LT-6709MP Rev 0 October 2021 Page 1 of 1
FleX-Netâ„¢ FX-4000 Quick Start
Factory Default Jumper Settings
To ensure the correct operation of the Fire Alarm Control Panel, check that the jumpers on the main board are
set correctly.
For more details, see LT-894MP the FleX-Netâ„¢ FX-4000 Installation Manual.
Jumper Factory Default Notes
JW1 Closed Open this jumper if a PR-300 or UDACT-300 is installed
JW2 Open Do not change
JW3 Closed on pins 1 and 2
(2 leftmost pins) Do not change
JW4 Closed Do not change
JW5 Open Close this jumper to silence the on-board buzzer
P12 Closed on pins 1 and 2
(2 rightmost pins) Do not change
Terminal Factory Default Notes
TS2
There is a wire connecting
positions E+ and I+
(the 2 top pins)
Do not remove
MAIN FIRE ALARM BOARD
JW1: Closed (open if a PR-300 or UDACT-300A is installed)
JW4 (Closed)
JW5: Open
JW3 (Closed on 2 leftmost pins)
JW2 (Open)
P12 (Closed on
2 rightmost pins)
TS2: There is a wire
connecting 2 top pins