2018
CONTENTS
Installation, operating and maintenance instructions
MPS...D
English
1. FOREWORD ............................................................................... 2
2. IMPORTANT INFORMATION .................................................................. 2
3. GENERAL SAFETY INSTRUCTIONS ............................................................. 3
4. ADHERE TO THE FOLLOWING INSTRUCTIONS ................................................... 5
5. PRODUCT INFORMATION .................................................................... 5
6. DELIVERY CONTENTS ....................................................................... 6
7. TECHNICAL DATA ........................................................................... 6
8. DIMENSIONS .............................................................................. 7
9. TRANSPORT AND STORAGE .................................................................. 8
10. ASSEMBLY ................................................................................ 8
11. ELECTRICAL CONNECTION .................................................................. 11
12. COMMISSIONING .......................................................................... 13
13. MAINTENANCE AND CLEANING .............................................................. 13
14. LIFETIME AND DISPOSAL ................................................................... 15
15. TROUBLESHOOTING ....................................................................... 16
ruck Ventilatoren GmbH
Max-Planck-Str. 5
D-97944 Boxberg-Windischbuch
Tel. +49 7930 9211-300
Fax +49 7930 9211-166
www.ruck.eu
Example configuration shown
e original instructions were created in the German language.
Information updated
print 31.10.2023
Subject to change
Fan for exhaust
applications
MPS...D.40
Made in EU
MPS 315 D4 30
15.11.2018
ID 140 696
SN 181115-Q00000-123
400V 3~Y
Imax.
tA/tM
P1N
nN
50Hz
60/120°C
669W
2280 1/min
ISO F
VSD not integrated
N= 70
η=52,6% (A,static)
ErP Data
EN
Installation, operating and maintenance instructions
1. FOREWORD
Dear customers,
ank you for choosing our device.
Before operating the unit, please read carefully these installation, operating and maintenance instructions. If you have any ques-
tions, please contact: (Contact details see page 1)
e data provided in these installation, operating and maintenance instructions are for the product description only. A statement
about a certain condition or a suitability for a certain application cannot be derived from our information. e information does not
release the user from his own assessments and examinations.
All rights reserved by the manufacturer, even in the event of industrial property rights.
Any disposal such as copying and distribution rights lies with us.
2. IMPORTANT INFORMATION
is manual contains important information on the safe and appropriate assembly, transport, commission-
ing, operation, maintenance, disassembly and simple troubleshooting of the product.
e product has been manufactured according to the accepted rules of current technology.
ere is, however, still a danger of personal injury or damage to equipment if the following general safety instructions and the warnings
before the steps contained in these instructions are not complied with.
Read these instructions completely and thoroughly before working with the product.
Keep these instructions in a location where they are accessible to all users at all times.
Always include the operating instructions when you pass the product on to third parties.
2.1. Other applicable documents and information
e following documents and information must be observed in addition to the installation, operating and maintenance instructions:
2.2. Provisions and regulations
When properly installed and operated, the device complies with the applicable standards and EU Directive at the time of its
placing on the market.
In addition, observe generally valid, legal and other binding regulations of the European or national legislation as well as the
regulations in your country for accident prevention and environmental protection.
2.3. Warranty and liability
Our devices are manufactured to the highest technical level in accordance with the generally accepted rules of technology. ey are
subject to constant quality controls. Because the products are being constantly developed, we reserve the right to make changes
to the products at any time and without prior announcement. We assume no liability for the correctness or completeness of these
installation, operating and maintenance instructions.
To ensure your warranty claims, it is imperative to provide a commissioning report and a maintenance record.
Warranty and liability claims for personal injury and property damage are excluded if they are due to one or more of the following
causes:
Nameplate Other applicable standards: Available documents at www.ruck.eu
DIN VDE 0100-100
DIN EN 60204-1
DIN EN ISO 13857
DIN EN ISO 12100
DIN 24154R3
VDI 2052
VDMA 24186-1
Installation, operating and maintenance instructions
Programming instruction FU
EC Declarations of conformity
EC-Declaration of Incorporation (Directive 2006/42/EC)
Commissioning report
Call to Tender
Dimensioned drawing
Technical drawing DWG
Technical drawing DXF
3D STEP
2 | MPS...D.40
EN
Improper use
Improper mounting, commissioning, operation and maintenance
Operating the device with defective and / or non-functional safety and protective devices
Failure to observe the instructions regarding transportation, installation, operation and maintenance
Unauthorized structural changes to the device
Poor monitoring and replacement of maintenance parts
Improperly performed repairs
Disasters and force majeure
3. GENERAL SAFETY INSTRUCTIONS
Planners, plant engineers and operators are responsible for ensuring that the product is installed and operated correctly.
Use our devices only in perfect technical condition.
Check the device for obvious defects, such as cracks in the housing or missing rivets, screws, caps or other application-relevant
defects.
Only use the device in the power range specified in the technical data and on the nameplate.
Protection against contact and being sucked in and safety distances should be provided in accordance with DIN EN 13857.
Generally prescribed electrical and mechanical protection devices are to be provided by the client.
Safety components must not be bypassed or put out of operation.
e product may be operated by personnel with limited physical, sensory or mental capacities only if they are supervised or
have been instructed by responsible personnel.
Children must be kept away from the product.
3.1. Intended use
Our devices are incomplete machineries as defined in the EU Machinery Directive 2006/42/EC (partly completed machinery). e
product is a not ready-for-use machine in terms of the machine directive.
It is intended exclusively for installation in a machine or in ventilation equipment and installations or for combination with other
components to form a machinery or installation. e product may be commissioned only if it is integrated in the machinery/system
for which it is designed and the machinery/system fully complies with the EC machinery directive.
Observe the operating conditions and performance limits specified in the technical data.
Conveying and ambient temperatures must be observed according to the technical data and the nameplate.
Intended use also implies that you have fully read and understood this manual.
Improper use may result in danger to the life and limb of the user or third parties or damage to the system
or other property.
3.2. Improper use
Any use of the product other than described in chapter “Intended use” is considered as improper.
e following points are improper and dangerous:
Delivery of explosive and flammable media or operation in potentially explosive atmospheres.
e conveying of moist mediums (over 90% relative humidity).
Delivery of aggressive and abrasive media.
Operation without the duct system.
Operation with closed air connections.
e use on vehicles, aircrafts and ships.
3.3. Personnel qualifications
Assembly, commissioning, operation, disassembly and service (including maintenance and repair) require basic mechanical and elec-
trical knowledge, as well as knowledge of the appropriate technical terms. In order to ensure operating safety, these activities may
therefore only be carried out by qualified technical personnel or a person under the direction and supervision of qualified personnel.
Qualified personnel are those who can recognize possible hazards and institute the appropriate safety measures due to their pro-
fessional training, knowledge, and experience, as well as their understanding of the relevant conditions pertaining to the work to be
done. Qualified personnel must observe the rules relevant to the subject area.
www.ruck.eu | 3
EN
Installation, operating and maintenance instructions
3.4. Safety instructions in this manual
In this manual, there are safety instructions before the steps whenever there is a danger of personal injury or damage to the equip-
ment. e measures described to avoid these hazards must be observed.
Safety sign (warning
triangle)
Consequence
General warning!
Indicates possible hazardous situations. Failure to observe the warnings may result in personal injury
and / or damage to property.
Electricity warning (hazardous voltage)!
Indicates possible hazards due to electricity. Failure to observe the warnings may result in death, injury
and/or damage to property.
Hot surface warning!
Indicates possible hazards due to high surface temperatures. Failure to observe the warnings may re-
sult in personal injury and/or damage to property.
Finger-Crushing Warning!
Indicates possible hazards due to moving and rotating parts. Failure to observe the warnings may re-
sult in personal injury.
Overhead load warning!
Indicates possible hazards due to overhead loads. Failure to observe the warnings may result in death,
injury and/or damage to property.
Follow important information!
Instructions for safe, optimum use of the product.
Safety instructions are set out as follows:
Safety sign (warning triangle) - Draws attention to the risk.
Type of risk! - Identifies the type or source of the hazard.
»Consequences - Describes what occurs when the safety instructions are not complied with.
→ Precautions - States how the hazard can be avoided.
!
!
General warning
»Failure to observe the warnings may result
in personal injury and / or damage to pro-
perty.
→ Unauthorized repairs may cause personal
injury and / or damage to property, in which
case the manufacturer‘s guarantee or war-
ranty will not apply.
!
!
Electricity warning (hazardous voltage)!
»Failure to observe the hazard may result in
death, injury or damage to property.
→ Before performing any work on conductive
parts, always disconnect the unit comple-
tely from the electricity supply and make
sure that it cannot be switched back on
again.
!
!
Caution! Burning hazard.
»Failure to observe the hazard may result in
personal injury and/or damage to property.
→ Do not touch the surface until the motor
and heater have cooled.
!
!
Never reach into the impeller or other
rotating or moving parts.
»Failure to observe the hazard may lead to
serious injury.
→ Work may only be performed once the im-
peller has come to a complete halt.
!
!
Never reach into the impeller or other
rotating or moving parts.
»Failure to observe the hazard may lead to
serious injury.
→ Work may only be performed once the im-
peller has come to a complete halt.
!
Never clean the internal space with flo-
wing water or a high-pressure cleaner. Do
not use aggressive or easily flammable
products for cleaning (impellers/housing).
Only use mild soapsuds. e impeller should
be cleaned with a cloth or brush.
4 | MPS...D.40
EN
4. ADHERE TO THE FOLLOWING INSTRUCTIONS
4.1. General instructions
Persons who assemble, operate, disassemble or maintain our devices must not be under the influence of alcohol, drugs or phar-
maceuticals that may affect perception and responsiveness.
Responsibilities for the operation, maintenance and regulation of the product should be clearly determined and observed so
that there can be no unclear areas of responsibility with regard to safety.
4.2. Indications assembly
Disconnect all of the product‘s poles from the mains before installing the product or connecting or removing plugs. Make sure
that the product cannot be switched back on again.
Lay cables and lines so that they cannot be damaged and no one can trip over them.
Information signs must not be changed or removed.
4.3. Indications Commissioning
Make sure that all electrical connections are either used or covered. Commission the product only if it is installed completely.
e power switch must always be fully functional and easy accessible!
4.4. Indications during operation
Only authorized personnel is allowed to operate the setting mechanisms of the components or parts, under the provision that
the system is used as intended.
In an emergency, or if there is a fault, or other irregularities, switch the equipment off and make sure it cannot be switched back
on again.
e technical data given on the rating plate must not be exceeded.
5. PRODUCT INFORMATION
Description:
Performance optimized fan for exhaust applications
Conveyed exthaust up to 120 °C
Backward curved radial impeller
Integrated grease tray with drain
Motor outside the air stream (VDI 2052)
ermal motor protection to be connected on site
Outdoor installation possible with appropriate accessories
ree discharge directions possible: right / left / up
Double-skin housing made of galvanized sheet steel with 40 mm thermoacoustic insulation, non-combustible according to DIN
EN 13501-1, building material class A1.
e backward curved impeller is made of powder-coated sheet steel.
3-phase motors according to IE-3 classification are basically only controllable via frequency converters!
www.ruck.eu | 5
EN
Installation, operating and maintenance instructions
5.1. Nameplate
ATTENTION! e information on the nameplate must always be observed!
6. DELIVERY CONTENTS
1 x Exhaust fan
2 x Feet
4 x Vibration dampers
1 x Installation, operating and maintenance instructions
EC Declarations of conformity
EC-Declaration of Incorporation (Directive 2006/42/EC)
7. TECHNICAL DATA
Product name
Item number
Voltage UN
Frequency fN
Rated power consumption PN
Max. motor current Imax
Max. ambient temperature tA
Max. medium temperature tM
Sound power casing
Sound power inlet
Sound power outlet
Wiring diagram
Weight
VHz W A °C °C dB(A) dB(A) dB(A) kg
Legend:
Imax Max. current consumption
tA / tMMax. ambient temperature / Max. medium temperature
P1N Rated power consumption
nNRated speed
IPX4 IP protection complete device
ISO F Insulation class motor
ErP Data ErP Conformity, if required according to Reg. 327/2011
η Overall efficiency
N Efficiency at the optimum energy efficiency
ID Item number
SN Serial number
Air direction arrow
ErP 2015
Product name
Test date
CE marking
UKCA marking
Insulation class motor
EAC marking
Grounding
6 | MPS...D.40
MPS 225 D2 40 156622 400V 3~Y 50 486 0,9 60 120 74 79 83 141262 29,3
MPS 250 D2 40 156623 400V 3~Y 50 756 1,3 60 120 72 82 85 141262 38,0
MPS 280 D2 40 156624 400V 3~Y 50 759 1,3 60 120 75 81 85 141262 38,5
MPS 315 D2 40 156626 400V 3~Y 50 1221 2,4 60 120 72 87 87 141262 52,9
MPS 315 D4 40 156627 400V 3~Y 50 669 1,2 60 120 71 79 80 141262 52,9
MPS 355 D4 40 156628 400V 3~Y 50 775 1,4 60 120 68 81 82 141262 54,7
MPS 400 D4 40 156629 400V 3~Y 50 564 1,1 60 120 66 74 74 141262 72,1
MPS 450 D4 40 156630 400V 3~Y 50 1278 2,5 60 120 74 82 82 141262 74,9
MPS 500 D4 40 156633 400V 3~Y 50 1504 3,0 60 120 72 83 83 141262 112,7
MPS 560 D4 40 156635 400V 3~Y 50 2577 5,0 60 120 76 87 86 141262 115,0
E
A C
F
B
G1
D2
D1
K
H
J
M
L
N
G2
ID A B C D1 D2 E F G1 G2 H J K L M N
mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm
EN
8. DIMENSIONS
Item
number A B C D1 D2 E F G1 G2 H J K L M N
mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm
www.ruck.eu | 7
156622 492 474 265 Ø199 Ø199 571 480 481 483 394 445 279 285 142 131
156623 592 561 315 Ø249 Ø249 690 540 550 562 494 505 329 344 166 156
156624 592 561 315 Ø314 Ø314 692 540 550 562 494 505 329 344 200 156
156626 700 663 365 Ø354 Ø354 790 590 616 612 602 555 382 404 218 181
156627 700 663 365 Ø354 Ø354 790 590 616 612 602 555 382 404 218 181
156628 700 663 365 Ø354 Ø354 790 590 616 612 602 555 382 404 218 181
156629 832 789 365 Ø354 Ø354 916 590 616 612 734 555 448 477 220 181
156630 832 789 365 Ø354 Ø354 916 590 659 612 734 555 448 477 220 181
156633 1016 954 510 Ø399 Ø399 1092 834 825 876 918 799 539 584 242 253
156635 1016 954 510 Ø499 Ø499 1090 834 859 876 918 799 539 584 289 253
MPS...D.40
1
2
EN
Installation, operating and maintenance instructions
9. TRANSPORT AND STORAGE
Transport and storage should only be performed by specialist personnel in accordance with the assembly and operating manual and
regulations in force.
e following points should be noted and followed:
Check the delivery according to the delivery note to ensure it is complete and correct and check for any damage. Any missing
quantities or damage incurred during transport should be confirmed by the carrier. No liability is accepted if this is not observed.
For weight see technical data
It should be transported with suitable lifting equipment in the original packaging or on the transport equipment indicated.
If transported with a forklift, it should be ensured that the product is resting with the basic profile or base frame completely on
the forks or on a pallet and the product‘s centre of gravity is between the forks.
e driver must be authorized to drive a forklift.
Do not go beneath the suspended load.
Avoid damage or deformation of the housing.
e product must be stored in a dry area and protected from the weather in the original packaging. Open pallets should be cov-
ered with tarpaulins. Even weatherproof modules should be covered because their weather resistance is only guaranteed after
complete installation. If moisture has penetrated into the original packaging, remove it immediately.
Storage temperature between +5 °C and +40 °C. Avoid severe temperature fluctuations.
If the product has been in storage for more than a year, check the smooth running of impellers and valves by hand.
10. ASSEMBLY
Assembly work may only be performed by specialist personnel in accordance with the installation and operating manual and the
regulations and standards in force.
e following points should be noted and followed:
e foundation must be even and levelled. It must not exhibit unevenness or a slope in any direction.
Set up and align the machine with the aid of a water level. A perfect function of the device can be guaranteed only if levelled
mounted.
Only suitable installation aids, in accordance with regulations, should be used.
e device must be installed in such a way that it is easily accessible for maintenance and cleaning purposes.
e unit should only be installed with authorized and suitable fastening materials at all fastening points.
Do not distort the unit when installing.
Just use the indicated mounting and fixing places. No holes should be made in the housing or any screws screwed into it.
e duct system must not be supported on the housing.
For structure-borne sound decoupling, a flexible connection is recommended when connected on a duct system.
e length of straight tube before fan must be at least 2.5 times the fan diameter
Unpacking example:
Packaging may vary, depending on the size of the device.
Release transportation lock (2)
Lift the device (3) out of the packaging
Final assembly of the device depending
on the location (see installation!)
8 | MPS...D.40
A
B
C
5
1
4
2
3
EN
10.2. Assembly with discharge up
WK MPS
Wall bracket (available as accessory)
WSH MPS
Weather protection cover (available as accessory)
Function condensate drain only possible with discharge up
A
B
Mount the mounting rail (1) with body (2),
ramp (3) and doorstop (4)
Mount socket silencer (5)
Condesate drain 3/4“ external thread
10.1. Assembly with accessories
www.ruck.eu | 9
A
BC D
1
3
3
2
4
2
1
6
5
3
3
6
4
5
1
2
3
3
EN
Installation, operating and maintenance instructions
10.3. Assembly with discharge on side
A.
Release handle (1), hinges (2) and
screwed connections (3)
C. Discharge left
Turn the device completely
Mount hinges (2) on the right
Mount handle (1) in position as shown
Make screw connections (3) of the door
Mount the mounting rails (4) on the
socket silencer
ATTENTION: Mounting rail with ramp
(5) left, mounting rail with doorstop (6)
right
Use of condensate drainage not possi-
ble here!
D. Discharge right
Turn the device completely
Mount hinges (2) on the left
Mount handle (1) in position as
shown
Make screw connections (3) of the
door
Mount the mounting rails (4) on the
socket silencer
ATTENTION: Mounting rail with
ramp (5) right, mounting rail with
doorstop (6) left
Use of condensate drainage not
possible here!
10 | MPS...D.40
EN
Electricity warning (hazardous voltage)!
»Failure to observe the hazard may result in death, injury or damage to property.
→ Before performing any work on conductive parts, always disconnect the unit completely from the elec-
tricity supply and make sure that it cannot be switched back on again.
e electrical installation may only be carried out by qualified electricians in compliance with the installation, operating and mainte-
nance instructions and the applicable national regulations, standards and guidelines:
ISO, DIN, EN and VDE specifications, including all safety requirements.
Technical connection conditions.
Safety at work and accident prevention requirements.
is list does not claim to be complete.
Requirements should be applied under one‘s own personal responsibility.
e electrical connections must be made as shown in the corresponding wiring diagrams and terminal diagrams.
e type of cable, size of cable and method of laying should be determined by an authorized electrician.
Low and extra-low voltage cables should be laid separately.
An all-pole mains disconnection device with at least 3 mm contact gap must be provided in the supply line.
Use a separate cable inlet for each cable.
Any cable inlets that are not used must be sealed so that it is airtight.
All cable inlets must have strain relief.-Create equipotential bonding between the unit and the duct system.
Check all protective measures after the electrical connection work (earthing resistance, etc.)
Motor current and motor power must not exceed the values stated on the motor nameplate. e specified max. fan speed must
never be exceeded, otherwise the motor and fan will be destroyed by this overload and dissolved or flying parts can destroy
other components.
11.1. Unit supply cable
Connect the mains supply cable as shown in the wiring diagram. For the dimensioning of the
line, observe the unit‘s rating plate and the relevant guidelines. Appropriate protection with
correctly dimensioned automatic safety breakers (circuit protection breaker) must be provided.
e device must be connected according to the wiring diagram. For fans which are controlled
by external control devices, the corresponding operating instructions of the manufacturer
must be observed.
Star circuit
11.2. Star circuit / Delta circuit
In star connection, the terminals U2, V2 and W2 are connected
by the shorting blades. In order to get a right turning field L1 has
to be connected to U1, L2 to V1 and L3 to W1.
e star circuit must be used if the motor is to be operated di-
rectly on the 3-phase supply network with a line voltage of 400V.
e star circuit is also to be used when controlling via a frequen-
cy inverter with 400V output voltage (usually a frequency con-
verter with 3-phase 400V mains connection).
11. ELECTRICAL CONNECTION
www.ruck.eu | 11
EN
Installation, operating and maintenance instructions
Product name Item number Rated frequency
fN
Maximum frequency
fmax
Max. motor current Imax
3~400V Y
Max. motor current Imax
3~230V D
Hz Hz A A
Delta circuit
If, in spite of the correct connection to the mains or to the frequency converter, the devices turn contrary
to the given direction of rotation, this must be corrected. For this purpose two phases can be interchanged
at the terminal block (e.g. L1 with L2 or L2 with L3). Afterwards the direction of rotation is to be checked
again.
For the electrical connection, for the setting of the motor protection switch or for the parameterization of a
frequency inverter, only the technical data on the nameplate of the fan are relevant. ese may differ from
the technical data of the motor.
11.3. ermal motor protection
During operation, electric motors heat up. Under certain circumstances (excessively high ambient or fluid temperatures, heavy
contamination, etc.), the motor temperature may exceed the safety limit of the electrically isolated parts. In order to avoid engine
damage, various types of temperature monitoring are possible, of which at least one must be installed on site:
Monitoring of the thermal motor current via a FU
Motor protection switch
11.4. Frequency converter
If the fans are placed on the EU market or operated within the EU, they must have a speed control. is is only possible by means
of frequency converters. Using other speed controls, such as voltage control, will directly damage the motor.
We offer tested and approved frequency converters as accessories. ese are pre-programmed and delivered exactly matched to the
respective engine power and speed. When using a frequency converter, the cable (max. length 50 m) between motor and frequency
converter must be shielded. If third-party products are used, the following parameters must be set correctly.
In delta connection, the short-circuiting blades are connecting
U1 to W2, V1 to U2 and W1 to V2. In order to get a right turning
field L1 has to be connected to U1, L2 to V1 and L3 to W1.
e delta circuit must be used if the motor is to be operated
directly on the 3-phase supply network with a line voltage of
230V.
e delta circuit is also to be used when controlling via a fre-
quency inverter with 230V output voltage (in general frequency
converter with 1-phase 230V mains connection).
12 | MPS...D.40
MPS 225 D2 40 156622 50 60 0,9 1,6
MPS 250 D2 40 156623 50 60 1,2 2,1
MPS 280 D2 40 156624 50 50 1,3 2,3
MPS 315 D2 40 156626 50 50 2,5 4,3
MPS 315 D4 40 156627 50 80 1,1 1,9
MPS 355 D4 40 156628 50 70 1,4 2,4
MPS 400 D4 40 156629 50 50 1,1 1,9
MPS 450 D4 40 156630 50 55 2,5 4,3
MPS 500 D4 40 156633 50 50 2,9 5
MPS 560 D4 40 156635 50 50 5 8,7
EN
11.5. Fault current protection switch
If a fault current protection switch is used, only AC/DC sensitive RCD protective devices (type B or B+) are permitted.
Even when the device is switched off, voltage is applied to terminals and connections. Do not touch the
device for 5 minutes after all-pole disconnection from the mains.
12. COMMISSIONING
Commissioning by trained technical personnel may only be performed after any risk has been ruled out.
e following checks should be performed in accordance with the installation and operating manual and
the regulations in force:
Correctly sealed installation of the unit and duct system.
Check the duct system, unit and medium lines, if present, remove any foreign bodies if necessary.
e intake opening and inflow into the unit must be clear.
Check all mechanical and electrical protection measures (e.g. earthing).
Voltage, frequency and type of current must correspond with the rating plate.
Note:
Standard frequency inverters have a modified sine-wave at the output. is may cause noises, depending on the combination motor
- frequency converter. Depending on the fan design and the radiating surface, these are perceptible.
At very high noise requirements, this can be disturbing. For industrial applications, the noises are generally acceptable.
Remedial measures may be a change in the clock frequency or the use of a sine-wave filter or a frequency converter with integrated
sine-wave filter.
13. MAINTENANCE AND CLEANING
Servicing, troubleshooting and cleaning may only be performed by specialised personnel in accordance with this
installation and operating manual and the regulations in force.
Make sure that no connections or components are loosened unless the device is disconnected from the mains. Make
sure that the equipment cannot be switched back on again.
Individual components must not be interchanged. For example, the components intended for one product may not
be used for other products.
e regular maintenance and care of our devices is designed to ensure proper function, value retention and avoid-
ance of damage. Keep a maintenance log.
Perform the specified maintenance on the unit at the specified intervals.
Our devices require little maintenance when operated properly.
e following work should be performed at regular intervals, in accordance with health and safety regulations:
Check the operation of the control system and safety devices.
Check electrical connections and wiring for damage.
Remove any dirt from the fan impeller or impellers and from inside the fan housing in order to prevent any unbal-
ance or reduction in output.
Do not use aggressive or easily flammable products for cleaning (impellers/housing).
Preferably only water (not flowing water) or mild soapsuds should be used.
e impeller should be cleaned with a cloth or brush.
Never use a high-pressure cleaner.
Balancing clips must not be moved or removed.
e impeller and fittings must not be damaged in any way.
Before putting the unit back into operation after maintenance and servicing work, carry out a visual inspection as described in sec-
tion 12 and 13.
www.ruck.eu | 13
A
A
B
B
A-A
B-B
1
2
3
3
4
EN
Installation, operating and maintenance instructions
13.1. Checklist Maintenance and Service
Description Months
Triggering device monthly
Fan
Check fan for function and operational readiness (test run at least 15 minutes) every 6 months
Check fan for function and operational readiness (test run at least 1 hour) yearly
Check for dirt, damage, corrosion and fastening every 6 months
Function-preserving cleaning every 6 months
Check impeller rotation direction yearly
Check flexible connections for leaks yearly
Check impeller for imbalance yearly
Check protective device for function yearly
Motor
Check externally for dirt, damage, corrosion and fastening every 6 months
Function-preserving cleaning yearly
Check bearing for noise yearly
Check terminals for tight fit yearly
Measure the voltage yearly
13.2. Maintenance works
Undo screws (1) and (2)
Swing out fan unit (3)
Secure the fan unit in the open
position (4)
13.3. Impeller installation with Taperlock clamping bush
e impeller is connected by means of the clamping bush to the shaft end of the drive motor.
1. Clean all bare surfaces (mating surfaces of the
clamping bushings and motor shaft).
2. Insert the clamping bush (1) into the hub (2) and
bring the holes into alignment.
3. Loosely lubricate the threaded pins (3) and screw in -
do not tighten yet.
4. Push the impeller onto the shaft with the clamping
sleeve, align it in the axial position and tighten the
threaded pins evenly on both sides. Observe the
tightening torque according to table.
Assembly
Disassembly
1. Loosen all the threaded studs (3) and screw them
out completely. Lubricate a threaded pin and
screw it into the disassembly hole (4).
2. Tighten the threaded pin until the clamping bush (1)
is released from the hub (2).
3. e impeller can be removed.
1
2
3
4
4
14 | MPS...D.40
EN
Bushing size
Torque table
Bushing size 1210 2012 2517
Screw tightening torque with feather
(Nm) 17 26 41
Screw tightening torque without feather
(Nm) 20 31 48
Number of screws 2 2 2
Technical data
Commissioning (after replacement)
Remove any remaining installation material and foreign objects from the impeller and suction area.
Check direction of rotation (direction of rotation arrow on the impeller base disc).
During initial commissioning, the entire unit must be checked for mechanical vibrations. If necessary, re-balancing must be car-
ried out.
Pay attention to a quiet operation, without vibrations.
14. LIFETIME AND DISPOSAL
14.1. Product life
e motors are equipped with maintenance-free, permanently lubricated ball bearings. Under normal operating conditions, the ex-
pected lifetime is about 30,000 operating hours.
e information given here depends strongly on the respective field of application as well as the environmental conditions. We rec-
ommend replacing these fans after reaching about 30,000 operating hours or 5 years.
14.2. Decommissioning and disposal
When disassembling, parts under voltage are exposed, which can lead to electric shock when touched.
Before dismantling, disconnect the fan from all poles of the mains and secure against being switched on
again!
Parts and components of the device that have reached their lifetime, e.g. due to wear, corrosion, mechanical stress, fatigue and/
or all other, not directly recognizable effects, must be disposed of professionally and properly after disassembly in accordance with
national and international laws and regulations. e same applies to excipients in use such as oils and fats or other substances.
e conscious or unconscious reuse of used components such as e.g. impellers, rolling bearings, motors. etc. can lead to a risk to
persons, the environment as well as machinery and equipment. e applicable local operating regulations must be observed and
applied.
14.3. Spare parts (motor + impeller)
Only original spare parts may be used.
e repair may only be carried out by personnel trained and authorized.
www.ruck.eu | 15
EN
Installation, operating and maintenance instructions
15. TROUBLESHOOTING
Fault Possible cause Remedy methods
Fan does not start No power supply Check mains supply / connections
Impeller does not rotate freely Check the causes and, if possible, remove them. If
not possible, contact the supplier.
Engine overheated /
temperature protec-
tion is switched on
Fault of the ball bearings Contact the supplier
Too high operating temperature Observe the data on the nameplate
Air flow is too low, motor cannot cool down See fault „Low air flow“
Abnormal noises /
vibrations
Dirt deposits on the impeller See chapter maintenance and cleaning
Imbalance of the impeller Contact the supplier
Connection with intake or exhaust pipe cau-
ses vibrations and oscillations
Install fan with vibration dampers
Fixing screws released Tighten screws
Fault of the ball bearings Contact the supplier
Loose impeller blade Contact the supplier
Low airflow Impeller runs in the wrong direction (wrong
air transport direction)
Note the marking on the device / nameplate. Check
electrical connections
High pressure losses in the system Improve piping configuration or select a more power-
ful fan
Back flow shutter flaps not at all or only
partially open
Check the backflow flap on site
Inlet clogged Remove blockage
Speed control incorrectly set / incorrectly
connected
Check settings / switching unit and possibly adjust /
connect
16 | MPS...D.40
EN
NOTES:
www.ruck.eu | 17
Information updated
print 31.10.2023
mpss_pb_03d_k10001_en
We reserve the right to make changes
Language:
English
ruck Ventilatoren GmbH
Max-Planck-Str. 5
D-97944 Boxberg-Windischbuch
Tel. +49 7930 9211-300
Fax +49 7930 9211-166
www.ruck.eu
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI