Swegon TBLZ-1-24-2/TBLZ-1-24-3 Owner's manual

Type
Owner's manual

Swegon TBLZ-1-24-2/TBLZ-1-24-3: temperature sensors for precise temperature measurement and control in various applications.

These digital sensors provide reliable temperature readings with a wide measurement range of -55 °C to +125 °C. Whether you need to monitor room temperature for comfort control or measure outdoor temperature for ventilation systems, these sensors deliver accurate data.

Installation is simple, with options for wall mounting or placement in a box. The included adaptor allows for easy connection to a 3-meter modular cable, providing flexibility in positioning.

The TBLZ-1-24-2 sensor is designed for indoor use, while the TBLZ-1-24-3 is suitable for outdoor applications with its IP54 rating. Both sensors feature screw terminals for secure connections.

Swegon TBLZ-1-24-2/TBLZ-1-24-3: temperature sensors for precise temperature measurement and control in various applications.

These digital sensors provide reliable temperature readings with a wide measurement range of -55 °C to +125 °C. Whether you need to monitor room temperature for comfort control or measure outdoor temperature for ventilation systems, these sensors deliver accurate data.

Installation is simple, with options for wall mounting or placement in a box. The included adaptor allows for easy connection to a 3-meter modular cable, providing flexibility in positioning.

The TBLZ-1-24-2 sensor is designed for indoor use, while the TBLZ-1-24-3 is suitable for outdoor applications with its IP54 rating. Both sensors feature screw terminals for secure connections.

GB.TBLZ242.160408
Registered design. The company reserves the right to make design changes without prior notice. www.swegon.com 1
1. General
The temperature sensor is intended for wall mounting
and is equipped with a screw terminal connection for a
cable. Temperature sensor TBLZ-1-24-2 is designed for
measuring the room temperature and temperature sensor
TBLZ-1-24-3 is designed for measuring the outdoor tem-
perature. The function selector switch is used for setting
whether the temperature sensor shall measure the room
temperature or the outdoor air temperature.
An adaptor for conversion from a 4 wire cable to a 3
metre long modular cable is supplied with the sensor.
2. Application
2.1 GOLD RX/PX/CX/SD Version E/F, GOLD LP,
COMPACT
Room temperature sensor
The room temperature sensor is designed for supplement-
ing the extract air temperature sensor inside the air han-
dling unit.
The room temperature sensor is used when the tempera-
ture in a room shall be given priority.
It can also be used if there are temperature losses in the
extract air duct up to the air handling unit’s point of meas-
urement.
Outdoor temperature sensor
The outdoor temperature sensor is designed for supple-
menting the outdoor air temperature sensor inside the air
handling unit.
The outdoor air sensor is used when measurement of the
outdoor temperature is required while the air handling unit
is idle or the outdoor air duct is closed off.
Modular cable
Adaptor
Instructions for Installation
Room temp. sensor TBLZ-1-24-2, for wall installation, IP20/
Outdoor temp. sensor TBLZ-1-24-3, for outdoor inst., IP54
GOLD/COMPACT
Temperature sensor, TBLZ-1-24-2
Temperature sensor, TBLZ-1-24-3
GB.TBLZ242.160408
Registered design. The company reserves the right to make design changes without prior notice.
2 www.swegon.com
5. Electrical Connections
The electrical connections should be wired by a qualified
electrician in accordance with local electrical safety regula-
tions.
5.1 Air handling unit
Connect the modular cable to an optional modular con-
nection, marked Internal Bus 1 (GOLD LP/COMPACT) or
COM1-3 (GOLD RX/PX/CX/SD Version E/F), on the control
unit of the air handling unit. See the wiring diagrams
below and on the following page.
5.2 Adaptor and temperature sensor
Connect the modular cable from the air handling unit to
the modular connection of the adaptor. Connect a 4-wire
cable (not supplied by Swegon) between the screw con-
nections on the adaptor and the temperature sensor. For
installation in a box, insert the cable through the backside
of the temperature sensor. For installation on a wall, insert
the cable according to the instructions on the cover and
mounting plate of the temperature sensor.
The temperature sensor is digital and depending on the
nature of the installation may be sensitive to external
interference. The cable to the temperature sensor must
not be run parallel near a power cable. If the sensor cable
crosses a power cable, it should cross it at a 90° angle.
3. Installation
3.1 Temperature sensors
3.1.1 To install the room temperature sensor
Remove the top cover on the temperature sensor by press-
ing the locking tabs on the sides of the cover with a small
screwdriver, to disengage them. Secure the temperature
sensor to an interior wall by means of two screws. The
temperature sensor’s slots that enable airflow through
the sensor must be vertical. Position the temperature
sensor at a representative point of measurement about 1.5
metres above the floor. Avoid sources of interference such
as radiators, direct solar radiation and the like.
3.1.2 To install the outdoor temperature sensor
Position the temperature sensor at a representative point
of measurement. Avoid sources of interference such as
direct solar radiation and the like.
3.2 Adaptor
Remove the cover on the adaptor by pressing in the tab
on the side of the cover with a small screwdriver and
then twist the cover. Secure the adaptor at an appropri-
ate place by means of two screws or the double-stick pad
(supplied).
4. Technical Data
4.1 Room temperature sensor
Dimensions (W x H x D) 80x80x16 mm
Degree of protection IP 20
Range of measurement -55 °C – +125 °C
Connection terminals, area 0.1 - 1.0 mm2
Colour White, RAL 9010
4.2 Outdoor temperature sensor
Dimensions (W x H x D) 97x63x34 mm
Degree of protection IP 54
Range of measurement -55 °C – +125 °C
Connection terminals, area 0.1 - 1.0 mm2
Colour Grey
4.3 Adaptor
Dimensions (W x H x D) 52x58x22 mm
Degree of protection IP 20
Colour Beige
4.4 Modular cable
Cable 6-pin
Connection RJ12
Length 3 metres
Colour Black
GB.TBLZ242.160408
Registered design. The company reserves the right to make design changes without prior notice. www.swegon.com 3
SD
WLAN
CPU 1
CPU 2
1
A2
B3
GND 4
+5
-6
+7
-8
+9
-10
+11
-12
+13
-
SA TempCom 5Com 4Com 3Com 2Com 1
14
+15
-16
+17
-18
+19
-
Heat Cool
20
C21
NO 22
C23
NO 24
C25
NO 26
C27
NO 28
P29
G30
G0 31
G32
G0
24V AC
Sensor 1Sensor 2Sensor 4Sensor 3 Com 6 Com 7 Com 8 Com 9 Com 10 Com 11
+
33 -
34 G
35 G0
36 Y
37 U
38 39 40
24V AC In
41 42
18V AC In
45 46
230V AC In
4743 44
230V AC Out
SD
WLAN
CPU 1
CPU 2
1
A2
B3
GND 4
+5
-6
+7
-8
+9
-10
+11
-12
+13
-
SA TempCom 5Com 4Com 3Com 2Com 1
14
+15
-16
+17
-18
+19
-
Heat Cool
20
C21
NO 22
C23
NO 24
C25
NO 26
C27
NO 28
P29
G30
G0 31
G32
G0
24V AC
Sensor 1Sensor 2Sensor 4Sensor 3Com 6Com 7Com 8Com 9Com 10 Com 11
+
33 -
34 G
35 G0
36 Y
37 U
38 39 40
24V AC In
41 42
18V AC In
45 46
230V AC In
4743 44
230V AC Out
Control unit
Adaptor
Temperature sensor
To be connected to op-
tional modular connec-
tion marked COM1-3
BL
YL
GR
WH
BK
RD
V+
A
V-
B
Max. permissible length: 100 metres;
min. permissible cross-sectional area:
0.5 mm2. A twisted pair cable is recom-
mended where 24 V DC is extended in
a pair and bus communication (A and
B) in a pair.
B
A
V-
V+
Insert the cable through
the backside.
Function selector switch
Installation
in a box
Installation
on a wall
Insert the
cable accord-
ing to the
instructions
on the cover
and mount-
ing plate.
GOLD RX/PX/CX/SD, version E/F
Alt. 1
Alt. 2
Control unit
Adaptor
Temperature sensor
To be connected to optional modular
connection marked COM1-3
B
A
V-
V+
Insert the cable through the backside.
Function selector switch
Installation
in a box
Installation
on a wall
Insert the cable according to
the instructions on the cover
and mounting plate.
The function selector switch on each temperature sensor must
be set to position 1-4 and must not share the same position with
another function selector switch. Their mutual order is of no
importance.
Example:
If two sensors are fitted, the function selector switches should be
set to position 1 and 2 respectively. If three sensors are fitted, the
function selector switches should be set to position 1, 2 and 3
respectively, and so forth.
B
A
V-
V+
V+
V-
A
B
Connect the leads according
to the following:
Adaptor Temp. sensor
Screw GR Terminal A
Screw RD Terminal B
Screw BK Terminal V-
Screw YL Terminal V+
Temp. sensor Temp. sensor
Terminal A Terminal A
Terminal B Terminal B
Terminal V- Terminal V-
Terminal V+ Terminal V+
Connect the leads according
to the following:
Adaptor Temp. sensor
Screw GR Terminal A
Screw RD Terminal B
Screw BK Terminal V-
Screw YL Terminal V+
Temp. sensor Temp. sensor
Terminal A Terminal A
Terminal B Terminal B
Terminal V- Terminal V-
Terminal V+ Terminal V+
B
A
V-
V+
B
A
V-
V+
B
A
V-
V+
V+
V-
A
B
BL
YL
GR
WH
BK
RD
V+
A
V-
B
BL
YL
GR
WH
BK
RD
V+
A
V-
B
Max. permissible length: 100 metres; min. permis-
sible cross-sectional area: 0.5 mm2. A twisted pair
cable is recommended where 24 V DC is extended
in a pair and bus communication (A and B) in a
pair.
The function selector switch on respective room tem-
perature sensors connected to an air handling unit,
should be preset to position 1-4; on Xzone room
temperature sensors to position 5-8 or on outdoor tem-
perature sensors to position A-D. The function selector
switches must not be set to the same position as that of
another function selector switch. Their mutual order is
of no importance.
Example:
For a room temperature sensor connected to an air
handling unit, the function selector switch should be
set to position 1. If two sensors are used, the function
selector switches should be set to position 1 and 2
respectively, etc.
GB.TBLZ242.160408
Registered design. The company reserves the right to make design changes without prior notice.
4 www.swegon.com
12 34 5678 910111213
1415 16 17 18 19 20 21 22 23 24 25 26 2728 29 3031 32 3334 3536 37
ON
Control unit
Adaptor
Temperature sensor
Internal BUS 1
To be connected to optional modular
connection marked Internal BUS 1
GR
YL
BL
RD
BK
WH
A
V+
B
V-
Max. permissible length: 100 metres; min. permissible cross-sectional
area: 0.5 mm2. A twisted pair cable is recommended where 24 V DC is
extended in a pair and bus communication (A and B) in a pair.
B
A
V-
V+
Insert the cable through the backside.
Function selector switch
Installation
in a box
Installation
on a wall
Insert the cable according to
the instructions on the cover
and mounting plate.
GOLD LP/COMPACT
If the temperature sensor is used as a room temperature
sensor, set the function selector switch to position 0.
If the temperature sensor is used as an outdoor tempera-
ture sensor, set the function selector switch to position A.
Connect the leads according to the following:
Adaptor Temperature sensor
Screw GR Terminal A
Screw RD Terminal B
Screw BK Terminal V-
Screw YL Terminal V+
B
A
V-
V+
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Swegon TBLZ-1-24-2/TBLZ-1-24-3 Owner's manual

Type
Owner's manual

Swegon TBLZ-1-24-2/TBLZ-1-24-3: temperature sensors for precise temperature measurement and control in various applications.

These digital sensors provide reliable temperature readings with a wide measurement range of -55 °C to +125 °C. Whether you need to monitor room temperature for comfort control or measure outdoor temperature for ventilation systems, these sensors deliver accurate data.

Installation is simple, with options for wall mounting or placement in a box. The included adaptor allows for easy connection to a 3-meter modular cable, providing flexibility in positioning.

The TBLZ-1-24-2 sensor is designed for indoor use, while the TBLZ-1-24-3 is suitable for outdoor applications with its IP54 rating. Both sensors feature screw terminals for secure connections.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI