HTP Versa-Hydro Solar Installation Drawings

Type
Installation Drawings

HTP Versa-Hydro Solar is a versatile and efficient water heater that utilizes solar energy to provide hot water for your home. With its innovative design, it combines the power of the sun with the reliability of a traditional water heater to deliver a sustainable and cost-effective solution for your hot water needs.

HTP Versa-Hydro Solar is a versatile and efficient water heater that utilizes solar energy to provide hot water for your home. With its innovative design, it combines the power of the sun with the reliability of a traditional water heater to deliver a sustainable and cost-effective solution for your hot water needs.

24
LP-314 REV. 3.24.14
F. HYDRONIC PIPING
Figure 9 LP-314-3
NOTES:
1. Minimum pipe size should match connection size on appliance. Upsize pipe accordingly if greater flow is required.
2. A thermal expansion tank suitable for potable water must be sized and installed within the piping system between the check valve
and cold water inlet of the appliance.
3. Gas line must be rated to the maximum capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check.
NOTES FOR AIR HANDLER APPLICATION (APPLIES TO DOMESTIC WATER OUTLET CONNECTIONS ONLY):
1. MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER
HEATER TO THE FAN COIL IN THE AIR HANDLER.
2. MASSACHUSETTS STATE PLUMBING CODE REQUIRES AN ELECTRONICALLY TIMED CIRCULATOR PUMP TO ACTIVATE
EVERY SIX HOURS FOR 60 SECONDS. THIS CIRCULATOR IS REQUIRED TO BE BRONZE OR STAINLESS.
3. ALL WATER PIPING MUST BE INSULATED.
4. YOU MUST INSTALL A VACUUM RELIEF VALVE PER 248 CMR.
NOTE: THIS DRAWING IS MEANT TO DEMONSTRATE SYSTEM PIPING ONLY. THE INSTALLER IS RESPONSIBLE FOR ALL
EQUIPMENT AND DETAILING REQUIRED BY LOCAL CODES.
DO NOT use the heat pack for high temperature (over 160
o
F) applications. Failure to comply will result in substantial overworking of the
appliance, and possibly lead to early appliance failure. Use of the heat pack for high temperature applications WILL VOID the warranty.
25
LP-314 REV. 3.24.14
Figure 10 LP-314-PIPING-1
NOTES:
1. Minimum pipe size should match connection size on appliance. Upsize pipe accordingly if greater flow is required.
2. A thermal expansion tank suitable for potable water must be sized and installed within the piping system between the check valve
and cold water inlet of the appliance.
3. Gas line must be rated to the maximum capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check.
NOTES FOR AIR HANDLER APPLICATION (APPLIES TO DOMESTIC WATER OUTLET CONNECTIONS ONLY):
1. MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER
HEATER TO THE FAN COIL IN THE AIR HANDLER.
2. MASSACHUSETTS STATE PLUMBING CODE REQUIRES AN ELECTRONICALLY TIMED CIRCULATOR PUMP TO ACTIVATE
EVERY SIX HOURS FOR 60 SECONDS. THIS CIRCULATOR IS REQUIRED TO BE BRONZE OR STAINLESS.
3. ALL WATER PIPING MUST BE INSULATED.
4. YOU MUST INSTALL A VACUUM RELIEF VALVE PER 248 CMR.
NOTE: THIS DRAWING IS MEANT TO DEMONSTRATE SYSTEM PIPING ONLY. THE INSTALLER IS RESPONSIBLE FOR ALL
EQUIPMENT AND DETAILING REQUIRED BY LOCAL CODES.
DO NOT use the heat pack for high temperature (over 160
o
F) applications. Failure to comply will result in substantial overworking of the
appliance, and possibly lead to early appliance failure. Use of the heat pack for high temperature applications WILL VOID the warranty.
26
LP-314 REV. 3.24.14
Figure 11 LP-314-PIPING-2
NOTES:
1. Minimum pipe size should match connection size on appliance. Upsize pipe accordingly if greater flow is required.
2. A thermal expansion tank suitable for potable water must be sized and installed within the piping system between the check valve
and cold water inlet of the appliance.
3. Gas line must be rated to the maximum capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check.
NOTES FOR AIR HANDLER APPLICATION (APPLIES TO DOMESTIC WATER OUTLET CONNECTIONS ONLY):
1. MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER
HEATER TO THE FAN COIL IN THE AIR HANDLER.
2. MASSACHUSETTS STATE PLUMBING CODE REQUIRES AN ELECTRONICALLY TIMED CIRCULATOR PUMP TO ACTIVATE
EVERY SIX HOURS FOR 60 SECONDS. THIS CIRCULATOR IS REQUIRED TO BE BRONZE OR STAINLESS.
3. ALL WATER PIPING MUST BE INSULATED.
4. YOU MUST INSTALL A VACUUM RELIEF VALVE PER 248 CMR.
NOTE: THIS DRAWING IS MEANT TO DEMONSTRATE SYSTEM PIPING ONLY. THE INSTALLER IS RESPONSIBLE FOR ALL
EQUIPMENT AND DETAILING REQUIRED BY LOCAL CODES.
DO NOT use the heat pack for high temperature (over 160
o
F) applications. Failure to comply will result in substantial overworking of the
appliance, and possibly lead to early appliance failure. Use of the heat pack for high temperature applications WILL VOID the warranty.
27
LP-314 REV. 3.24.14
Figure 12 LP-314-PIPING-4
NOTES:
1. Minimum pipe size should match connection size on appliance. Upsize pipe accordingly if greater flow is required.
2. A thermal expansion tank suitable for potable water must be sized and installed within the piping system between the check valve
and cold water inlet of the appliance.
3. Gas line must be rated to the maximum capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check.
NOTES FOR AIR HANDLER APPLICATION (APPLIES TO DOMESTIC WATER OUTLET CONNECTIONS ONLY):
1. MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER
HEATER TO THE FAN COIL IN THE AIR HANDLER.
2. MASSACHUSETTS STATE PLUMBING CODE REQUIRES AN ELECTRONICALLY TIMED CIRCULATOR PUMP TO ACTIVATE
EVERY SIX HOURS FOR 60 SECONDS. THIS CIRCULATOR IS REQUIRED TO BE BRONZE OR STAINLESS.
3. ALL WATER PIPING MUST BE INSULATED.
4. YOU MUST INSTALL A VACUUM RELIEF VALVE PER 248 CMR.
NOTE: THIS DRAWING IS MEANT TO DEMONSTRATE SYSTEM PIPING ONLY. THE INSTALLER IS RESPONSIBLE FOR ALL
EQUIPMENT AND DETAILING REQUIRED BY LOCAL CODES.
DO NOT use the heat pack for high temperature (over 160
o
F) applications. Failure to comply will result in substantial overworking of the
appliance, and possibly lead to early appliance failure. Use of the heat pack for high temperature applications WILL VOID the warranty.
28
LP-314 REV. 3.24.14
Figure 13 LP-314-PIPING-5
NOTES:
1. Minimum pipe size should match connection size on appliance. Upsize pipe accordingly if greater flow is required.
2. A thermal expansion tank suitable for potable water must be sized and installed within the piping system between the check valve
and cold water inlet of the appliance.
3. Gas line must be rated to the maximum capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check.
NOTES FOR AIR HANDLER APPLICATION (APPLIES TO DOMESTIC WATER OUTLET CONNECTIONS ONLY):
1. MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER
HEATER TO THE FAN COIL IN THE AIR HANDLER.
2. MASSACHUSETTS STATE PLUMBING CODE REQUIRES AN ELECTRONICALLY TIMED CIRCULATOR PUMP TO ACTIVATE
EVERY SIX HOURS FOR 60 SECONDS. THIS CIRCULATOR IS REQUIRED TO BE BRONZE OR STAINLESS.
3. ALL WATER PIPING MUST BE INSULATED.
4. YOU MUST INSTALL A VACUUM RELIEF VALVE PER 248 CMR.
NOTE: THIS DRAWING IS MEANT TO DEMONSTRATE SYSTEM PIPING ONLY. THE INSTALLER IS RESPONSIBLE FOR ALL
EQUIPMENT AND DETAILING REQUIRED BY LOCAL CODES.
PART 6 - VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL
The appliance must be vented as detailed in this Venting Section. Ensure exhaust and intake piping complies with these instructions
regarding vent system. Inspect finished exhaust vent and intake piping thoroughly to ensure all joints are well secured, airtight, and
comply with all applicable code requirements, as well as with the instructions provided in this manual. Failure to properly install the vent
system will result in severe personal injury or death.
DO NOT use the heat pack for high temperature (over 160
o
F) applications. Failure to comply will result in substantial overworking of the
appliance, and possibly lead to early appliance failure. Use of the heat pack for high temperature applications WILL VOID the warranty.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5

HTP Versa-Hydro Solar Installation Drawings

Type
Installation Drawings

HTP Versa-Hydro Solar is a versatile and efficient water heater that utilizes solar energy to provide hot water for your home. With its innovative design, it combines the power of the sun with the reliability of a traditional water heater to deliver a sustainable and cost-effective solution for your hot water needs.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI