WEG PFW03-M12 / PFW03-M24 Configuration Guide

Type
Configuration Guide

WEG PFW03-M12 / PFW03-M24 is an automatic power factor controller that offers advanced features for precise and efficient reactive power compensation in electrical systems. With its ability to read and learn connection types, step types, and powers, this device simplifies setup and ensures optimal performance. The PFW03-M12 / PFW03-M24 monitors system parameters such as voltage, current, frequency, and power factor, providing comprehensive insights into electrical system health. It also features six different compensation modes, allowing for customized control based on specific application requirements.

WEG PFW03-M12 / PFW03-M24 is an automatic power factor controller that offers advanced features for precise and efficient reactive power compensation in electrical systems. With its ability to read and learn connection types, step types, and powers, this device simplifies setup and ensures optimal performance. The PFW03-M12 / PFW03-M24 monitors system parameters such as voltage, current, frequency, and power factor, providing comprehensive insights into electrical system health. It also features six different compensation modes, allowing for customized control based on specific application requirements.

PFW03-M12
PFW03-M24
Automatic Power Factor Controller
Reading for PF correction in one phase;
Compensation for 12 and 24 steps;
Steps can be capacitive or inductive;
Reads and learns connection types;
Reads and learns step types and powers;
Records switch counts and service rate for each step;
6 different modes of reactive power compensation;
Monitors the step dynamically. Checks if any step is
faulty (only for 12 steps);
PFW03-M12_24
Overview
Allows testing the steps via manual actuation of the
relays;
Automatic calculation of C/k;
response value C/K:
Represents the minimum step to be inserted
by the controller.
PFW03-M12_24
Overview
C = Lowest current among the steps;
K or Kct= CT ratio;
Q = Lowest power among the steps;
U = line voltage (V);
Measures and calculates:
- Current, voltage and frequency;
- Active, reactive and apparent power;
- Voltage and current harmonics up to the 51st order;
- THDV, THDI;
- Power factor and cosφ;
All values above per phase
Alarm configuration and saving of the last 50 alarms;
Allows setting an alternate power factor using a digital
input;
PFW03-M12_24
Overview
Saves active and reactive energy values hourly,
previous hour, daily, previous day, monthly, previous
month;
Import and export energy meter (kWh and kvarh) with
the choice of setting the start counting value and saving
the records in real time;
2 alarm output relays;
RS485 communication port, 2000 VRMS insulation;
Graphic LCD display and 6 keys
4-digit access password;
Real time clock;
PFW03-M12_24
Overview
Supply
Voltage.............95..410V AC +_ 10%
Frequency........45-65 Hz
Measurement Inputs
Voltage..... ……95..410V AC +_ 10% (L-N)
…………….......95..410V AC +_ 10% (L-L)
Current............. 0.01..6 A RMS
Frequency........ 45..65 Hz
Night/Day Input. 95.. 240 VAC RMS
Relay Outputs for Compensation
12/24 pcs.,
Max. switching voltage... : 250 VAC
Max. switching current..... : 2A
Alarm Relay Outputs:
2 pcs,
Max. switching current.....: 4A
Max. switching voltage….: 250 VAC
Max. switching power...... : 1250 VA
Protection class
IP40 front, IP20 rear
PFW03-M12_24
Technical data
1. Menus
2. Cosφ of the system;
3. Total active power;
4. Total reactive power;
5. Monthly average inductive rate;
6. Monthly average capacitive
rate;
7. Step number;
8. Step power;
9. Step type (C or I);
10.Voltage and current presence
indication;
11.Compensation mode selected;
12.Alarm indication activated;
13.Indication of temperature alarm
activated;
PFW03-M12_24
Description of the display functions
PF ~ 0.92
PFW03-M12_24
Description of the display functions
tan =
Q
P
14.Alarm relay activated;
15.Dynamic step monitoring
mode activated;
16.RS485 communication active;
17.Clock
PFW03-M12_24
Description of the display functions
PFW03-M12_24
Description of the display functions - 24 steps
If the operator presses the "down" key, the reading of each
step is enabled.
PFW03-M12_24
In the step menu, press the right and left keys to navigate
across the menu shown below:
Description of the display functions - 24 steps
Settings - Startup - 1st power-on
PFW03-M12_24
When you turn on the PFW03 for the first time, the following
screen will be displayed:
Startup Settings
PFW03-M12_24
Settings - Startup - 1st power-on
Use the keys to set the date:
PFW03-M12_24
Use the virtual keyboard to set the current transformer ratio -
CTR:
Startup Settings
Settings - Startup - 1st power-on
- Press the OK key to open the
virtual keyboard and enter the
numbers;
- After entering the numbers,
press OK on the virtual
keyboard to confirm.
PFW03-M12_24
Use the virtual keyboard to set the voltage transformer ratio -
VTR:
Settings - Startup - 1st power-on
Startup Settings
- Press the OK key to open the
virtual keyboard and enter the
numbers;
- Use the virtual keyboard to
enter the decimal point;
PFW03-M12_24
Settings - Startup - 1st power-on
In this menu, set how the PFW03 will be connected to the line.
There are 2 types: phase-phase and phase-neutral.
Startup Settings
PFW03-M12_24
Settings - Startup - 1st power-on
In this menu, you define the number of steps to be used.
The Learning function only works for three-phase capacitors.
Startup Settings
PFW03-M12_24
Settings - Startup - 1st power-on - End
NOTE: The startup settings page is automatically shown the first
time the PFW-03 is turned on.
After that, use the available menus to access it.
Startup Settings
PFW03-M12_24
Settings Menu
PFW03-M12_24
Settings Menu - Quick setup
In this menu, the PFW03 is set.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76

WEG PFW03-M12 / PFW03-M24 Configuration Guide

Type
Configuration Guide

WEG PFW03-M12 / PFW03-M24 is an automatic power factor controller that offers advanced features for precise and efficient reactive power compensation in electrical systems. With its ability to read and learn connection types, step types, and powers, this device simplifies setup and ensures optimal performance. The PFW03-M12 / PFW03-M24 monitors system parameters such as voltage, current, frequency, and power factor, providing comprehensive insights into electrical system health. It also features six different compensation modes, allowing for customized control based on specific application requirements.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI