DC26-12A

Fullriver Battery DC26-12A Operating instructions

  • Hello! I've reviewed the Fullriver Battery charging instructions. This document details a voltage-regulated charging process, complete with specifications for bulk, absorption, and float stages, as well as temperature compensation settings. I'm ready to assist you with any questions you might have about how to properly charge your Fullriver battery.
  • What is the recommended initial charge current?
    What is the maximum absorption time?
    What is the minimum float time?
    What is the temperature coefficient?
0.35
0.30
0.25
CURRENT (X C20 RATE)
VOLTAGE PER CELL
CHARGING TIME: NO LIMIT
BULK ABSORPTION
U = 2.45V/Cell (+/- .025V/Cell)
0
Current will taper down
I = 0.15 - 0.35 x C
1 20
I = 0.012 - 0.02 x C
2 20
Minimum float time = 8 hrs.
Maximum absorption time = 8 hrs.
Temperature: 25˚C (77˚F)
FLOAT
0.20
0.15
0.10
0.05
0.00
2.70
2.60
2.50
2.40
2.30
2.20
2.10
2.00
Temperature Coefficient: -4mV/ C/cell (-2mV/ F/cell)
0 0
U = 2.275V/Cell (+/- .025V/Cell)
FIGURE 1
CHARGE VOLTAGE REFERENCE
For a 6V battery, divide the voltage by 2.
REFRESH CHARGE
If Fullriver batteries are properly charged they
should never require an equalizing charge. If
they were not properly charged and there is a
decrease in capacity, recharge the batteries and
make sure they complete the entire charge cycle.
If the batteries are stored for extended periods
of time, recharge them as follows:
Storage Temperature Refresh Charge
Interval
Below 68˚F (20˚C) 9 Months
68˚F (20˚C) - 86˚F (30˚C) 6 Months
Higher than 86˚F (30˚C) 3 Months
OTHER CHARGERS
There are many types of chargers and inverters
available for charging lead-acid batteries. If
you are not sure if your charger meets the
recommended charging characteristics or if you
need help programming your charger, please
contact your local Fullriver Battery distributor for
assistance.
12V Battery Charge
Voltage Float Voltage
32˚F (0˚C) 15.30 14.25
50˚F (10˚C) 15.06 14.01
50˚F (10˚C) 14.82 13.77
77˚F (25˚C) 14.70 13.65
86˚F (30˚C) 14.58 13.53
104˚F (40˚C) 14.34 13.29
0.35
0.30
0.25
CURRENT (X C20 RATE)
VOLTAGE PER CELL
CHARGING TIME: <=20 HRS
BULK ABSORPTION
U = 2.45V/Cell (+/- .05V/Cell)
I = 0.012 - 0.02 x C 202
Voltage varies with age
to a maximum of 2.7V/Cell
Termination: dV/dT= 2.5mV/Cell/hr
or 105-110% recharge
Temperature: 25˚C (77˚F)
TERMINATION
0.20
0.15
0.10
0.05
0.00
2.70
2.60
2.50
2.40
2.30
2.20
2.10
2.00
Temperature Coefficient: -4mV/ C/cell (-2mV/ F/cell)
0 0
Maximum absorption time = 8 hrs.
Maximum termination time = 8 hrs.
I = 0.15 - 0.35 x C
1 20
FIGURE 2
/