.....................................................................................................2
2.2RoutethePowerCablesthroughtheStrainReliefs..................................................................................3
Figure2:RoutingPowerCablesthroughtheStrainReliefs....................................................................3
2.3RoutingtheCablesthroughtheCMA........................................................................................................3
Figure3:RoutingtheCablesthroughtheCMA.......................................................................................4
Figure4:AttachingtheKVMDongletotheCMABasket.........................................................................4
Figure5:CompletedLeftSideMountedCMAInstallation.......................................................................5
Figure6:CompletedRightSideMountedCMAInstallation....................................................................5
CablingaPowerEdgeR610withoutaCMA...............................................................................................................6
3.1RoutingtheCables....................................................................................................................................6
Figure7:CableRoutingWithoutaCMA..................................................................................................6
3.1RemovingtheCMABracketsforShallowRacks........................................................................................6
Figure8:RemovingtheCMABracketsforShallowRacks........................................................................6
ReplacingaPowerSupplyonaPowerEdgeR610withCMA.....................................................................................7
Figure9:ReplacingOuterPowerSupply..................................................................................................7
CablingaPowerEdgeR610InstalledinStaticRails...................................................................................................8
Figure10:CablingaSystemInstalledinStaticRails................................................................................8

CablingtheDell™PowerEdge™R610
Page2
Introduction
Thiswhitepaperdescribesrecommendedcableroutingprocedures,bothwithandwithouttheoptionalCable
ManagementArm(CMA)fortheDell™PowerEdge™R610inthefollowingracks:
PowerEdge4210
PowerEdge2410
PowerEdge4220
PowerEdge2420
IfusingtheoptionalCMA,followingtheseprocedureswillallowyouto
extendthesystemfromtherackforservice
withoutpoweringdownordisconnectingthecables.IfnotusingtheCMA,followingtheseprocedureswillensure
secureattachmentandstrainreliefofthecablesbehindthesystem.Forguidelinesonhowtoroutecableswithin
therack,refertotheDell
WhitePaper“BestPracticesGuideforRackEnclosure.”
CablingaPowerEdgeR610withCMA
ThissectiondetailshowtocableaPowerEdgeR610usingaCMA.Ifyouarecablingthesystemwithoutthe
optionalCMA,pleasereferto“CablingaPowerEdgeR610withoutaCMA”laterinthiswhitepaper.
FollowtheinstructionscontainedintheRackInstallationGuidefoundintherailkit
toinstalltheserverintothe
rackandtoinstallthecables.AllillustrationsinthefollowingsectionswerecreatedusingaPowerEdgeR610.
NOTE:ThePowerEdgeR610isnotcompatiblewithpreviousgenerationrailsandCMAs.
2.1InstallingtheCablestotheSystem
AttachtheCMAtraytothebackoftherailsasdescribedintheCMAInstallationInstructionsprovidedintheCMA
kit.Pluginallapplicablecablestotherearofthesystemandverifythatallconnectionsaresecure.SeeFigure1.
Figure1:SystemwithCablesInstalled
CablingtheDell™PowerEdge™R610
Page3
2.2RoutethePowerCablesthroughtheStrainReliefs
Afterthetrayandcablesareinstalled,routethepowercablesthroughthestrainreliefslocatedonthepower
supplyhandlesasshowninFigure2.
Figure2:RoutingPowerCablesthroughtheStrainReliefs
2.3RoutingtheCablesthroughtheCMA
NOTE:TheCMAcanbeinstalledoneithertherightorleftrearsideoftherails.MountingtheCMAontheside
oppositethepowersupplies(leftsidemount)isrecommended;otherwise,theCMAmustbedisconnectedinorder
toremovetheouterpowersupply.Referto“ReplacingaPower
SupplyonaPowerEdgeR610withCMA”laterin
thiswhitepaperfordetailsonpowersupplyreplacement.
NOTE:Forguidelinesonhowtoroutecableswithintherack,refertotheDellWhitePaper“BestPracticesGuide
forRackEnclosures”.
LeftSideMountingInstructions
1. InstalltheCMAontheleftrearsideoftherailsbyattachingbothCMAhousingstotheattachmentbracketson
therails.SeeFigure3.
2. RoutethecablesthroughtheCMAwhilekeepinganytwistingofthecablestoaminimum.Usethehookand
loopstrapsontheCMAtosecurethe
cables.
CablingtheDell™PowerEdge™R610
Page4
Figure3:RoutingtheCablesthroughtheCMA
3. IfthecablebundleincludesaKVMdongle,placethedongleinsidetheCMAbasket.IftheKVMdonglewillnot
fitinsidethebasketwiththeothercables,attachthedongletotheexteriorofthefrontbasketusingthehook
andloopstraps
ontheCMAbasketasshowninFigure4.
Figure4:AttachingtheKVMDongletotheCMABasket
KVM Dongle
hook and loop straps
Cables entering CMA should
have a small amount of slack to
avoid cable strain when CMA is
extended.
NOTE: Do not store excess cable
slack inside the CMA. The cable may
protrude through the CMA causing
binding and potentially damaging the
cable.
CablingtheDell™PowerEdge™R610
Page5
4. OnceallthecablesareroutedthroughtheCMA,dressthecablesbetweenthebackofthesystemandthe
entranceoftheCMAwiththetiewrapsprovidedintheCMAkit.Thetiewrapsareshowninyellowinall
illustrations.
5. Clipoff
theexcesslengthofmaterialfromthetiewrapsandmakesurethatthetiewrapsarepositionedto
avoidinterferencewithadjacentsystems.
6. ReturntheCMAtotheclosed(retracted)position.
7. Extendthesystemfromtheracktoverifythereissufficientslackinthecablesatboth
theentranceandexitof
theCMA.
8. SeeFigure5foranexampleofacompletedleftsidemountedCMAinstallation.
Figure5:CompletedLeftSideMountedCMAInstallation
RightSideMountingInstructions
InstalltheCMAontherightrearsideoftherailsbyattachingbothCMAhousingstotheattachmentbracketson
therails.Followsteps27fromtherightsidemountinginstructionsintheprevioussection.SeeFigure6foran
exampleofacompletedright
sidemountedCMAinstallation.
Figure6:CompletedRightSideMountedCMAInstallation
CablingtheDell™PowerEdge™R610
Page6
CablingaPowerEdgeR610withoutaCMA
NOTE:TheCMAontheDellPowerEdgeR610isoptional.WithouttheCMAinstalled,thesystemmustbepowered
downandallcablesdisconnectedbeforeitcanberemovedfromtherack.
3.1RoutingtheCables
1. Pluginallapplicablecablestotherearofthesystem,verifyingthatallconnectionsaresecure.
2. Usingthehookandloopstrapssuppliedwiththerailkit,bundlethecablesandsecurethemtoeithertheleft
railorrightrailCMAattachmentbracketsasdescribedinthe
RackInstallationGuide.SeeFigure7foran
exampleofpowercablessecuredtotheleftCMAbracketanddatacablessecuredtotherightCMAbracket.
3. Itisrecommendedthatthecablesbesecuredtotheouterbrackets,butcablesmaybesecuredtotheinner
bracketsif
desired.
Figure7:CableRoutingWithoutaCMA
3.1 RemovingtheCMABracketsforShallowRacks
Ifyouareinstallingthesystemintoashallowrack(lessthan1mdeep)andyouwillnotbeinstallingaCMA,the
outerCMAbracketsmayberemoved,enablingtherailstofitintotherack.RemovetheouterCMAbracketsby
removingbothscrewswitha#2Philipsscrewdriver
asshowninFigure8.
Figure8:RemovingtheCMABracketsforShallowRacks
CablingtheDell™PowerEdge™R610
Page7
ReplacingaPowerSupplyonaPowerEdgeR610withCMA
1. RemovethetrayfromundertheCMAasdescribedintheCMAInstallationInstructionsprovidedwiththeCMA
kit.
2. SwingtheCMAintotheserviceposition.
3. Disconnectthepowercordfromthepowersupplyanddisengagethestrainrelief.
4. Removeandreplacethepowersupply
a. If
theCMAisattachedtotheleftside,bothpowersuppliescanberemovedwithoutdisconnecting
theCMA.
b. IftheCMAisattachedtotherightsideandtheinnerpowersupplyneedstobereplaced,theCMA
doesnotneedtobedisconnected.
c. IftheCMAis
attachedtotherightsideandtheouterpowersupplyneedstobereplaced,theinner
CMAattachmenthousingwillneedtobedisconnected.WhilesupportingtheCMAwithonehand,
removeandreplacethepowersupplywiththeotherhandasshowninFigure9.
Figure9:ReplacingOuterPowerSupply
5. Pluginthepowercord.
6. Reengagethestrainrelief.
7. ReturntheCMAtotheclosed(retracted)position.
Inner CMA attachment housing has
been disconnected
CablingtheDell™PowerEdge™R610
Page8
CablingaPowerEdgeR610InstalledinStaticRails
NOTE:TheCMAisonlycompatiblewithslidingrails,andnotwithstaticrails.
1. FollowtheinstructionscontainedintheRackInstallationGuidefoundinthestaticrailkittoinstalltheserver
intoa2postor4postrack.
2. Verifythatthehookandloopsstrapsprovided
withthestaticrailkitareinstalledtotherearoftherails.
3. Pluginallapplicablecablestotherearofthesystemandverifythatallconnectionsaresecure.
4. Usingthehookandloopstrapssuppliedwiththerailkit,bundlethecablesandsecurethem
toeithertheleft
railorrightrailasdescribedintheRackInstallationGuide.SeeFigure10.
Figure10:CablingaSystemInstalledinStaticRails

/