Luminor MOD-EMU User manual

Type
User manual
Operaon & Installaon Instrucons
EQUIPMENT MODULES
BL
ACKCOMB
OWNER’S MANUAL
illuminating technologies for life
Table of Contents
Emulator Module .............................................. 1
Remote Alarm Module ...................................... 2
4-20 mA Module................................................ 3
Solonoid Module ............................................... 4
SHERPA Water Quality Monitor Module ........... 8
UV Concierge Module ..................................... 10
*Modules not available in all markets.
*TheseinstruconsareavailableinsocopyviaemailfromLuminorCustomerService.
CAUTION: The appliance is not to be used by persons (including children) with reduced
physical, sensory or mental capabilies, or lack of experience and knowledge, unless they
have been given supervision or instrucon.
Children should be supervised so that they do not play with the appliance.
1|Page
EMULATOR MODULE
MODEL # MOD-EMU
The Emulator module comes with a male
IEPconnecon(InniteExpandability
Port).Priortostart-up,rstensureallthe
toggleswitchesforthe“ModuleAlarms”
and“LampAlarm”areintheOFF(toggle
up)posion.PlugtheEmulatorconnector
intotheIEPontheBLACKCOMB/HO
controller,thenpluginthecontroller
powercord.
ToEmulateaparcularmodulefailure,
togglethecorrespondingswitchtothe
ON(toggledown)posion.Thealarm
can be cleared by returning the switch to
itsOFF(toggleup)posion.Thedevice
alsocanemulatetheUVintensityreportedbyaUVsensormodule.Turningtheright“UV”
knobintheclockwisedireconwillincreasetheintensity,whileturningitcounterclockwisewill
decreasetheintensity.Pleasenotethattoseeallthecapabiliesofthesensor,youwillneed
tocycletheintensitythroughtherangeof49through66%.The“DaysRemaining”cyclecan
alsobeadjustedbyturningthele“Days”knob.Theemulatormodulemustonlybesupplied
atSELV.
*Fordealeruseonly.Notavailableforsaletogeneralpublic.
Emulation Module
Module Alarms
Closed Open
Days UV
Sensor Solenoid 4-20 LampRemote Alarm
Solenoid Status
MOD-EMU
BLACKCOMB
Controller
BLACKCOMB-HO
Controller
IEP
connecon
IEP
connecon
2|Page
REMOTE ALARM MODULE
MODEL # MOD-RAM
TheRemoteAlarmmodulecomeswithbothamaleandfemale
IEPconnecon(InniteExpandabilityPort).Toiniatethemodule
simplyplugthemaleplugintotheIEPontheStandardorHigh
Outputcontroller,orintoanyotherBLACKCOMBmodulethat
containsanIEP(sensor,4-20mAmodule,solenoidmodule,etc.)
and then restart the system.
TheRemoteAlarmmoduleisapairofdrycontactsandcanbe
usedtoconnectthecontrollertoaPLCbasedsystem,analarm
buzzer(orlight),oran“OK”light.Maximumcontactrangis30V
/1A.Iftheconnecteddevice(eg.lightorbuzzer)exceedsthe1A
currentrangthenusetheRemoteAlarmModuletocontrolan
appropriatelyratedrelay.
TheremotealarmmodulemustonlybesuppliedatSELV.
Disconnectpowersupplybeforeservicing.
“OK”
Light
Customer
Power Supply
Maximum 30V
“FAIL” Light/Buzzer
Autodialer
Customer
Power Supply
Maximum 30V
Sensor IEP
Installaon
IEP
connecon
BLACKCOMB
Controller
BLACKCOMB-HO
Controller
IEP
connecon
IEP
connecon
Figure 1
Secure module to
wall with screws
Figure 2
IEPconnecon
IEP
3|Page
4-20 mA MODULE
MODEL # MOD-420
The4-20mAmodulecomeswithbothamaleandfemaleIEP
connecon(InniteExpandabilityPort).Toiniatethemodule
simplyplugthemaleplugintotheIEPonthecontroller,orinto
anyotherBLACKCOMBmodulethatcontainsanIEP(sensor,
remotealarm,solenoidmodule,etc.)
The4-20mAmodulemustonlybesuppliedatSELV.Disconnect
powersupplybeforeservicing.
Connect “LOOP” Connecons as follows:
Sensor IEP
Installaon
IEP
connecon
BLACKCOMB
Controller
BLACKCOMB-HO
Controller
IEP
connecon
IEP
connecon
Figure 1
Secure module to
wall with screws
Figure 2
IEPconnecon
IEP
LOOP Specifications
Power Supply: Min 5 volts
Max 30 volts
Power Supply
PLC
or
Data Logger
Power Supply (must be SELV):
Min 5 volts
Max 30 volts
4|Page
SOLENOID MODULE
MODEL # MOD-SOL1 (in 110V, NEMA 5-15 plug)
MOD-SOL2 (in 230V, CEE 7/7 plug)
MOD-SOL3 (in 230V, BS 1363 plug)
MOD-SOL4 (in 230V, AS/NZS 3112 plug)
TheSolenoidModuleisdesignedtoconnectaNORMALLY
CLOSEDlinevoltagesolenoidvalvetothecontroller.Itis
possibletousea12Vor24Vnormallyclosedsolenoidby
replacingtheACpowercord.Notethatthemaximumcontact
rangis240VAC(50-60Hz)/30VDC/2A.
LOCATION
Step 1) Findasuitablelocaononthewallforthesolenoid
module. The module must be installed close enough to the
controller,ortheUVsensortobeabletopluginthemale
IEP connector. The module must also be installed close
enough to the actual solenoid valve and this distance will
bedependentonthecordlengthoftheparcularsolenoid
valve that is used.
Step 2)Pickalocaonforthesolenoidvalveandinstallas
perthemanufacturersdirecons.Thesolenoidmodule
requiresbareleadsforconnecontoterminalblocks,so
ifthesolenoidcablehasaplugaached,removetheplug
andstripthewirestoasuitablelength.
INSTALLATION
Step 1) MakesurethesolenoidvalvecableisNOTpluggedintotheelectricaloutlet.Insert
thesolenoidvalvecablethroughthecenterholeofthemiddlestrainrelief.Connectthethree
electricalwirestotheterminalblockthatismarked“SOLENOID”(seeFig.2).Connectthe
groundwireintheposionmarked“GND”,thelinevoltagewireintheposionmarked“L1”
andtheneutralwireintheposionmarked“N”.Typicalwirecolourconguraonsaremarked
directlyonthecircuitboardtotheleoftheSOLENOIDterminalblocktoaidinthisprocess
(seeFig.3)Ifyouareunsureofthecorrectwiringconguraonforyouparcularsolenoid
valve,pleasecontactanapprovedelectricalcontractor.Onceallthelinevoltageconnecons
havebeenmade,ghtenthestrainreliefnuttosecurethecabletothesolenoidmodule.
Figure 3
WiringColourGuide
Figure 2
SolenoidWireInstallaon
Figure 1
Secure
module to
wall with
screws
5|Page
Step 2) Plugthesolenoidvalveintotheapplicableelectrical
outlet.Atthisstage,thefunconalityofthesolenoidvalve
canbetestedbypressingthesolenoidtestbuonlocatedon
theupperleofthecircuitboard.Manuallydepressing(and
holding)thisbuonwillcompletetheelectricalcircuitandwill
openthenormallyclosedsolenoidvalve.Youshouldbeableto
heartheacvaonofthesolenoidvalveatthisstagetoensure
thevalveisfunconingproperly(seeFig.4).
Step 3) MakesureyourUVcontrollerisunpluggedfromthe
powersource.Oncealltheseconneconshavebeenmade,
axthemaleIEPplugofthesolenoidmodulecableintothe
IEPportonthecontroller(seeFig.5),oranyotheravailable
IEPportsuchastheUVsensor,4-20mAmoduleorremote
alarmmodule.ItdoesnotmaerwhichIEPportanymodule
isaachedto,aslongastheyareaached.
OPERATION
Step 1) PlugtheBLACKCOMBcontrollerintothepower
sourceandmakesurethesolenoidmoduleisacvatedon
thecontroller.Duringthestart-upsequence,theSOLENOID
MODULEscreenwillindicatea“inialized”whenthemodule
isacvatedproperly(seeFig.6).
Figure 4
SolenoidTestBuon
Figure 6
Solenoid
Acvaon
Screens
Sensor IEP
Installaon
IEP
connecon
BLACKCOMB
Controller
BLACKCOMB-HO
Controller
IEP
connecon
IEP
connecon
Figure 5
IEPconnecon
IEP
6|Page
Step 2) Thecontrollerwillonlynofyyouwhenthereisafailure
modewherebythesolenoidmodule(andconnectedsolenoidvalve)
willbeacvated.OntheBLACKCOMB5.1system,thesolenoid
modulewillbeacvated(shungotheowofwater)uponLAMP
FAILURE(seeFig.7).Toremedythis,replacetheUVlampandrestart
thesystemasperthedireconsoutlinedintheOwner’sManual.
Step 3) OntheBLACKCOMB6.1systemwhereaUVsensorisinstalled,
thesolenoidmodulewillbeacvated(shungotheowofwater)
uponaLOWUVcondion(lessthan50%)(seeFig.8).Toremedythis,
youwillneedtoaddressthereasonforthislowUVcondionwhich
may be due to a dirty UV sensor and quartz sleeve, a lamp that is
not eming enough UV energy, or a change in the water quality.
PleaserefertotheUVsystemsOwnersManualforcorrecveacon
procedures.
Figure 7
LAMPFAILUREScreen
Step 4) To determine what posion the solenoid valve is currently in, the solenoid module
incorporates three lights on the circuit board (see Fig. 9). When the solenoid is in the OPEN
posionagreenlightwillappearonthecircuitboardbesidetheword“OPEN”.Whenthevalve
isCLOSED,aredlightwillappearonthecircuitboardbesidetheword“CLOSED”.Andwhenthe
solenoidisinanOVERRIDEposion,anamberlightwillappearonthecircuitboardbesidethe
word“OVERRIDEON”.
Figure 8
LOWUV
Screens
Figure 9
Solenoid Status
(Colour)
Boil Water Advisory: If any failure occurs on a BLACKCOMB UV system, the water
must not be used for human consumpon unl the system is returned to a safe operaonal
mode. If the water is used for human consumpon during this period, the water must be
boiled (minimum 20 minutes at a full boil) prior to consumpon.
EMERGENCY BYPASS
Inacasewherethesolenoidvalvehasbeenacvated(valveisclosedandnowaterisallowed
toow),thesolenoidmodulehastheabilitytobypassthesolenoidvalveincaseofan
emergencyneedofwater.Toiniatethisbypass,depressthebuonlabeled“OVERRIDE”
locatedinthelowerleporonofthecircuitboard(seeFig.10)
7|Page
Figure 10
SolenoidBypass
Buon
Oncethisbuonhasbeenpressed,thesystemwillremaininthis
overridemoderegardlessofwhetherornotthecondioncausingthe
solenoidacvaonhasbeenremediedornot.Toresetthesystem,
thepowertothecontrollermustbeshutoandrestarted.While
inthisoverridemodethecontrollerwillintermientlydisplayared
“SOLENOIDOVERRIDE”screen(seeFig.11).
Figure 11
SOLENOIDOVERRIDE
Screen
DISABLING EMERGENCY BYPASS
Incertainregulatedapplicaons,theavailability,anduse,
oftheemergencybypassfeaturemaybeinviolaonofthe
local,state/provincialcodes.Ifthisisthecase,thebypass
featurecaneasilybedisabledbyphysicallyremovingthe
bypassbuon.Toaccomplishthis,carefullyuseapairof
needlenosepliersandphysicallyremovetheactualbypass
buon(marked“OVERRIDE”)fromthecircuitboard.
Figure 12
SOLENOIDFAILURE
Screen
OTHER FAILURE MODES
Intheeventthereisanissuewiththesolenoidconneconfrom
theIEPcabletothecontroller,thesystemwillregistera“SOLENOID
FAILURE”screenonthecontroller(seeFig.12).
CAUTION: BEFORE PERFORMING ANY
WORK ON THE SOLENOID MODULE, THE
POWER CORD MUST BE DISCONNECTED
FROM ITS POWER SOURCE (WALL PLUG).
8|Page
WATER QUALITY
MONITOR MODULE
MODEL # MOD-SHERPA
ThemodulecomeswithaSHERPATransmierandaSHERPARemoteDisplay.TheTransmier
connectstoaBLACKCOMBandBLACKCOMB-HOcontrollerandtransmitsthecontroller’sstatus
wirelesslytotheRemoteDisplay.EveryTransmierandRemoteDisplayispairedtogether
andusesencryptiontocreateareliableandsecurecommunicationlinkbetweenthetwo
devices.EveryTransmiersupportsuptoveRemoteDisplays.AdditionalRemoteDisplays
canbepurchasedandinstalledseparately.Referto‘PairinganAdditionalRemoteDisplay’for
additionalRemoteDisplayinstallation.
Sensor IEP
Installaon
IEP
connecon
BLACKCOMB
Controller
BLACKCOMB-HO
Controller
IEP
connecon
IEP
connecon
Installation
Step 1)PowerotheBLACKCOMBorBLACKCOMB-HOcontroller.
Step 2)PlugthemaleplugoftheSHERPATransmierintotheIEP(InniteExpandability
Port)onthecontroller,orintoanyotherLUMINORmodulethatcontainsanIEP
(sensor,4-20mAmodule,solenoidmodule,etc.)andthenrestartthesystemNote1.
Step 3)ToReceivetheBLACKCOMBor
BLACKCOMB-HOcontrollers
status on the SHERPA Remote
Display,plugtheAC/DCwall
adapterintothePowerPorton
theSHERPARemoteDisplay(5V
Max)andslidetheswitchto
theONposion.
Back of
Remote
Display
SHERPA Transmier
SHERPA Remote Display
50m/164
(Note2)
9|Page
Operation
SHERPA Remote Display
Status LED’s
Good
(Green) Waterissafeforconsumption.NoActiveAlarms.
Caution
(Yellow)
Watermaynotbesafeforconsumption.
ActiveMinorAlarm,checksystemfordetails.
Alarm
(Red)
WaterisNOTsafeforconsumption.
ActiveMajorAlarm,checksystemfordetails.
Comm. LED
OFF Communication is working.
Flashing
CommunicationisNOTworking.
Remote Display is Out-of-Range2, Transmier is disconnected
OR controller is powered o.
ON RemoteDisplayisaemptingtopairwithalocal
transmierinproximity.
Power
Switch
IRemoteDisplayPoweredON
O RemoteDisplayPoweredOFF
NOTE 1: Not Compable with MOD-RAM. The SHERPA gets detected as a “Remote Alarm” on
BLACKCOMB or BLACKCOMB-HO controllers during the start-up sequence.
NOTE 2: The Wireless Range can vary based on the installation environment; objects, walls
and metal obstacles can interfere and degrade the wireless signal. Best suited for residential
applications.
Pairing an Additional Remote Display
TopairanadditionalRemoteDisplaytoacurrentlyinstalledTransmier:
Step 1)PowerONtheAdditionalRemoteDisplaywithin5m(15)proximitytothe
transmier;bysimplypluggingtheAC/DCwalladapterintothePowerPorton
theRemoteDisplayandslidingtheswitchtotheONposition.
Step 2)TheRemoteDisplayperformsself-pairingwiththelocaltransmier.Oncepaired
theCommunicationLEDontheRemoteDisplaywillturnOFFandaStatusLED
willturnON.
Step 3)Oncepairingiscomplete,relocatetheRemoteDisplaytoanylocation2.
10|Page
UV CONCIERGE MODULE
MODEL # MOD-APP
TheUVConciergemoduleconnectstoyourwirelessnetwork(WiFi)andtransmitsyourUV
system’sstatustotheuvconcierge.comwebpage.Youcanthenviewyourstatusonlinefrom
anywhereyouhaveinternetaccess,andreceiveemailorSMSnocaonsofyoursystem’s
status on your mobile device.
TheUVConciergemodulecomeswithbothamaleandfemaleIEPconnecon(Innite
ExpandabilityPort).ToiniatethemodulesimplyplugthemaleplugintotheIEPonthe
StandardorHighOutputcontroller,orintoanyotherBLACKCOMBmodulethatcontainsanIEP
(sensor,4-20mAmodule,solenoidmodule,etc.),plugintheincludedpoweradaptertothe
wallandyourUVConciergemodule,andthenrestarttheUVsystem.
Oncethesystemisiniatedasabove,youwillneedtoprovideyourWiFilogincredenalsto
thesystem.InstalltheUVConciergeapponyouriOSorAndroiddevicebysearchingforitin
youriOSAppStoreorGooglePlaystore,orscantheQRcodebelow:
Fromtheapp,clicktheConnectDevicebuon,andfollowthepromptstoselectyourWiFi
networkandenterinyourpassword.
Oncetheappreportsthemoduleisconnected,addthedevicetoyouraccountbyoneofthe
threefollowingmethods:
Sensor IEP
Installaon
IEP
connecon
BLACKCOMB
Controller
BLACKCOMB-HO
Controller
IEP
connecon
IEP
connecon
11|Page
If you do not currently have a uvconcierge.com account: FromtheUVConciergeapp,click
Adddevicetoaccount”.Thismethodwillautomacallypopulateyourmodulekeyforyou.
OR
Make note of the Module Key from the label on your UV Concierge module. Goto
uvconcierge.comandclickthe“Registeranewdevice”link.Youwillneedthemodulekeyto
successfullyregisteryourmodule.
If you currently have a uvconcierge.com account: FollowoneoftheabovetwooponsORlog
intoyouraccount,select(oradd,thenselect)thelocaonyou’dliketohavethedevice,thenclick
the“Addadevicebuon”.Youwillneedthemodulekeytosuccessfullyregisteryourmodule.
App Troubleshoong
The app does not nd my UV Concierge module
EnsureyouhavepluggedyourUVConciergemoduleintothepoweroutletusingtheincluded
poweradapter.
I’m stuck at “Waing for system to complete startup”
Youmustrestartyoursystembyunpluggingandplugginginthecontrollerpowercordaer
pluggingintheUVConciergemodule.OncethecontrollerdetectstheUVConciergemodule
andthestartuprouneisnished,youwillautomacallypassthissecon.Aerstartupis
complete,youcanpressandholdthecontrollerbuonfor3secondstoseewhatmodulesit
currentlydetects.IfthecontrollerisnotdetecngtheUVConciergemodule,checkyourIEP
connecons.Connectonemoduletothecontrolleratametotesteachmoduleindividually.
Withmulplemodules,theorderofthedaisychain(whichdeviceispluggedintowhich)does
notmaer.
I get a “Pairing Failed” error
Aertheappndsyourdevice,youmustenterinthe6numbersdisplayedonthecontroller
intoyourapp,includingleadingzeros.Ifyouaresllstuck,tryrestarngtheUVConcierge
modulebyunpluggingitandpluggingitbackin.TryrestarngyouriOS/Androiddevicealso.If
theissuepersists,trywithanotheriOSorAndroiddevice.
12|Page
13|Page
illuminating technologies for life
80SouthgateDrive,Unit4
Guelph,Ontario,CanadaN1G4P5
P:519-837-3800
TF:855-837-3801
F:519-837-3808
info@luminoruv.com
www.luminoruv.com
PN: 910352
VersionDate:04-2022
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Luminor MOD-EMU User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI