Johnson & Starley WARMCAIR C10DW Installation guide

Category
Water heaters & boilers
Type
Installation guide
www.johnsonandstarley.co.uk
Johnson & Starley Ltd
Rhosili Road
Brackmills, Northampton
NN4 7LZ
WarmCair Condensing Warm Air
and Hot Water
FM 525200
For Installation in Mainland UK only.
INSTALLATION,
COMMISSIONING
& SERVICING
INSTRUCTIONS
WARMCAIR C10DW
Condensing Air & Water Heater
High Efficiency Downflow
Condensing Air & Water Heater
WarmCair C10DW - G.C. No. 43-417-59
These instructions are to be left with the User
Publication No. ZZ 1446-5
October 2021
www.johnsonandstarley.co.uk
2
TECHNICAL UPDATES
INFORMATION REGARDING UPDATES TO THIS MANUAL ARE LISTED BELOW AND SHOULD BE NOTED BEFORE
COMMENCING WITH ANY INSTALLATION WORK.
Date of Amendment Version No Page Description
15/05/2020 ZZ1446-4 5 Amendment to Magnetic-Non Magnetic Filter requirements
15/05/2020 ZZ1446-4 15 Changes to parts and part Numbers
15/05/2020 ZZ1446-4 29 New Fault Finding Flow Charts
15/05/2020 ZZ1446-4 39 Changes to list of ancillaries
31/03/2021 ZZ1446-4 8 Amendment to Return Air duct system
3
Sales/Spares & Replacement Help Line 01604 762881
CONTENTS
The Benchmark Scheme 3
1. Features 4
2. General Description 4
3. Building Standards & Regulations 5
4. Safety, Electrical & Gas Information 5
General Safety Information
Power Flushing
Electrical Connections
Handling the unit
Operating the Appliance
Gas Supply
Water Supply
5. Technical Data 7
Technical Data
Performance Data
6. Heater Positioning 8
7. Heater Compartment Clearances 8
8. Duct System 8
Return Air
9. Heating System 9
Warm Delivered Air System
Additional Radiator System If Fitted
Schematics
Pipework Sizing
Water Treatment
Hot Water System For DHW
10. Flue Instructions 11
Types of Flue Systems
Flue Terminal Positions
Flue Requirements & General Information
Extended Horizontal Flue Configuration Example
Vertical Flue Configuration Example
Optional Roof Outlets
Plume Terminal Outlets
Conventional 60/100 mm Flue Accessories Part No.s
11. Condensate Pump & Drain Tube 16
Condensate Pump
Condensate Tube Routing Options
12. Electrical 17
13. Warm Air Fan Performance 17
14. Operating Modes 17
15. Domestic Hot Water Heating Commissioning 18
Check Gas Installation
Check the Operational Gas Inlet Pressure
Air Purge Function
Reset Procedure
16. Initial Lighting 19
Warm Air Central Heating
Water Circulation System
Balance the System
Central Heating Water Temperatures
17. Warm Air Heating Commissioning 20
With No OpenTherm Controller Fitted
18. Handing Over 19
19. Servicing & Maintenance 21
Service Schedule
Initial Inspection
Servicing Sequence
Flue Inspection & Checks
Gaining Access to the Hot Water
Air Filter Removal
Upper Panel Removal
Control Panel
Combustion Air Fan
Burner Assembly
Water Heat Exchanger
Gaining Access for Servicing the Heat Generator
Lower Panel Removal
Air Circulation Fan
Air Heat Exchanger
Condensate Pump
Condensate Trap
20. Parts Replacements 25
Part Replacements without Draining the System
Control Panel
Burner Injector
Combustion Air Fan
Burner Assembly
Flow & Return Thermistor Sensors
Ignition/Detection Electrode
Gas Valve
Warm Air PCB
PCB Interface
Air Circulation Fan
Condensate Pump
Condensate Trap
Diverter Actuator Head
Parts Replacement By Draining the System
Draining the Appliance
Pump Head
Diverter Cartridge
Automatic Air Vent
Air Heat Exchanger
21. Fault Finding 29
22. Wiring Diagram 37
23. Dimensions 38
24. Exploded Spares Diagram 39
25. List of Spares 40
26. List of Ancillaries 42
27. Benchmark Checklist and Service Record 43
Code of Practice
Commissioning Checklist
Service Record
In the interest of continuous development Johnson and Starley reserves the right to change specification without prior notice. Johnson
and Starley prides itself on its ability to supply spare parts quickly and efficiently.
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION.
LEAVE THESE INSTRUCTION WITH THE USER OR AT THE GAS METER AFTER INSTALLATION
The Benchmark Scheme The Benchmark Scheme
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are
provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with
the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building
Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be
provided to the customer for future reference.provided to the customer for future reference.
Visit www.centralheating.co.uk for more information.Visit www.centralheating.co.uk for more information.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice, which is available from the Heating and Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice, which is available from the Heating and
Hot water Industry Council who manage and promote the Scheme. Hot water Industry Council who manage and promote the Scheme.
www.johnsonandstarley.co.uk
4
1. FEATURES
Appliance Classification:
The WarmCair C10DW has been
tested and CE certified by BSI Ltd for
use with NATURAL gas G20.
FEATURES
1. Flue Adaptor
(shown fitted but not supplied)
2. Flue Test Point
3. Inspection Glass
4. Ignition Detection Electrode
5. Burner Injector
6. Flow & Return Sensors
7. Pressure Differential Tube
8. Gas Valve
9. Air Filter
10. Condensate Trap
(at the back)
11. Gas Cock
12. Circulation Fan
13. HE Pump/Diverter Assembly
14. Return Water Temperature Sensor
15. Heat Exchanger
(warm Air)
16. Drain Cock
17. Access Panel
18. Condensate Pump
19. Condensate Pipe
20. Condensate Drain Tube
21. Electronic Air Filter & LED
22 PCB Interface
23. Combustion Fan
24. Warm Air PCB
25. Heat Generator
(water)
26. Flue Sensor
2. GENERAL DESCRIPTION
2.1 The WarmCair C10DW is a highly efficient combined condensing gas-fired water-to-air downflow forced
convection air heater and water heater. Significant reductions in Carbon and NOx emissions are achieved.
This appliance has been designed with two compartments, one to provide the user with Warm Air Central
Heating and one to provide Domestic Hot Water. Using sophisticated controls, enabling it to provide a warm
air heat output of 16.0 kW and hot water output of 24.2 kW, fully modulating down to 4.8 kW. It is room
sealed, with a stainless steel heat exchanger, using a vertical or horizontal Concentric Flue System.
The WarmCair C10DW combines air heater is ideally suited for new built dwellings and the replacement of
existing non-condensing air heaters. For Indirect system applications only.
2.2 “Summer Air Circulation” of unheated air is available by manual selection (see the user’s instructions)
2.3 The air is drawn in through the air filter or air cleaner (if fitted) and the heat exchanger by a centrifugal fan, and
is
discharged through the base of the unit. A Summer Air Circulation switch (optional) provides the facility to supply
unheated air to the air outlets during warm weather. Modairflow control is incorporated for modulating of the air
circulation fan.
9
14
1
2
3
4
8
11
10
12
13
23
21
24
25
26
15
16
17
19
20
18
22
FIGURE 1. CONTROL PANEL
5
7
6
5
Sales/Spares & Replacement Help Line 01604 762881
3. BUILDING STANDARDS & REGULATIONS
STATUTE LAW DEFINES THAT ALL GAS APPLIANCES MUST BE INSTALLED BY
COMPETENT PERSONS, i.e. GAS SAFE REGISTERED INSTALLERS.
GAS SAFE MEMBERSHIP ENQUIRIES TEL: 0800 408 5500 IN ACCORDANCE WITH
THE GAS SAFETY (INSTALLATION AND USE) REGULATIONS (CURRENT EDITION).
FAILURE TO COMPLY WITH THESE REGULATIONS MAY LEAD TO PROSECUTION.
3.1 INSTALLATION REGULATIONS
Building Standards (Scotland) (Consolidation) Regulations
Building Regulations Part L
Gas Safety (Installation and Use) Regulations (as amended)
The Water Fittings Regulations or Water bylaws in Scotland
Model and Local Authority Byelaws
Health & Safety Document No. 635.
The Electricity at Work Regulations, 1989.
Institute of Electrical Engineers (I.E.E) Wiring Regulations
EU Regulation No 811/2013 and No. 812/2013 supplement Directive 2013/20/EU
This appliance has been Tested and Certified in order to meet the necessary European Directives
and comply with the latest Building Regulations.
Efficiency of Hot Water Boilers Directive 92/42/EEC
Gas Appliance Directive 2009/142/EC
Low Voltage Directive 2006/95/EEC
Electromagnetic Compatibility Directive 2004/108EC
3.2 BUILDING STANDARDS AND REGULATIONS
Where no specific instructions are given, reference should be made to the relevant British Standard Code of
Practice.
BS 5440:1 Flues (for gas appliances of rated input not exceeding 70 kW).
BS 5440:2 Ventilation (for gas appliances of rated input not exceeding 70 kW).
BS EN 12828 Heating Systems in buildings: Design for water based heating systems.
BS EN 12831 Heating Systems in buildings: Method for calculation of the design heat load.
BS EN 14336 Heating Systems in buildings: Installation and commissioning of water based
heating systems.
BS 5546 Installation of gas hot water supplies for domestic purposes (2nd Family Gases)
BS 6798 Installation of gas fired hot water boilers of rated input not exceeding 70 kW.
BS 6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic
premises (2nd family gases).
BS 7671 Institute of Electrical Engineers (I.E.E) Wiring Regulations
IMPORTANT: This appliance is UKCA certificated for safety and performance. It is important that no modifications are
made to this appliance, unless fully approved in writing by Johnson & Starley Ltd. If in doubt, please ring Johnson & Starley
Ltd on Telephone 01604 762881.
4. SAFETY, ELECTRICAL, GAS & WATER INFORMATION
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE COMMENCING WITH THE INSTALLATION
4.1 GENERAL SAFETY INFORMATION
4.1.1 Only use WarmCair original spare parts on this appliance. Failure to do so will invalidate the guarantee.
4.1.2 The manufacturer’s instructions supplied must not be taken as overriding any statutory requirements.
4.1.3 No artificially softened water should be used to fill the central heating system.
4.2 POWER FLUSHING - When a radiator system is also connected.
4.2.1 The system can be damaged by debris entering the heat exchanger and reduce efficiency. It is recommended
that the appliance is flushed, follow these guidelines as this will protect the unit and prolong its life.
4.2.2
It is important that the system is flushed thoroughly before the appliance is left to operate (as recommended in BS
7593) in order to maintain an efficiently operating heating system. For replacement installations, the system MUST
be flushed with the old unit in situ, in order to prevent the appliance becoming a trap for system debris. Once the
system has been flushed, an inhibitor (suitable for stainless steel heat exchangers) should be added. Appropriate
inhibitors are available, for example Sentinel, Fernox and Salamader.
4.3 MAGNETIC AND NON MAGNETIC FILTERS
For new and replacement installations a Magnetic & Non Magnetic filtration system must be fitted on all returns to
the appliance.
4.3.1 Failure to carry out the above procedures will invalidate the guarantee!
www.johnsonandstarley.co.uk
6
GAS LEAKS
DO NOT OPERATE ANY ELECTRICAL SWITCHES, OR USE A
NAKED FLAME TURN OFF THE GAS SUPPLY. VENTILATE THE
AREA BY OPENING DOORS AND WINDOWS. CALL THE NATIONAL
GAS EMERGENCY SERVICE ON
0800 111999
FIGURE 2. GAS COCK PRESSURE DROP
3
2.5
2
1.5
1
0.5
0
PRESSURE DROP (mbar)
0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0
HEAT INPUT TO BOILER (kW)
4.4 ELECTRICAL INFORMATION
4.4.1 Ensure the mains supply voltage, frequency, number of phases and power rating comply with details on the rating label.
4.4.2 All wiring must be in accordance with the appropriate standards. The equipment must be supplied with a double pole isolator
switch.
4.5 HANDLING THE UNIT
4.5.1 Ensure safety regulations and practices are adhered to when installing and using this equipment
4.5.2 The weight of this appliance exceeds that recommended for a one-man lift. It will therefore be necessary to gain assistance at
times during the installation procedure.
4.5.3 It should be noted that this appliance may contain sharp edges. Care MUST be taken when handling the appliance to prevent
injury.
4.5.4 Once the appliance has been fired beware that certain parts will be hot to the touch.
4.5.5 Do not install flues during rain, high winds or in severe weather conditions.
4.6 GAS SUPPLY
4.6.1 It is the responsibility of the Gas Installer to size the gas installation pipework in accordance with BS 6891. Whilst the principle of
the 1:1 gas valve ensures the WarmCair Combined DHW range is able to deliver its full output at inlet pressures as low as 14mb,
other gas appliances in the property may not be as tolerant. When operating pressures are found to be below the minimum
meter outlet of 19mb these should be checked to ensure this is adequate for correct and safe operation.
4.6.2 Allowing for the acceptable pressure loss of 1mb across the installation pipework, it can be assumed that a minimum permitted
operating pressure of 18mb will be delivered to the inlet of the appliance. (Reference BS 6400-1 Clause 6.2 Pressure Absorption).
4.6.3 The external gas cock could further reduce the operating pressure when measured at its test point. The pressure drop is relative
to the heat input to the boiler (kW), refer to graph below.
IMPORTANT: Installation pipes must be fitted in accordance with BS 6891. In Ireland refer to IS.813.
4.7 WATER SUPPLY
4.7.1 Water connections to the unit should be by 22mm compression fittings that are suitable for the duty.
NOTE: UNDER NO CIRCUMSTANCES SHOULD ISOLATION VALVES BE FITTED.
IMPORTANT: It is recommended that the water system be drained and flushed prior to the installation of the unit. A strainer
should be fitted upstream of the unit. See Paragraph 4.2.
7
Sales/Spares & Replacement Help Line 01604 762881
NOTE: Gas consumption is calculated using a calorific value of 38.7 MJ/m³ gross or 34.9 MJ/m³ nett. To
obtain the gas consumption at a different calorific value:
a. For l/s - divide the gross heat input (kW) by the gross C.V. of the gas (MJ/m³)
b. For ft³/h - divide the gross heat input (Btu/h) by the gross C.V. of the gas (Btu/ft³)
c. For m³/h - multiply l/s by 3.6
TABLE 2. C10DW
PERFORMANCE DATA
MAXIMUM MINIMUM
Burner CO² (%)
case off
9.3 8.4
case on
9.5 8.6
± 0.5
PERFORMANCE DATA FOR WATER HEATING
Input Q
Net
kW 17 4.40
Gross
kW 18.9 4.88
Gas Consumption
m³/h 1.75 0.45
Output
Non condensing kW 16.75
Condensing
kW 18.48 4.83
NOx Classification
CLASS 5
Recommended Central Heating set point
80 °C
5. TECHNICAL DATA
TABLE 1. C10DW
Maximum weight lift kg 66
Gas supply mbar 2H - G20 - 20 mbar
Gas connection mm 15 mm copper
Gas Injector size mm 4.2 mm
Heating flow and return mm 22 mm copper
Flue terminal diameter mm 100 mm (4”)
Condense drain mm 6 mm ID
Electrical supply V ~ Hz 230 V ~ 50 Hz
Electrical rating W 150
External fuse rating A 3
WARM AIR HEATING
Nominal Rated Output kW 10
Air on Temperature ˚C 20
Air off Temperature ˚C 67
Water Supply Temperature ˚C 80
Water Return Temperature ˚C 73
Water Flow Rate l/s 0.4
Air Volume m³/h 576
ADDITIONAL DATA
ELECTRIC POWER CONSUMPTION 100 W (at rated heating capacity), 30 W (at minimal cap.), 10 W (standby mode)
USEFUL EFFICIENCY 88.6 % (at rated heating capacity), 98.9 % (at minimum capacity)
ENVELOPE LOSS FACTOR 0
IGNITION BURNER POWER CONSUM. 0 W
EMISSIONS OF NITROGEN OXIDES 33 mg / kWh
EMISSION EFFICIENCY 84.71 %
SEASONAL SPACE HEATING ENERGY EFFIC. 81.6 %
www.johnsonandstarley.co.uk
8
6. HEATER POSITIONING
6.1 This heater is not suitable for external installation unless it is protected from the elements by a suitable
enclosure. The enclosure must provide the clearance for installation, servicing and maintenance as well as
the correct level of ventilation. The selected position should allow for a suitable flue system to be installed.
6.2 When installed in a timber frame, building guidance should be taken from the Gas Industry Publication IGE/
UP-7 (Guide for Gas Installations in Timber Frame Housing).
6.3 BS 6798 gives details of the essential features for a compartment or cupboard where a gas appliance is to
be installed. An existing cupboard may require modification.
IMPORTANT: This system can only be used in conjunction with an indirect system application.
6.4 If the heater is installed in a room containing a bath or shower, it is important to locate the electrical switch
in a position where it cannot be touched by anyone using the bath or shower. The current IEE Wiring
Regulations (BS 7671) for England and electrical provision of the Building Regulations for Scotland gives
details.
6.5 Room ventilation for the heater is not necessary (as the heater draws its combustion air from the outside of
the building, cupboard or compartment ventilation), providing that the minimum clearances are maintained.
However, reference should be made to BS 5440 Pt. 2.
IMPORTANT: This appliance must be completely level. It MUST NOT lean in any direction. This would
cause problems with the condense draining.
7. HEATER COMPARTMENT CLEARANCES
7.1 IMPORTANT: If the heater is to be fitted to an existing base duct (warm air plenum), always ensure that
installation is carried out such that the rear of the heater is aligned with the rear of the base duct so that any
overhang or blanking off will be at the front. In any event, blanking plates must be mechanically secured and
all joints sealed.
7.2 When the heater is fitted into a compartment, a minimum clearance from the compartment walls of 3 mm
(1/8”) at the sides, rear and front must be left. Where clearances are less than 75 mm, internal surface must
be lined with non-combustible material and the compartment must be of a fixed rigid structure. However,
there is no requirement for the use of non-combustible material at the front of the unit. Consideration should
also be given to the space required for the removal and replacement of the filter tray and the entry of the
gas and electrical supplies. If gas connections are made from a side entry, a minimum clearance of 75 mm
(3”) is required at that side.
7.3 For service access, a minimum clearance of 450 mm (18”) is required at the front of the heater. Space must
also be allowed, in a compartment installation, to permit the complete removal of the heater.
7.4 In airing cupboard installations, the part used as the air heater compartment must comply with the relevant
section of BS 5864 and must be completely separated by either a non-combustible partition or a perforated
metal partition with the perforations not exceeding 13 mm (½”). The secondary flue must be a tight fit where
it passes through the partition and must be suitably protected (see BS 5440: Part 1).
7.5 In understairs installations, the compartment must comply with the relevant section of BS 5864, provided
that in addition all internal surfaces (including the base) are non-combustible or lined with non-combustible
material. This requirement is applicable only to dwellings of more than two storeys.
7.6 In free-standing installations, (see instructions packed with top closure kit), only one or two walls will be in
close proximity to the air heater; these must be non-combustible.
7.7 Where the air heater is to be installed onto a combustible surface and under-floor ducting used, a suitable
base tray MUST be used in order to provide insulation.
NOTE: where a base plenum is used, no base tray is required!
7.8 Although two permanent ventilation openings are not required, consideration should be given to the amount
of heat emitted by any ductwork present in the compartment, otherwise the compartment temperature
could increase and will affect the safe operation of the appliance and its controls.
8. DUCT SYSTEM (See British Design Manual - Gas fired Warm Air Heating)
8.1 RETURN AIR
8.1.1 A room-sealed heater can be installed without positive return air ducting, provided that the path between
the return air grille and the heater return air inlet is protected in such a manner that the required airflow is
maintained at all times (BS5864).
8.1.2 The return air grille MUST have a free area of not less than 900 cm² (140 in²). It is recommended that the
return air duct not be routed directly from the main living area, but from a convenient central area serving
the remainder of the dwelling.
8.1.3 The return air system should be constructed of fire-resistant material where used. It is extremely important
that the correct size of return air grilles and ducting is used. The return air duct area should not be less than
450 cm² (70 in²). If flexible duct is used the duct diameter should not be less than 300 mm (12”) diameter.
8.1.4 An adequate and unobstructed return air path is essential from areas not served by a directly ducted return
and to which warm air is delivered. All such rooms should be fitted with relief grilles which have a free area of
0.0088 m2/kW (1 in²/250 Btu/h) of heat supplied to the room. The only exceptions are kitchens, bathrooms
and WCs.
8.1.5 The return air duct should allow for ease of removal for access to the flue.
8.1.6 All duct work in the room or internal space in which the heater is installed shall be mechanically secured and
sealed with ducting tape.
8.1.7 If a return air duct is not to be fitted, the top of the unit must be suitably guarded to prevent blockage.
9
Sales/Spares & Replacement Help Line 01604 762881
9. HEATING SYSTEM
9.1 WARM DELIVERED AIR SYSTEM
9.1.1 All duct work, including riser ducts, should be fully insulated with 50 mm (2”) fibre-glass or
similar. If short extended duct runs are taken below floor level, these should be similarly
insulated and, in addition, wrapped with a sound vapour proof barrier. They must also be
protected from crushing.
9.1.2 The duct system should be carefully designed (as given in the guidelines in the British
System Design Manual) to suit the needs of specific heating requirements and building
layout. The type of duct system (e.g. radial/extended, plenum/stepped) should be
installed using the least number of fittings to minimise airflow resistance. The base duct,
which equalises the air pressure to supply ducts, must be constructed to support the
weight of the heater, which must be sealed using self-adhesive foam strip, ducting tape
or sealing compound. All ducting and blanking plates must be mechanically secured and
sealed.
9.2 ADDITIONAL RADIATOR SYSTEM IF FITTED
9.2.1 Any additional radiators must be connected to pipe tails provided as detailed in Figure 3.
9.2.2 The installation must comply with all relevant national and local regulations.
All components of the system must be suitable for a working pressure of 3 bar and
temperature of 110 °C. Extra care should be taken in making all connections so that the
risk of leakage is minimised.
NOTE: a. The method of filling, refilling, topping up or flushing sealed primary hot water circuits
from the mains via a temporary hose connection is only allowed if acceptable to the local
water authority.
b. Antifreeze fluid, corrosion and scale inhibitor fluids suitable for use with boilers having
stainless steel heat exchangers may be used in the central heating system.
FIGURE 3. WATER FLOW SCHEMATIC
www.johnsonandstarley.co.uk
10
9.3 PIPEWORK SIZING
In order to keep the noise of the system to a minimum, the velocity of water should be kept below
1.5 m/s and it should be noted that the appliance is designed to operate with a temperature
differential of 20 ˚C between flow and return. The maximum flow rates are 0.3 kg/s, which,
through a 22 mm pipe, give velocities of 1.00 m/s. Therefore, the recommended minimum pipe
size is 22 mm.
9.4 WATER TREATMENT
It is important that the system is flushed thoroughly before the appliance is left to operate (as
recommended in BS 7593) in order to maintain an efficiently operating heating system and
in accordance with the Benchmark Guidance Notes on Water Treatment in Central Heating
Systems.
9.4.1 For replacement installations, the system MUST be flushed with the old boiler in situ, in
order to prevent the boiler becoming a trap for system debris. Once the system has
been flushed, an inhibitor (suitable for stainless steel heat exchangers) should be added.
9.4.2 Appropriate inhibitors are available, for example Sentinel, Fernox and Salamader. Failure
to carry out the above procedure will invalidate the guarantee!
NOTE: Water supplied from a water softener MUST NOT be used unless a specially
formulated corrosion inhibitor is added (see BS 6798).
IMPORTANT: This appliance can only be used with a Indirect heating System.
9.5 HOT WATER SYSTEM FOR DHW
9.5.1 A cylinder with a thermostat must be fitted.
9.5.2 Separate timing of DHW is required for connections: see Figure 52.
FIGURE 4. HOT WATER SYSTEM SCHEMATIC
COLD WATER
STORAGE
EXPANSION
VESSEL
HOT WATER
DRAIN COCK
INDIRECT STORAGE
CYLINDER
NOTE: Johnson & Starley Ltd recommends the use of a
sealed system kit. The pressure vessel and PVR must be
fitted in the flow before any auxiliary diverter valves.
11
Sales/Spares & Replacement Help Line 01604 762881
10. FLUE INSTRUCTIONS
10.1 The WarmCair C10DW Condensing Air Heater is certified as a warm air heater with corresponding
flue systems according to EU Directive 2009/142/EC on gas-fired devices. These installation
instructions are covered by this certification and are referred to in the design approval test
certificate.
10.2 The installation of the warm air heater and flue system must be in accordance with the Gas Safety
(Installation and Use) Regulations 1998 and the Building Regulations. If no specific instructions are
given, reference should be made to the relevant codes of practice.
THESE RELEVANT STANDARDS SHOULD BE FOLLOWED
BS 5440:1 Flues and ventilation for gas appliances of rated heating input not
exceeding 70 kW (net) : Flues
BS 5440:2 Flues and ventilation for gas appliances of rated heating input not
exceeding 70 kW (net) : Air Supply
Ensure all legislation, regulations and directives mentioned are observed.
10.3 The air/flue duct operates at very low temperatures therefore no clearance is necessary between
the air duct and the adjacent services.
10.4 Ensure while installation work is being carried out that no debris such as swarf, filings or fragments
of mortar are allowed to remain in the air/flue duct.
10.5 TYPE OF FLUE SYSTEMS
Two types of flue systems are available for the
C10DW.
i) The standard concentric flue system 60/100
(100 mm diameter)
FIGURE 6. 60/100 mm FLEXIBLE FLUE EXAMPLEFIGURE 5. 60/100 mm HORIZONTAL CONCENTRIC FLUE EXAMPLE
VERTICAL TERMINAL
ii) A Flexible flue kit (FFK 5) 60/100 mm (100
mm diameter). For further information
contact the sale office at Johnson &
Starley Ltd. Telephone 01604 762881.
10.6 FLUE TERMINAL POSITIONS
10.6.1 The following information provides the general requirements for siting flue terminals. As
part of the recommendation given in BS 5440 Part 1. For Ireland recommendations,
see the current issue of I.S. 813 “Domestic Gas Installations.” Also publication a “Guide
for Gas Installations in Timber Framed Housing DM2” or consult your local gas region, it
MUST be consulted when installing the appliance into a timber-framed building.
NOTE: Due to the nature of the warm air heater, water vapour will discharge from the flue. This
should be taken into account when siting the flue
10.6.2 Both the horizontal and vertical terminals must be positioned on the outside of the
building and the free passage of air must be available at all times. It is not recommended
to position the terminal close to projections especially under a balcony or near to a
drainpipe.
10.6.3 Ensure that combustion products cannot enter the building where the heater is installed
or near to any other building where doors or windows may be open.
10.6.4 Recommended terminal positions for both horizontal and vertical flues are shown and
flue components and installation options are also detailed.
10.6.5 The flue MUST NOT be installed under a car port.
FLEXIBLE
FLUE
VERTICAL
ADAPTOR
FLUE
SUPPORT
90˚ ELBOW
45˚ ELBOW 1 m EXTENSION
1 m
EXTENSIONS
HORIZONTAL
TERMINAL
WEATHER COLLAR
VERTICAL TERMINAL
www.johnsonandstarley.co.uk
12
FIGURE 7. TERMINAL POSITIONS
P
K
J
I
A
M
M
B
F
G
HH
N
N
C
D, E
Q
TABLE 3 TERMINAL POSITION MINIMUM DISTANCE
A Directly below an opening, air brick, opening window etc. 300 mm
B Above an opening, air brick, opening window, etc. 300 mm
C Horizontally to an opening, air brick, opening window etc. 300 mm
D Below gutters, soil pipes or drain pipes. 75 mm
E Below eaves. 200 mm
F Below balconies. 200 mm
G From a vertical drain pipe or soil pipe. 150 mm
H From an internal or external corner. Greater than 450 mm protrusion. 300 mm
I Above ground, roof or balcony level. 300 mm
J From a surface facing the terminal. 600 mm
K From a terminal facing the terminal. 1,200 mm
M Vertically from a terminal on the same wall. 1,500 mm
N Horizontally from a terminal on the same wall. 300 mm
Q Above intersection with roof. 530 mm
P From a vertical structure on the roof 300 mm
R From the terminal to the boundary 300 mm
13
Sales/Spares & Replacement Help Line 01604 762881
10.8 EXTENDED HORIZONTAL FLUE
CONFIGURATION EXAMPLE
NOTE: Vertical Appliance adaptor is fitted
as part of the air heater.
Can be fitted to the left or the right.
FIGURE 8. EXTENDED FLUE CONFIGURATION
100 mm
19 mm
CORRECT
POSITION OF
HORIZONTAL
TERMINAL END
10.7 FLUE REQUIREMENTS & GENERAL INFORMATION
10.7.1 Horizontal and vertical concentric flues (60/100 mm diameter) with balanced terminals may be
installed on all the WarmCair C10DW appliance.
10.7.2 If an extended horizontal flue is being used it must have a continuous fall back towards the appliance
of 3° (52 mm) per meter. This ensures that condensate runs back into the appliance from the flue
system for safe discharge via the condensate waste pipe. Reference should be made to Table 5 for
relevant part numbers.
10.7.3 The maximum length of flue permissible is 10 meters excluding terminal.
10.7.4 The minimum vertical flue length is 1.25 m from the top of the appliance case to the top of the terminal.
10.7.5 Elbows may be fitted within the flue system with a corresponding reduction in overall flue length.
10.7.6 Guidelines for the maximum flue lengths are as follows.
EQUIVALENT HORIZONTAL FLUE LENGTHS
Adaptor + 10 metres straight
Adaptor + 1 x 90° Elbow + 8 metres straight lengths
Adaptor + 2 x 90° Elbow + 6 metres straight lengths
Adaptor + 3 x 90° Elbow + 4 metres straight lengths
When using 90˚ Elbows = 1 x 90° Elbow is equivalent to 2 m Straight lengths
When using 45˚ Elbows = 2 x 45˚ Elbows are equivalent to 1 x 90˚ Elbow
Flue Extensions
as Required
60/100 mm
Adaptor
Clamps
90° Elbow
ITEM DESCRIPTION QTY
1 Vertical 60/100 mm Adaptor 1
2 Appliance Seal 1
3 EPDM Outside Wall Cover Plate 1
4 Inside Wall Cover Plate 1
5 100 mm Diameter Clamps -
6 Required Extension Flue Length up to
8 m
7 90° Elbow 1
8 800 mm Horizontal Terminal 1
www.johnsonandstarley.co.uk
14
FIGURE 9. VERTICAL FLUE
10.11 PLUME TERMINAL OUTLETS
10.11.1 A flue duct outlet of an appliance should be at least 600 mm from the boundary line when facing
it and at least 300 mm from the boundary line when running parallel to it (See Figure 6).
NOTE: When the flow of products is at an angle to the boundary, the 600 mm dimension may be
measured in the direction of the flow, as long as the terminal is not less than 300 mm from the
boundary.
10.11.2 It is recommended the terminals are not sited within 2 m of an opening in an adjacent building
or within 2 m of the boundary facing the terminal if the plume is likely to cause a nuisance to a
neighbour, e.g. discharging over a walkway or patio.
ITEM DESCRIPTION QTY
1 Vertical 60/100 mm Adaptor 1
2 Vertical Terminal 1
3 1 m Extensions for required length 1
FIGURE 10. PLUME TERMINAL OUTLET DIMENSIONS
10.9 VERTICAL FLUE CONFIGURATION
EXAMPLE
NOTE: Vertical Appliance adaptor is
fitted as part of the air heater. Can be
fitted to the left or the right.
10.10 OPTIONAL ROOF OUTLETS
FLAT ROOF PITCHED ROOF
PITCHED ROOF PITCHED ROOF SIDE VIEW
500 mm
Pitched
Roof
Weather
Collar
500 mm
Flat Roof
Weather
Collar
20˚ to 50˚
Ridge
Terminal
Ridge
Terminal
Clamps
Flue
Extensions
Vertical
Appliance
Adaptor
Adjustable
length
60/100 mm
Adaptor
Clamps
1140 mm
Vertical
Terminal
1 m Extension
15
Sales/Spares & Replacement Help Line 01604 762881
TABLE 5. DESCRIPTION COLOUR QTY APPLICATION PART No.
1
60/100 Standard Horizontal Flue Kit White 1 Horizontal 1000-0020070
2
Turret White 1 Horizontal 1000-0020020
3
800mm Horizontal Terminal White 1 Horizontal 1000-0019830
4
Vertical Appliance Adaptor White 1 Vertical 1000-0024940
5
90° Elbow White 1 Horizontal & Vertical 1000-0018980
7
250mm Straight Extension White 1 Horizontal & Vertical 1000-0018960
8
500mm Straight Extension White 1 Horizontal & Vertical 1000-0018950
9
1000mm Straight Extension White 1 Horizontal & Vertical 1000-0018940
10
2000mm Straight Extension White w Horizontal & Vertical 1000-00025570
11
Flat Roof Weather Collar 1 Vertical 1000-0014900
12
Pitched Roof Collar Black 1 Vertical 1000-0014890
13
Ridge Terminal Grey/
Brown 1 Vertical 1000-0021030
14
Wall Fixing Bracket 100mm 1 Horizontal & Vertical 1000-0014970
15
1140mm Vertical Terminal
White/Black
1 Vertical 1000-0018930
16
Plume Management Kit Black 1 Horizontal & Vertical 1000-0020730
21
Flexible Flue Kit 60/100mm Black 1 Flexible FFK5
33
Chimney Terminal Kit 60/100mm Black 1 Vertical 1000-0026250
34
Skyline Terminal & Outer Flue Cowl Black 1 Vertical 1000-0023990
35
Locking Ring Grey 1 Vertical 1000-0026610
36
Flashing Ring Grey 1 Vertical 1000-0026660
37
Chimney Cover Plate 1 Vertical 1000-0026600
10.12 CONVENTIONAL 60/100 mm FLUE ACCESSORIES PARTS No.s
www.johnsonandstarley.co.uk
16
FIGURE 12. CONDENSATE ROUTING OPTIONS
11. CONDENSATE PUMP & DRAIN TUBE
11.1 CONDENSATE PUMP
11.1.1 Supplied with 6 mm x 10 m condense tube. Condense adaptor and 2 x
clips.
SAFETY NOTE: If the pump fails, the safety float switch will shut off the heater
operation.
11.1.2 DO NOT HANDLE PUMP IN WET CONDITIONS OR WITH WET
HANDS
11.1.3 TECHNICAL DATA
a) Tank capacity : 0.5 L
b) High level safety cut out
c) Outlet size 6 mm I.D.
d) Maximum water temperature: 60 °C
e) Maximum noise level: 21 dB(A) at 1 m
11.1.4 Where the tubing from the pump is connected directly to the soil stack
or waste pipe, there must always be either a waste trap after the tubing
connections, or a 75 mm U trap formed within the tubing.
11.1.5 Where the tubing from the pump is connected to an external soil and
vent stack extra care is necessary to ensure that the condense pipe
could not be blocked through the condense freezing.
11.1.6 The tank pump uses small bore (6 mm) flexible hose which can be
routed above or below doors, windows and under kitchen cabinets.
IMPORTANT: Ensure the condensate tube is protected and
cannot freeze in an unheated area.
11.2 CONDENSE TUBE ROUTING OPTIONS
Option A. Routing to outside drain via sink
Option B. Routing to drain pipe via roof
Option C. Routing to bath waste
Option D. Routing to under floor
to sink waste
B
C
D
A
NOTE:
10 m MAXIMUM
HEAD LENGTH OF
CONDENSE TUBE
RESERVOIR
FLOAT FILTER
FIGURE 11. CONDENSE PUMP
17
Sales/Spares & Replacement Help Line 01604 762881
12. ELECTRICAL
12.1 The appliance is supplied with PVC sheathed, 3 core (Brown-Blue-Green/Yellow) 0.75 mm2 CSA
rated at 6 A, connected to a terminal block and exiting through the casing at the top left hand
front. The cable is suitable for a 230 V - 50 Hz single phase supply.
12.2 The means of isolating the appliance MUST be via a double pole switch with a contact separation
of at least 3 mm in both poles, and fused at 3 A. If switched live is fitted, a triple pole switch should
be used.
12.3 An OpenTherm Controller is supplied with the unit, which is to be connected using PVC sheathed
to BS 6500, 2 core cable of 0.5 mm2 CSA rated at 3 A, to terminals 29 & 30 on the PCB in
accordance with Figure 52 and observing correct polarity.
13. WARM AIR FAN PERFORMANCE
14. OPERATING MODES
14.1 Operating modes are covered in the User Instructions, ZZ1449 packed with the appliance, for
both Domestic Hot Water and Central Heating.
14.2 For heating systems that include additional heating circuits e.g. radiators, circuit instructions for
use and installation will be provided within additional control packages provided.
14.3 For installations that include a solar water circuit to the domestic hot water cylinder, instructions
for use and installation will be provided within the solar heating kit.
FIGURE 13. FAN PERFORMANCE GRAPH
www.johnsonandstarley.co.uk
18
15. DOMESTIC HOT WATER HEATING COMMISSIONING
15.1 CHECK GAS INSTALLATION
15.1.1 The whole of the gas installation, including the meter, should be inspected and tested for
tightness and purged in accordance with the recommendations of BS 6891. In Ireland
refer to IS 813.
15.1.2 Purge air from the gas installation by the approved methods only.
NOTE: The combustion for this appliance has been checked, adjusted and preset
at the factory for operation on the gas type defined on the appliance data plate. No
measurement of the combustion is necessary. Do not adjust the air/gas ratio valve.
15.1.3 Having checked the heater has been installed in accordance with these instructions. The
integrity of the flue system and the flue seals, as described in the Flue Installation section.
Proceed to put the boiler into operation as follows:
15.2 CHECK THE OPERATIONAL GAS INLET PRESSURE
15.2.1 Set up the heater to operate at maximum rate by opening hot tap to
maximum flow.
15.2.2 With the heat generator operating in the maximum rate condition,
check the operational gas
pressure at the inlet gas pressure test
point complies with the requirements. See Figure 13.
15.2.3 Ensure that this inlet pressure can be obtained with all other gas
appliances in the property working.
15.3 AIR PURGE FUNCTION
15.3.1 On initial power up an air purge cycle is initiated.
15.3.2 Ensure air bleed valve is open.
15.3.3 Ensure air bleed valve is open on initial power up and air purge cycle
is indicated.
15.3.4 During this function, heat demand is switched off and combustion
fan will run at maximum for 120 seconds.
15.3.5 Also at the same time, the circulation pump will be switched on for 5
seconds and off for 5 seconds continuously.
15.3.6 Diverting 3 WV (three way valve) will be moved in CH position for the first 30
seconds, then in DHW position for 30 seconds, then in CH position for 30
seconds and finally in DHW position for 30 seconds.
15.3.7 In this way, air is expelled from the circuit. On completion of this function
normal operation of the circulation pump will occur.
15.3.8 During the fan on period, there will be an indication on the LCD display:
15.3.9 Function can be skipped pressing K4 push button twice.
This function can be activated by four conditions:
a. If the controller is plugged in to the Mains for the first time.
b. After a manual reset to reset the lockout fault E03: High limit temperature protection.
c. When the central heating water pressure is built up to the normal level after the fault
F37 or fault F40.
15.3.10 If there is no heat demand afterwards, the controller will switch to standby mode.
FIGURE 15.
AIR PURGE LED
READ OUT
FIGURE 16. LED DISPLAY FUNCTIONS
K7 K1
K6 K2
K3 K5
K4
ITEM DESCRIPTION
K1 + Installer function only
K2 - Installer function only
K3 Installer information
K4 Reset
K5 Summer/Winter mode
K6 No Function
K7 No Function
15.5 RESET PROCEDURE - To reset boiler press the reset button “K4” twice.
FIGURE 14.
GAS PRESSURE TEST POINT
19
Sales/Spares & Replacement Help Line 01604 762881
16. INITIAL LIGHTING
16.1.1 Check that the system has been filled and the heat exchangers are not air-locked.
NOTE: It is important the burner is not operated before the system is fully vented of air.
IMPORTANT: The gas input to the burner is regulated by the gas valve according
to the air flow produced by the fan. It is not user-adjustable. Any interference to
sealed settings on the gas valve will adversely affect operation and render our
warranty void.
16.1.2 Refit the boiler front panel. See Paragraph 17.5.
16.1.3 Check that the electrical supply is OFF.
16.1.4 Check that the gas service cock is OPEN.
16.1.5 Slacken the screw in the inlet pressure test point and connect a gas pressure gauge via
a flexible tube.
16.1.6 Switch the electricity supply ON and check all external controls are OFF. The heat
generator will select “self purge”.
16.2 WARM AIR CENTRAL HEATING
16.2.1 Set the CH temperature to maximum and switch on external control. The heat generator
control should now go through its ignition sequence until the burner is established.
16.2.2 If the heat generator does not light, code E-01 will be displayed.
16.2.3 Reset the heat generator (see Paragraph 15.5). The heat generator will repeat its ignition
sequence. If reset occurs 5 times within 15 minutes, F-15 will be shown. If power is
removed, this will be reset.
16.2.4 When the burner is established the display will show the “flame symbol”.
16.2.5 Ensure that the CH external controls are calling for heat. The burner should
light.
16.2.6 Gas Rate: Check the heat generator gas rate when the heat generator is
at full CH output.
Check at the gas meter, with no other appliance in use. Refer to Table 2 for
gas rates.
16.2.7 Set the central heating external controls to OFF. The burner should go off and the pump
continue to run for two minutes.
16.2.8 Check the correct operation of the timer (if fitted) and all other system controls. Operate
each control separately and check that the main burner responds.
16.3 WATER CIRCULATION SYSTEM
16.3.1 With the system still hot, turn off the gas, water and electricity supplies to the boiler and
drain down to complete the flushing process.
NOTE: A flushing solution should be used during the flushing procedure. Flushing solutions:
Fernox Superfloc, Sentinel X300 (new systems) or X400 (existing systems). Refer to
Paragraph 8.8.
16.3.2 Refill and vent the system, add inhibitor, clear all air locks and again check for water
tightness.
16.3.3 Reset the system initial pressure to the design requirement.
16.4 BALANCE THE SYSTEM (if radiator system is fitted)
16.4.1 The heat generator does not normally need a bypass but at least some radiators on the
heating circuit, of load of at least 10% of the minimum heat generator output, must be
provided with twin lockshield valves so that this minimum heating load is always available.
See note regarding thermostatic radiator valves.
NOTE: Systems incorporating zone valves which could completely cut off the flow through the
system must also include a bypass.
16.4.2 Check the condensate drain for leaks and check that it is discharging correctly.
16.4.3 Finally, set the controls to the User’s requirements.
NOTE: The circulation pump will operate briefly as a self-check once every 24 hours in the
absence of any system demand.
16.5 CENTRAL HEATING WATER TEMPERATURES
Temperatures can be selected using the CH
thermostat See Table 5.
16.5.1 Set water differential to 20 °C using
lockshield valve or equivalent.
16.5.2 Check fan stops when water cools to
minimum temperature.
TABLE 5.
Button Setting CH Flow Temperature °C
Max 80
Min
45
FIGURE 17.
LED READ OUT
www.johnsonandstarley.co.uk
20
17. WARM AIR HEATING COMMISSIONING
17.1 Ensure the heater is correctly filled with water and all air vented from the flow and return circuits.
17.2 Switch on electrical supply.
17.3 Setting maximum speed.
a. Remove the PCB cover plate.
b. Make a short across summer vent connections on the PCB interface and adjust the fan
speed as required using a small screwdriver on the warm air PCB to turn the relevant pot.
Remove the short.
17.4 Setting minimum fan speed.
a. Make a short across the pipe sensor or minimum fan adjustment of PCB interface and
adjusted the fan speed as required, using a small screwdriver on the warm air PCB to
turn the relevant pot. Remove short.
17.5 WITH OPENTHERM CONTROLLER FITTED
17.5.1 Turn up OpenTherm Controller to call for heat.
17.5.2 With the water at the required temperature, ensure fan starts (when the display shows
62 °C to 68 °C).
17.5.3 Allow the system to warm up and check temperature rise across unit is 40 °C.
17.5.4 Set water differential to 20 °C using lockshield valve or equivalent.
17.5.5 Turn off OpenTherm Controller and check there is NO 230 V on switch live out.
17.5.6 Check fan stops when water cools to minimum temperature.
17.6 WITH NO OPENTHERM CONTROLLER FITTED
17.6.1 With the water at the required temperature, ensure fan starts (the display shows 62 °C
to 68 °C).
12.6.2 Allow the system to warm up and check temperature rise across unit is 40 °C.
18. HANDING OVER
18.1 Hand the User Instructions to the householder and explain his/her responsibilities under the
relevant national regulations.
18.2. Explain and demonstrate the lighting and shutting down procedures.
18.3 The operation of the heater and the use and adjustment of all system controls should be fully
explained to the householder, to ensure the greatest possible fuel economy consistent with the
household requirements of both heating and hot water consumption. Advise the User of the
precautions necessary to prevent damage to the system and to the building, in the event of the
system remaining inoperative during frosty conditions.
18.4 Explain the function and the use of the boiler heating.
18.5 Explain the function of the heater Fault Mode. Emphasise that if a fault is indicated refer to “Fault
Codes” in the User Guide.
18.6 Explain and demonstrate the function of time and temperature controls, radiator valves etc., for
the economic use of the system.
18.7 If a timer is fitted, draw attention to the Users.
18.8 Explain heater reset procedure.
18.9 After installation and commissioning, please complete the Commissioning Checklist before
handover to the customer. For Ireland, its is necessary to complete a “Declaration of Conformity”
to indicate compliance to IS 813.
IMPORTANT:
18.10 A comprehensive service should be carried out ANNUALLY. Stress the importance of regular
servicing by a Gas Safe Registered Engineer. In Ireland, servicing work must be carried out by a
Registered Gas Installer (RGII).
18.11 Inform the householder of the guarantee/registration found within the folder pack and the
requirement to register it to receive the full benefit of the
warranty.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Johnson & Starley WARMCAIR C10DW Installation guide

Category
Water heaters & boilers
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI