4 83015700aUK– Translation of the original operating manual – We reserve the right to make changes without notice.
Scope of delivery
INSTALLATION PACKAGE 50/50, 50/65, 65/65
SIZE 1: IPFK 50/50:
Brine/Water H series 29 KW - 56 kW
Brine/Water series 37 KW - 69 kW
Water/Water series 55 KW - 110 kW
4 x rubber expansion joints DN 50
16 x bolts DIN 933 M16x60 8.8 zinc-coated
16 x nuts DIN 934 M16 8.8 zinc-coated
32 x washers DIN 125 A17 zinc-coated
SIZE 2: IPFK 65/50:
Brine/Water H series 70 kW - 100 kW
Brine/Water series 110 kW
2 x rubber expansion joints DN 50
2 x rubber expansion joints DN 65
16 x bolts DIN 933 M16x60 8.8 zinc-coated
16 x nuts DIN 934 M16 8.8 zinc-coated
32 x washers DIN 125 A17 zinc-coated
SIZE 3: IPFK 65/65:
Brine/Water series 125 kW - 160 kW
4 x rubber expansion joints DN 65
16 x bolts DIN 933 M16x60 8.8 zinc-coated
16 x nuts DIN 934 M16 8.8 zinc-coated
32 x washers DIN 125 A17 zinc-coated
STORAGE
See DIN 7716, Guidelines for the storage of rubber parts. Rubber
expansion joints must be stored stress-free, free from deformation and
kinks.
Rubber expansion joints with steel anges must be stored upright on
the anges (otherwise risk of crushing).
STORAGE ROOM
The storage room should be cool, dry, dust-free and moderately
ventilated.
OXYGEN AND OZONE
Protect rubber parts from draughts. Cover if necessary.
Do not operate any ozone-producing equipment such as electric
motors, uorescent light sources, etc. in the storage room.
MATERIALS STORED WITH THE EXPANSION JOINTS
Do not store any solvents, fuels, chemicals or similar materials in the
storage room at the same time as the expansion joints.
Installation
Check the packaging of the rubber expansion joints for damage. Never
install damaged expansion joints.
Check the installation gap allowed for their installation; the mating
ange should be inserted ush.
Maximum dierence in the gap to the pressure joint: + 10 mm minus
appropriate expansion allowance. Lateral deviation of the anges: 5 mm
maximum.
Do not use sharp-edged tools. No additional seals are required. The
rubber ange of the expansion joint seals directly against the pipe
ange.
In the case of expansion joints with through holes, the bolts must be
inserted with the bolt head facing the bellows, to avoid damaging the
bellows body under pressure.
The bolts of the ange must be tightened alternately, uniformly tight.
Further, also ensure that the sealing bead does not cant. The protruding
sealing surface should be uniformly pressed together, all-round. The
bolts must be tightened uniformly tight, cross-wise in 3 to 4 passes.
See tightening torques.
Do not weld near the rubber expansion joints. If necessary, cover the
expansion joint to protect it from welding heat and ying sparks. (Sparks
and temperatures above 90°C damage the rubber parts!)
ATTENTION
In case of welding work on the whole pipe system, steel wire expansion
joints can become irreparably damaged by stray currents ore electrical
earth cable. The anode and cathode of the electric welding connection
must always lie on the same section of the pipe. (Not separated by the
rubber expansion joint!)
ATTENTION:
The bellows may not be coated or insulated (heating and hardening of
the rubber).