The appliance can be put into operation by the technician specified by the manufacturer. The
warranty applies to the appliance only if it was put into operation in accordance with the
instructions.
Before the test run, gas tightness and pressure tests have to be performed for the gas network.
- Clean the radiant tube from contamination (e.g. dust).
- Make sure that the appliance is electrically grounded.
- Check that the power supply of the heater was not interrupted by the thermostat or the
weekly schedule.
- Open the gas valve.
- The appliance can be switched on with the controller.
- Check that the nozzle pressure reaches the required operating pressure after the magnetic
valve. The following pressure values are required for the different gas types: nozzle
pressure for natural gas H and L depending on the appliance type: 8.6 mbar; 10 mbar; 11
mbar or 12 mbar, for liquid PB-gas: 24.9 mbar.
As soon as voltage is applied to the appliance, the blower starts to rotate. After a pre purging
period of 30 seconds, sparks are produced and the gas valve is opened.
When the sensing probe detects the presence of the flame, spark is de-energized (it is de-
energized after 3.5 seconds in all cases), and the burner starts to heat (the green control light
on the bottom part of the appliance is ON).
If the sensing probe does not detect flame, the appliance is switched to safety mode (red
control lamp is ON)
When the appliance goes into ‘lockout’, it can be reset by removing the mains plug.
To measure the efficiency of LAS exhaust gas extraction, the combustion air temperature has
to be measured in the combustion air inlet pipe right before the blower. For this, insert the
thermometer into the flexible hose or cut a small hole into the flexible hose, then seal the hole
with adhesive tape after the measurement (no pressure tightness is required)
If required, the factory setting of the venting inlet aperture can be modified to obtain
values of about 1,4-1,65 (for natural gas) and about 1,85 (for liquid gas).
For the setting, exhaust gas analyser is needed.