ELECTRICAL CONNECTIONS
STEP 1:
NOTE: Luminaires with BML sensor will have the dimming leads
capped off. Keep the dimming leads on these luminaires capped
off.
Using Listed 90°C minimum rated wire connectors make the
following electrical connections within the adjustable fitter
wiring compartment:
a. For 120/277/347V connect the black fixture lead to the
voltage supply or Hot 1 (for 208/240/480V wiring).
b. For 120/277/347V connect the white fixture lead to the
neutral supply or Hot 2 (for 208/240/480V wiring).
c. Connect the green or green/yellow ground lead to
ground.
d. If fixture ordered with –F fuse option (Single-Phase
connection only)
• Connect the black fixture lead to the voltage supply.
• Connect the white fixture lead to the neutral supply.
• Connect the green or green/yellow ground lead to
ground.
e. If Dimming is an option; connect the violet dimming
positive fixture lead to the supply dimming positive lead.
If dimming is not being used, cap off the violet lead.
f. If Dimming is an option; connect the grey or pink
dimming negative fixture lead to the supply dimming
negative lead. If dimming is not being used, cap off the
grey or pink lead.
g. Connect orange fixture lead to orange supply lead.
h. Connect red fixture lead to brown supply lead.
LINE
OR HOT 1
GREEN
LINE-BLACK
GROUND-GREEN
NEUTRAL-WHITE
DIM (-) GREY
OR PINK
DIM (+) VIOLET
NEUTRAL
OR HOT 2
DIM (+)
DIM (-)
SUPPLY WIRING
(DIMMING OPTIONAL)
LUMINAIRE
RED
ORANGE
BROWN
(CONTROLS FROM
PHOTOCONTROL
OPTIONAL)
ORANGE
NEMA® RECEPTACLE (OPTIONAL)
PLEASE READ: The method for rotating this NEMA receptacle is
different than other Cree Lighting Products. Rotation of the photocontrol
receptacle after photocontrol installation is not recommended. This may
disengage the electrical contacts, compromise the seal, or damage the
photocontrol.
STEP 1:
Remove protective cap.
STEP 2:
If necessary, rotate photocontrol receptacle so the arrow is pointed in the
north direction. Some photocontrols operate best when aimed between
the north-west and north-east direction. To rotate, lift upwards on the
photocontrol receptacle to disengage the internal lock, rotate, and then
release the photocontrol receptacle to return it to the locked position.
Ensure that the photocontrol receptacle has returned to the fully locked
position.
STEP 3:
Install photocontrol into photocontrol receptacle by inserting the blades
into the receptacle and turning clockwise. Ensure that the photocontrol is
fully locked in place by gently pulling upwards. Less than full engagement
of the photocontrol may result in a compromised seal.
BLUETOOTH® TECHNOLOGY ENABLED MULTILEVEL SENSOR
(OPTIONAL)
The 20’ to 40’ sensor lens comes installed on the sensor on the OSQ
luminaires. An 8’ to 20’ sensor lens and aisle shroud may be found in the
hardware bag. To change the lens, unscrew the existing lens, remove the
shroud from the replacement lens and screw it back on to the sensor.
For Sensor information please visit the Leviton website, www.Leviton.com
and search on ZLDxZ-xxx/OFDxZ-xxx.
Configuration is made using the Leviton Smart Sensor App from a
smartphone or other Bluetooth® enabled Android or iOS device. The
Smart Sensor App can be downloaded from either Goggle Play or Apple