March 2009
CablingtheDell™PowerEdge™R610
Pageii
THISWHITEPAPERISFORINFORMATIONALPURPOSESONLY,ANDMAYCONTAINTYPOGRAPHICALERRORSAND
TECHNICALINACCURACIES.THECONTENTISPROVIDEDASIS,WITHOUTEXPRESSORIMPLIEDWARRANTIESOF
ANYKIND.
©2009DellInc.Allrightsreserved.Reproductionofthis
materialinanymannerwhatsoeverwithouttheexpress
writtenpermissionofDellInc.isstrictlyforbidden.Formoreinformation,contactDell.
Dell,theDELLlogo,theDELLbadge,andPowerEdge,aretrademarksofDellInc.
CablingtheDell™PowerEdge™R610
Page1
Table of Contents
Introduction...............................................................................................................................................................2
CablingaPowerEdgeR610withCMA.......................................................................................................................2
2.1InstallingtheCablestotheSystem..........................................................................................................2
Figure1:SystemwithCablesInstalled.....................................................................................................2
2.2RoutethePowerCablesthroughtheStrainReliefs..................................................................................3
Figure2:RoutingPowerCablesthroughtheStrainReliefs....................................................................3
2.3RoutingtheCablesthroughtheCMA........................................................................................................3
Figure3:RoutingtheCablesthroughtheCMA.......................................................................................4
Figure4:AttachingtheKVMDongletotheCMABasket.........................................................................4
Figure5:CompletedLeftSideMountedCMAInstallation.......................................................................5
Figure6:CompletedRightSideMountedCMAInstallation....................................................................5
CablingaPowerEdgeR610withoutaCMA...............................................................................................................6
3.1RoutingtheCables....................................................................................................................................6
Figure7:CableRoutingWithoutaCMA..................................................................................................6
3.1RemovingtheCMABracketsforShallowRacks........................................................................................6
Figure8:RemovingtheCMABracketsforShallowRacks........................................................................6
ReplacingaPowerSupplyonaPowerEdgeR610withCMA.....................................................................................7
Figure9:ReplacingOuterPowerSupply..................................................................................................7
CablingaPowerEdgeR610InstalledinStaticRails...................................................................................................8
Figure10:CablingaSystemInstalledinStaticRails................................................................................8

CablingtheDell™PowerEdge™R610
Page2
Introduction
Thiswhitepaperdescribesrecommendedcableroutingprocedures,bothwithandwithouttheoptionalCable
ManagementArm(CMA)fortheDell™PowerEdge™R610inthefollowingracks:
PowerEdge4210
PowerEdge2410
PowerEdge4220
PowerEdge2420
IfusingtheoptionalCMA,followingtheseprocedureswillallowyouto
extendthesystemfromtherackforservice
withoutpoweringdownordisconnectingthecables.IfnotusingtheCMA,followingtheseprocedureswillensure
secureattachmentandstrainreliefofthecablesbehindthesystem.Forguidelinesonhowtoroutecableswithin
therack,refertotheDell
WhitePaper“BestPracticesGuideforRackEnclosure.”
CablingaPowerEdgeR610withCMA
ThissectiondetailshowtocableaPowerEdgeR610usingaCMA.Ifyouarecablingthesystemwithoutthe
optionalCMA,pleasereferto“CablingaPowerEdgeR610withoutaCMA”laterinthiswhitepaper.
FollowtheinstructionscontainedintheRackInstallationGuidefoundintherailkit
toinstalltheserverintothe
rackandtoinstallthecables.AllillustrationsinthefollowingsectionswerecreatedusingaPowerEdgeR610.
NOTE:ThePowerEdgeR610isnotcompatiblewithpreviousgenerationrailsandCMAs.
2.1InstallingtheCablestotheSystem
AttachtheCMAtraytothebackoftherailsasdescribedintheCMAInstallationInstructionsprovidedintheCMA
kit.Pluginallapplicablecablestotherearofthesystemandverifythatallconnectionsaresecure.SeeFigure1.
Figure1:SystemwithCablesInstalled
CablingtheDell™PowerEdge™R610
Page3
2.2RoutethePowerCablesthroughtheStrainReliefs
Afterthetrayandcablesareinstalled,routethepowercablesthroughthestrainreliefslocatedonthepower
supplyhandlesasshowninFigure2.
Figure2:RoutingPowerCablesthroughtheStrainReliefs
2.3RoutingtheCablesthroughtheCMA
NOTE:TheCMAcanbeinstalledoneithertherightorleftrearsideoftherails.MountingtheCMAontheside
oppositethepowersupplies(leftsidemount)isrecommended;otherwise,theCMAmustbedisconnectedinorder
toremovetheouterpowersupply.Referto“ReplacingaPower
SupplyonaPowerEdgeR610withCMA”laterin
thiswhitepaperfordetailsonpowersupplyreplacement.
NOTE:Forguidelinesonhowtoroutecableswithintherack,refertotheDellWhitePaper“BestPracticesGuide
forRackEnclosures”.
LeftSideMountingInstructions
1. InstalltheCMAontheleftrearsideoftherailsbyattachingbothCMAhousingstotheattachmentbracketson
therails.SeeFigure3.
2. RoutethecablesthroughtheCMAwhilekeepinganytwistingofthecablestoaminimum.Usethehookand
loopstrapsontheCMAtosecurethe
cables.
CablingtheDell™PowerEdge™R610
Page4
Figure3:RoutingtheCablesthroughtheCMA
3. IfthecablebundleincludesaKVMdongle,placethedongleinsidetheCMAbasket.IftheKVMdonglewillnot
fitinsidethebasketwiththeothercables,attachthedongletotheexteriorofthefrontbasketusingthehook
andloopstraps
ontheCMAbasketasshowninFigure4.
Figure4:AttachingtheKVMDongletotheCMABasket
KVM Dongle
hook and loop straps
Cables entering CMA should
have a small amount of slack to
avoid cable strain when CMA is
extended.
NOTE: Do not store excess cable
slack inside the CMA. The cable may
protrude through the CMA causing
binding and potentially damaging the
cable.
CablingtheDell™PowerEdge™R610
Page5
4. OnceallthecablesareroutedthroughtheCMA,dressthecablesbetweenthebackofthesystemandthe
entranceoftheCMAwiththetiewrapsprovidedintheCMAkit.Thetiewrapsareshowninyellowinall
illustrations.
5. Clipoff
theexcesslengthofmaterialfromthetiewrapsandmakesurethatthetiewrapsarepositionedto
avoidinterferencewithadjacentsystems.
6. ReturntheCMAtotheclosed(retracted)position.
7. Extendthesystemfromtheracktoverifythereissufficientslackinthecablesatboth
theentranceandexitof
theCMA.
8. SeeFigure5foranexampleofacompletedleftsidemountedCMAinstallation.
Figure5:CompletedLeftSideMountedCMAInstallation
RightSideMountingInstructions
InstalltheCMAontherightrearsideoftherailsbyattachingbothCMAhousingstotheattachmentbracketson
therails.Followsteps27fromtherightsidemountinginstructionsintheprevioussection.SeeFigure6foran
exampleofacompletedright
sidemountedCMAinstallation.
Figure6:CompletedRightSideMountedCMAInstallation
CablingtheDell™PowerEdge™R610
Page6
CablingaPowerEdgeR610withoutaCMA
NOTE:TheCMAontheDellPowerEdgeR610isoptional.WithouttheCMAinstalled,thesystemmustbepowered
downandallcablesdisconnectedbeforeitcanberemovedfromtherack.
3.1RoutingtheCables
1. Pluginallapplicablecablestotherearofthesystem,verifyingthatallconnectionsaresecure.
2. Usingthehookandloopstrapssuppliedwiththerailkit,bundlethecablesandsecurethemtoeithertheleft
railorrightrailCMAattachmentbracketsasdescribedinthe
RackInstallationGuide.SeeFigure7foran
exampleofpowercablessecuredtotheleftCMAbracketanddatacablessecuredtotherightCMAbracket.
3. Itisrecommendedthatthecablesbesecuredtotheouterbrackets,butcablesmaybesecuredtotheinner
bracketsif
desired.
Figure7:CableRoutingWithoutaCMA
3.1 RemovingtheCMABracketsforShallowRacks
Ifyouareinstallingthesystemintoashallowrack(lessthan1mdeep)andyouwillnotbeinstallingaCMA,the
outerCMAbracketsmayberemoved,enablingtherailstofitintotherack.RemovetheouterCMAbracketsby
removingbothscrewswitha#2Philipsscrewdriver
asshowninFigure8.
Figure8:RemovingtheCMABracketsforShallowRacks
CablingtheDell™PowerEdge™R610
Page7
ReplacingaPowerSupplyonaPowerEdgeR610withCMA
1. RemovethetrayfromundertheCMAasdescribedintheCMAInstallationInstructionsprovidedwiththeCMA
kit.
2. SwingtheCMAintotheserviceposition.
3. Disconnectthepowercordfromthepowersupplyanddisengagethestrainrelief.
4. Removeandreplacethepowersupply
a. If
theCMAisattachedtotheleftside,bothpowersuppliescanberemovedwithoutdisconnecting
theCMA.
b. IftheCMAisattachedtotherightsideandtheinnerpowersupplyneedstobereplaced,theCMA
doesnotneedtobedisconnected.
c. IftheCMAis
attachedtotherightsideandtheouterpowersupplyneedstobereplaced,theinner
CMAattachmenthousingwillneedtobedisconnected.WhilesupportingtheCMAwithonehand,
removeandreplacethepowersupplywiththeotherhandasshowninFigure9.
Figure9:ReplacingOuterPowerSupply
5. Pluginthepowercord.
6. Reengagethestrainrelief.
7. ReturntheCMAtotheclosed(retracted)position.
Inner CMA attachment housing has
been disconnected
CablingtheDell™PowerEdge™R610
Page8
CablingaPowerEdgeR610InstalledinStaticRails
NOTE:TheCMAisonlycompatiblewithslidingrails,andnotwithstaticrails.
1. FollowtheinstructionscontainedintheRackInstallationGuidefoundinthestaticrailkittoinstalltheserver
intoa2postor4postrack.
2. Verifythatthehookandloopsstrapsprovided
withthestaticrailkitareinstalledtotherearoftherails.
3. Pluginallapplicablecablestotherearofthesystemandverifythatallconnectionsaresecure.
4. Usingthehookandloopstrapssuppliedwiththerailkit,bundlethecablesandsecurethem
toeithertheleft
railorrightrailasdescribedintheRackInstallationGuide.SeeFigure10.
Figure10:CablingaSystemInstalledinStaticRails

  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9