Danfoss Controller type AKC 114A, 115A, and 116A for controlling evaporators. Verx. 1.5x. AKA 21 Installation guide

Category
Thermostats
Type
Installation guide
RC.1M.B2.02 RC.1M.B3.02 11-1998
Menu operation via AKA 21
Software version 1.5x
Controller for controlling evaporators
AKC 114A, 115A and 116A
ADAP-KOOL
®
2 Menu operation RC.1M.B3.02 © Danfoss 11/1998 AKC 114A-116A Version 1.5x
System survey
A refrigerating plant fitted with ADAP-KOOL
®
refrigeration controls will mostly consist
of several controllers where each controller will regulate its own refrigeration
appliance/cold room.
The system has been designed in such a way that contact can be made to each and
every controller via a data communication system. One specific controller is selected,
and it will now be possible to make settings and readouts for this unit.
The individual controllers can be operated in two
ways:
1. With control panel type AKA 21.
Use this document when operation takes place in
this way.
2. With PC and system software type AKM. Use
another document with literature number
RC.1M.C
Operation
Validity
This menu operation was worked out in November 1998 and applies to AKC 114A,
AKC 115A and AKC 116A with the following code numbers:
084B6171 and 084B6172 (AKC 114A)
084B6173 and 084B6174 (AKC 115A)
084B6175 and 084B6176 (AKC 116A)
that are fitted with software version 1.5x.
AKC 114A-116A Version 1.5x Menu operation RC.1M.B3.02 © Danfoss 11/1998 3
All controllers that are connected to the same network can be operated with the
control panel. There may be as many as 125 controllers, and they are shown in
groups of 16 on the display.
A system is shown here which consists of more than 16 controllers. The meaning of
the letters is, as follows:
A: AKC controller
E: Controller with active ERROR (on addresses 2, 11 and 12 in this example)
g: Gateway (to addresses 13 and 14 in this example)
G: Gateway with connected printer
: A blank field indicates that there is no unit with this address.
Select the unit that is to be operated by using the “+/On” or “-/Off” key, and push
“Enter”. In this example you select the controller with address 4.
If the system comprises more than 16 units or units with an address code higher than
16, you may change to the next group by pushing “”.
When a controller has been selected, you can make settings in it. This setting is
performed, as follows:
Shown in the upper right corner of the display is the setting with which the controller is
operating. Below that value a new setting may be made. Use the three keys “+/ON”,
“-/OFF” and “Digit” for setting the new value. This new value will not govern the
regulation until you push the key “Enter”.
Select a controller
Settings of a controller
5
-50 to +50 5
ON
OFF / ON ON
The functions in the controller can be protected by means of an access code.
Depending on the settings to be made, you may gain access in one of the following
ways:
User input: Gives access to:
1. Push F1 Display of alarms
2. Push F2 Reading of selected temperatures, change of
temperature in the refrigeration appliance, start of
defrost
3. Code 1 and then F1 Acknowledgement of alarms
Code 1 and then F3 Setting of selected parameters
4. Code 2 Operation of all settings of the entire menu system
(with system software type AKM there is access to
additional functions).
Pages 6 and 7 contain a description of how you gain access to the system via a code.
Access to a controller
1 < 1 > 16
AEAAAAAAAAEEgg A
1 < 4 > 16
AEAAAAAAAAEEgg A
17 < 17 > 32
AAA
4 Menu operation RC.1M.B3.02 © Danfoss 11/1998 AKC 114A-116A Version 1.5x
A supporting text is attached to the individual functions. When such a function is
shown in the control panel’s display, the supporting text can be obtained by pushing
the key “Help”. The supporting text is intended as a help to users who no longer use
these operating instructions.
In the menus shown below functions with supporting texts are identified with the word
“Help” next to the function.
When an error appears in a system, it can be seen on the control panel’s display
which will show an “E”. If the control panel shows a text from a selected controller, the
LED at the word “Alarm” will furthermore flash.
When an error has occurred, first select the controller on which the error is registered.
When the controller has been found, push “F1”, and the error message will appear.
At the end of the document there is a list of all the error messages and a description
of how to acknowledge an alarm.
Supporting text
How to localise an error
When one controller has been selected from the total system, the following display will
appear (the display is the first one shown when you have selected an address from
the total system):
e.g.
AKC 116A Adr: 2
E Mon-11:27
From this position you can freely choose between several forms of operating levels:
1. Display of alarms - push “F1”
2. Display and setting of a few selected functions - push “F2”
3. Display and setting of several selected functions - push “F3”
The function may be protected with a code (code 1)
4. Display and setting of all allowed functions in the controller. The function may be
protected with a code (code 2).
Operation of the individual levels is shown below:
When you push “F1” the alarm messages from the controller in question appear. Only
active alarms are shown. With a push on “” you can see whether there are more alarm
messages, and if so, their texts.
When an alarm has been localised and corrected, the alarm is acknowledged
(removed from the system, so that it no longer appears). In large systems where a
gateway is also connected this acknowledgement will take place automatically. In
other systems it has to be done manually, cf. end of the document.
Prior to the acknowledgement of the alarm, the keying of a code is required, see page
6.
Leave the F1 function by pushing “”.
Functions of a
controller
1 < 2 > 16
AEAAAAAAAAAAgg A
AKC 116A Adr: 2
E Mon-11:27
Standby Mode
1. F1
AKC 114A-116A Version 1.5x Menu operation RC.1M.B3.02 © Danfoss 11/1998 5
When you push “F2” a number of functions will appear where it is possible to read or set
values.
You can move to and from the individual functions by pushing “” or “”. On page 3 you
can see how a setting is changed.
Man.Def. Manual defrost is activated when ON
OFF/ON (Changes automatically to OFF)
7:03:02
|
CutOut A °C Setting of thermostat cut-out value
-50 - 50 MUST BE SET. Even if the thermostat function has not been
3:05:02 selected. (The value is used by the injection function).
|
CutOut B °C Only AKC 115A/ Setting of thermostat cut-out value
-50 - 50 AKC 116A MUST BE SET. Even if the thermostat function has not been
4:05:02 selected. (The value is used by the injection function)
|
CutOut C °C Only AKC 116A Setting of thermostat cut-out value
-50 - 50 MUST BE SET. Even if the thermostat function has not been
5:05:02 selected. (The value is used by the injection function)
|
Ther.Air A Actual air temperature (section A)
3:04:01
|
Ther.Air B Only AKC 115A/ Actual air temperature (section B)
4:04:01 AKC 116A
|
Ther.Air C Only AKC 116A Actual air temperature (section C)
5:04:01
|
RunTime A Actual thermostat cut-in time of section A
3:04:08 or duration of the latest finished cut-in
|
RunTime B Only AKC 115A/ Actual thermostat cut-in time of section B
4:04:08 AKC 116A or duration of the latest finished cut-in
|
RunTime C Only AKC 116A Actual thermostat cut-in time of section C
5:04:08 or duration of the latest finished cut-in
|
Reg Cond. A Help Regulating condition
3:02:01 0: No cooling 5: Start after defrost
| 1: Start up 6: Forced closing
Reg Cond. B Help 2: Adaptive control
4:02:01 Only AKC 115A/ 8: Sensor errror
AKC 116A 4: Defrosting 9: Modulating temperature control
| 10: Forced cutout (Melt function)
Reg Cond. C Help
5:02:01 Only AKC 116A
Leave the F2 function by pushing “”.
2. F2
6 Menu operation RC.1M.B3.02 © Danfoss 11/1998 AKC 114A-116A Version 1.5x
When you push “F3”, a number of functions will appear which are used when the system
is serviced.
• If access code is used (code 1), key it as follows:
- Push the “key”
- Enter the code by using the three keys “+”, “-” and “Digit” (the code is mentioned
later as code 1, and the factory setting is 40. If code 2 has been set at 0,
access code 1 cannot be used).
- Push “Enter”
- Push “F3”
Move to and from the individual functions by pushing “” or “”.
On page 3 you can see how a setting is changed.
Main Switch Main switch: 1: Regulation
-1 / 0 / 1 0: Controller stop
2:02:01 -1: Service
|
Def.Stop °C Temperature value of defrost stop
0 - 60
7:04:03
|
MaxDefTime Max. permissible defrost time in minutes
5 - 180 (Security time on Temperature stop)
7:04:02
|
T0 °C Evaporating temperature
3:02:05
|
Superheat A Superheat section A
3:02:02
|
Superheat B Superheat section B
4:02:02
|
Superheat C Superheat section C
5:02:02
|
AKV OD % A Actual valve opening degree
3:02:04
|
AKV OD % B Actual valve opening degree
4:02:04
|
AKV OD % C Actual valve opening degree
5:02:04
Leave the function by pushing “”.
3. F3
AKC 114A-116A Version 1.5x Menu operation RC.1M.B3.02 © Danfoss 11/1998 7
4. Access to all
functions
The access to the functions may be protected with a code (code 2).
• If access code is used, key it as follows:
- Push the “key”
- Enter the code by using the three keys “+”, “-” and “Digit”
- Push “Enter”
- Push “
Move to and from the individual functions by pushing the four arrow keys.
On page 3 you can see how a setting is changed.
When you wish to leave the “Access to all functions” function, push “Clear” and then
”.
List of functions on level 1:
1. Controllers access display and access to system information
2. Interruption of regulation and selection of language
3. Controller A
4. Controller B (AKC 115A/116A only)
5. Controller C (AKC 116A only)
6. Common functions; Thermostat function, day/night Ctrl. settings, fan control, rail
heat control, display control, DI Alarm, Output control at forced closing, safety
function, Ext. injection, Ext. Temp. reference
7. Defrost control
8. Forced control functions for service and initial setting
Below and on the following pages the individual functions are shown together with a
brief description:
Level 1 Level 2 Level 3 Level 4 Description
AKC 11xA Adr: xxx Controller access display
Mon hh:mm If the code function is used, continue by pushing the "key" key.
Enter Code Entry of access code 1 or access code 2 (cf. also 1:07 and 1:08).
0 - 255 0 Continue by pushing "arrow left"
1:01
AKC 11xA Adr: xxx Access to system information
Mon hh:mm If an E appears in the display, an error has been re
g
istered.
1
Code No. Readin
g
of the controller’s code no. and pro
g
ramme version.
Prog. Ver.
1:02
|
Clock: Settin
g
of controller clock (AKC clock)
Mon hh:mm
1:03
Clock: Day. Settin
g
of day (1 = Monday, 7 = Sunday)
Mon(1) Sun(7)
1:03:01
|
Clock: Hour Settin
g
of hours
0 - 23
1:03:02
|
Clock: Min. Settin
g
of minutes
0 - 59
1:03:03
|
System Address Readin
g
of the controller’s system address
Addr. yyy xxx yyy=network no. and xxx=address.
1:04 The system address can only be set via PC
|
Alarm report to Readin
g
of the alarm address (end receiver) the alarms are to be
Addr. yyy xxx sent to.
1:05 The alarm address can only be set via PC.
8 Menu operation RC.1M.B3.02 © Danfoss 11/1998 AKC 114A-116A Version 1.5x
|
Gateway Address Reading of the address on the nearst gateway which has to
xxx effect alarms (see 1:05)
1:06 The address can only be set via PC
|
Ch
g
. Code1 Chan
e of code 1. The code
ives access to acknowled
ement
0 - 255 of active alarm by means of the F1 key.
1:07 Also access to the selected settin
g
s/readouts via the F3 key.
| (Factory settin
g
= 40) (See also code 2)
Ch
g
. Code2 Chan
g
e of code 2. The code
g
ives access to the whole menu
0 - 255 system.
1:08 (Factory settin
g
= 0. Settin
g
= 0 offers free access where
neither code 1 not code 2 is required)
|
Main Function Main function
2
Alarm Messa
g
e(s) In case of alarm, an E is shown on the display
2:01 (Error lo
g
becomes visible)
See pa
g
e 19, check of error lo
g
2:01:01
|
Main Function Access to the main switch
Settin
g
s
2:02
Main Switch Main switch: 1: Re
g
ulation
-1 / 0 / 1 Help 0: Controller stop
2:02:01 -1: Service
|
Lan
g
ua
g
e Selection of lan
g
ua
g
e. Three lan
g
ua
g
es have been entered
0 - 4 Help in the controller
2:02:02 Either: Or:
0: En
g
lish 0: En
g
lish
1: German 3: Danish
2: French 4: Spanish
NB! This function must be set prior to any uploadin
g
to system
software type AKM.
When the lan
g
ua
g
e code has been chan
g
ed, push "ENTER"
and then "Clear".
|
Rf
g
. Type R Readin
g
of set refri
g
erant type
2:02:03
|
Rf
g
. Type Refri
g
erant selection: 0: No refri
g
erant selection. 12: R142b
0 - 23 Help 1: R12 13: User defin
e
2:02:04 2: R22 14: R32
3: R134a 15: R227
4: R502 16: R401A
5: R717 (ammonia) 17: R507
6: R13 18: R402A
7: R13b1 19: R404A
8: R23 20: R407C
9: R500 21: R407A
10: R503 22: R407B
11: R114 23: R410A
|
Controller A Section A
3 In case of alarm, an E is shown on the display
Alarm messa
g
e(s) (Error lo
g
becomes visible)
3:01
See pa
g
e 19, check of error lo
g
3:01:01
AKC 114A-116A Version 1.5x Menu operation RC.1M.B3.02 © Danfoss 11/1998 9
|
In
j
ection A Read-out of measurin
g
values related to section A
Measurements
3:02
Re
g
Cond. A Re
g
ulatin
g
condition
3:02:01 Help 0: No coolin
g
5: Start after defrost
1: Start up 6: Forced closin
g
2: Adaptive control
8: Sensor errror
4: Defrostin
g
9: Modulatin
g
temperature control
10: Forced cutout
(
Melt function
)
|
Superheat A Superheat section A
3:02:02
|
SH Ref K A Actual superheat reference of the re
g
ulation
3:02:03
|
AKV OD % A Actual valve openin
g
de
g
ree
3:02:04
|
T0 °C Evaporating temperature
3:02:05
|
S2 A °C Gas temperature at evaporator outlet.
3:02:06
|
In
j
ection A Settin
g
of expansion valve function section A
Settin
g
s
3:03
In
j
. Ctrl. A Choose expansion valve function ON/OFF
OFF / ON
3:03:01
|
Thermostat Read.out of measurin
g
values related to thermostat function.
Measurements
3:04
Ther.Air A Actual air temperature
(
section A
)
3:04:01
|
AlarmAir A Actual air temperature for the alarm function in section A
3:04:02
|
S3 A °C Air temperature at evaporator inlet
(
section A
)
(
air on
)
3:04:03
|
S4 A °C Air temperature at evaporator outlet
(
section A
)
(
air off
)
3:04:04
|
CutOut A °C Actual thermostat
(
s
)
cut-out value
3:04:05
|
CutIn A °C Actual thermostat
(
s
)
cut-in value
3:04:06
|
Night Cond Status of day-/night operation (ON/OFF)
3:04:07
|
RunTime A Actual thermostat cut-in time of section A
3:04:08 or duration of the latest finished cut-in
|
Thermostat Settin
g
s for thermostat function
Settin
g
s
3:05
Ther. Sx A Definition of thermostat sensor(s)
1 - 3 Help 1: S3 in use
3:05:01 2: S4 in use
3: S3, S4 in use. CPT
(
calculated product temperature
)
|
CutOut A °C Settin
g
of thermostat cut-out value
-50 - 50 MUST BE SET. Even if the thermostat function has not been
3:05:02 selected.
(
The value is used b
y
the in
j
ection function
)
.
|
Diff. A K Setting of thermostat differential
0.5 - 10
3:05:03
10 Menu operation RC.1M.B3.02 © Danfoss 11/1998 AKC 114A-116A Version 1.5x
|
S4A Day % S4 wei
g
htin
g
by day
0 - 100 S3 is automatically wei
g
hted. Must only be set if "Ther.Sx" = 3
3:05:04
|
S4A Ni
g
ht % S4 is wei
g
htin
g
at ni
g
ht
0 - 100 S3 is automatically wei
g
hted
3:05:05
|
S4MinLim A Settin
g
of low S4 temperature alarm limit
-50 - 50 The function is only active, if wei
g
htin
g
between S3 and S4
3:05:06 Help is used for the thermostat function
|
Air Temp. Alarm Settin
g
s for alarm function
Settin
g
s
3:06
Alarm ModeA Definition of alarm thermostat
0 - 3 Help 0: No alarm thermostat
3:06:01 1: S3 used as alarm sensor
2: S4 used as alarm sensor
3: TherAir used as alarm sensor
|
Hi
g
h LimA °C Hi
g
h air temperature alarm limit (absolute value).
-50 - 50 When there is ni
g
ht setback operation, the alarm limit is raised
3:06:02 by the ni
g
ht setback value.
|
Hi
g
h1Del A Time delay of hi
g
h air temperature alarm durin
g
pull-down.
0 - 240 Help This value will apply until the actual air temperature has dropped
3:06:03 below the "upper alarm limit".
Thereafter shift to the time delay "Hi
g
h2Del m".
|
Hi
g
h2Del A Time delay of hi
g
h air temperature alarm durin
g
normal re
g
ulation.
0 - 60 Help
3:06:04
|
Low LimA °C Low air temperature alarm limit (absolute value)
-50 - 50
3:06:05
|
Low Del A Time delay for low air temperature alarm
0 - 60
3:06:06
|
Controller B Only AKC 115A/116A Section B (only AKC 115A and AKC 116A)
Description for "Controller B" is the same as for "Controller A" (3)
4
|
Controller C Only AKC 116A Section C (only AKC 116A)
Description for "Controller C" is the same as for "Controller A" (3)
5
|
Common Functions common to sections A, B and C
Controller
6
Alarm messa
g
e(s) In case of alarm, an E is shown on the display
6:01 (Error lo
g
becomes visible)
See pa
g
e 19, check of error lo
g
6:01:01
|
Thermostat
Mode
6:02
Ther. Mode Definition of thermostat function
0 - 3 Help 0: No thermostat function
6:02:01 1: The thermostat function is atached to section A
(cutout and cutin of sections B and C will come after section A)
2: There is one thermostat function in each function
3: Modulatin
g
temperature re
g
ulation (there is one
thermostat in each section.)
AKC 114A-116A Version 1.5x Menu operation RC.1M.B3.02 © Danfoss 11/1998 11
|
Day/Ni
g
ht Ctrl. Settin
g
s of day/ni
g
ht function
Settin
g
s
6:03
Day/Ni
g
ht Choose day-/ni
g
ht operation function
0 3 Help 0: No ni
g
ht setback
6:03:01 1: Chan
g
e between day and ni
g
ht operation accordin
g
to
si
g
nal on S6 input
2: Chan
g
e between day and ni
g
ht operation accordin
g
to
internal time clock
3: Chan
g
e between day and ni
g
ht operation accordin
g
to the
si
g
nal from the master controller (Si
g
nal via DANBUSS)
|
Dt Ni
g
ht K Ni
g
ht set back value
-25 - 25
6:03:02
Mo Day h Time table for day and ni
g
ht operation on Mondays
0 24 End of ni
g
ht setback
6:03:03 At settin
g
= 0 there is no ni
g
ht setback this day
|
Mo Ni
g
ht h Time table continued:
0 24 Start (of ni
g
ht setback)
6:03:04 At settin
g
= 0 there is no displacement this day
If day and night settings are identical, or if night is set before
the function will be chan
g
ed. See functional description
|
Tu day h As above, Tuesdays
0 24
6:03:05
|
Tu ni
g
ht h As above, Tuesdays
0 24
6:03:06
|
We day h As above, Wednesdays
0 24
6:03:07
|
We ni
g
ht h As above, Wednesdays
0 24
6:03:08
|
Th day h As above, Thursdays
0 24
6:03:09
|
Th ni
g
ht h As above, Thursdays
0 24
6:03:10
|
Fr day h As above, Fridays
0 24
6:03:11
|
Fr ni
g
ht h As above, Fridays
0 24
6:03:12
|
Sa day h As above, Saturdays
0 24
6:03:13
|
Sa ni
g
ht h As above, Saturdays
0 24
6:03:14
|
Su day h As above, Sundays
0 24
6:03:15
|
Su ni
g
ht h As above, Sundays
0 24
6:03:16
12 Menu operation RC.1M.B3.02 © Danfoss 11/1998 AKC 114A-116A Version 1.5x
|
Fan Pulsin
g
Settin
g
of fan pulsin
g
durin
g
ni
g
ht operation
(CutOut Ni
g
ht)
6:04
Fan On % Settin
g
of the fans ON period in percent of the "FanCycl m" time
0 - 100 (the function is only active in the cutout period durin
g
ni
g
ht
6:04:01 operation).
|
FanCycl m Period time for total ON / OFF time
0.0 - 60.0
6:04:02
|
Railheat Pulsin
g
Settin
g
s for railheat function
(Day/Ni
g
ht)
6.05
RailOnDay % Durin
g
day operation: Settin
g
of rail heat ON period in percent
0 - 100 of the "RailCycl m" time.
6:05:01
|
RailOnN
g
t % Durin
g
ni
g
ht operation: Settin
g
of rail heat ON period in percent
0 - 100 of the "RailCycl m" time
6:05:02
|
RailCycl m Period time for total ON / OFF time
6 - 60
6:05:03
|
Display Ctrl. Settin
g
s for external temperature display type AKA 14
Settin
g
s
6:06
Disp. Ctrl. Choose read-out for display
0 - 3 Help 0: No display function
6:06:01 1: S3 read out
2: S4 read out
3: Ther.Air read out
|
Offset K A Offset adjustment of display si
g
nal, display A
-10.0 10.0
6:06:02
|
Offset K B Offset adjustment of display si
g
nal, display B
-10.0 10.0
6:06:03
|
Offset K C Offset adjustment of display si
g
nal, display C
-10.0 10.0
6:06:04
|
DI Alarm Settin
g
s for DI alarm function
6:07
DI Alarm Choose alarm function ON / OFF
OFF / ON
6:07:01
|
DI Text Select the alarm text
0 - 4 Help 0: DI alarm
6:07:02 1: Door alarm
2: Safety cutout
3: Fan failure
4: Leak alarm
|
DI Delay m Time delay from the alarm is re
g
istered until executed
0 - 180
6:07:03
AKC 114A-116A Version 1.5x Menu operation RC.1M.B3.02 © Danfoss 11/1998 13
|
Output Ctrl. at Definition of controller outputs at forced control si
g
nal
Forced Closin
g
(when the "ON" inlet is cut-out (terminal 32 - 33))
6:08
Output Ctrl. Output functions when there is forced control
1 - 3 Help 1: Fan outlet is ON
6:08:01 2: Fan outlet is OFF
3: All outlets are OFF and alarm thermostat function is stopped.
|
ON-InpMode Definition of AKC-ON input (terminals 32-33)
0 - 1 0: Connection not used, as the re
g
ulation is controlled by the
6:08:02
g
ateways override function
1: Connection must be made (when the volta
g
e is interrupted, the
valve closes)
|
Safety Function Settin
g
s for fan stop function
Fan Stop by S5
6:09
FanStopS5 Choose Fan stop function ON / OFF
OFF/ON Help
6:09:01
|
FanStop °C Temperature limit for fan stop (the fans are stopped when the
-50 - 50 S5A temperature is hi
g
her than this value. The fans will start
6:09:02 a
g
ain when S5A is lower than "FanStop °C" - 2K)
|
Extended Inject. Extended settin
g
s for injection function
Ctrl. Settin
g
s
6:10
SH Max K Max. superheat reference value
3.0 - 15.0
6:10:01
|
SH Min K Min. superheat reference value
3.0 - 10.0
6:10:02
|
MOP Ctrl. Choose MOP function ON/OFF
OFF/ON
6:10:03
|
MOP °C MOP point value
-50 - 15
6:10:04
|
Ext. Temperature Settin
g
s for Extern AL temperature reference
Reference
6:11
ExtRef Si
g
Definition for extern AL reference si
g
nal
1 - 2 1: 0 - 10 V si
g
nal
6:11:01 2: 2 - 10 V si
g
nal
|
ExtRefTemp Displacement to be produced by max. reference si
g
nal (10 V)
-50 - 50 (With settin
g
= 0 the function is OFF)
6:11:02
|
ExtRef K Display of reference (input si
g
nal + displacement)
6:11:03
|
Al MaxLim % Upper alarm limit. Set in percenta
g
e of input si
g
nal
0 - 100
6:11:04
|
Al MinLim % Lower alarm limit. Set in percenta
g
e of input si
g
nal
0 - 100
6:11:05
|
AI Delay m Time delay for alarm
0 - 180
6:11:06
|
Al Input % Input si
g
nal value in per cent.
6:11:07
14 Menu operation RC.1M.B3.02 © Danfoss 11/1998 AKC 114A-116A Version 1.5x
|
Defrost Control Defrost function
7:00
Alarm messa
g
e(s) In case of alarm, an E is shown on the display
7:01 (Error lo
g
becomes visible)
See pa
g
e 19, check of error lo
g
7:01:01
|
Defrost Read-out of measurin
g
values related to defrost function
Measurements
7:02
Def. Cond. Defrost condition
7:02:01 Help 0: No defrost 4: Not used
1: Pump down 5: Drainin
g
2: Not used 6: Injection delay
3: Defrostin
g
7: Fan delay
|
S5 A °C Defrost sensor temperature in section A
7:02:02
|
S5 B °C Only AKC 115A
/
Defrost sensor temperature in section B
7:02:03 AKC 116A
|
S5 C °C Only AKC 116A Defrost sensor temperature in section C
7:02:04
|
DefTime m Actual defrost cut-in time or duration of the latest finished
7:02:05 defrostin
g
period.
|
MDefTime m Avera
g
e value of the latest 4 defrostin
g
periods.
7:02:06
|
AccDefSkip Total number of skipped defrosts since start
7:02:07
|
AccNo.Def Total number of sustained defrosts since start
7:02:08
|
Defrost Ctrl. Definition of defrostin
g
method
Settin
g
s
7:03
Def. Ctrl. Choose defrost function ON/OFF
OFF/ON
7:03:01
|
Man.Def. Manual defrost is activated when ON
OFF/ON (Chan
g
es automatically to OFF)
7:03:02
|
DOD Ctrl. Choose defrost on demand ON/OFF
OFF/ON
7:03:03
|
Fan run Choose fan operation durin
g
defrost ON/OFF
OFF/ON
7:03:04
|
Defrost Stop. Definitions of defrost stop
Temp(1)/Time(2)
7:04
Temp/Time 1: Temperature stop (time as security)
1 - 2 2: Stop on time
7:04:01
|
MaxDefTime Max. permissible defrost time in minutes
5 - 180 (Security time on Temperature stop)
7:04:02
|
Def.Stop °C Temperature value of defrost stop
0 - 60
7:04:03
|
DefStop Sx Definition of sensor for defrost
2 - 5 Help 2: S2 3:S3
7:04:04 4: S4 5: S5 (default settin
g
)
AKC 114A-116A Version 1.5x Menu operation RC.1M.B3.02 © Danfoss 11/1998 15
|
Defrost Sequence Defrost sequence
Settin
g
s
7:05
Inj.Del m Liquid injection delay time
0 - 60
7:05:01
|
FanOnDel m Max. permissible fan start delay after defrostin
g
.
0 - 60 The delay time runs from the expiry of the delay time, if applicable,
7:05:02 for the liquid injection.
|
Fan On °C Temperature at which the fan starts after defrost.
-15 - 0 Fans starts when all S5 temperatures are below the value.
7:05:03
|
Def.Pro
g
ramme
schedules Select
7:06
|
Mon Sched. Choose defrost pro
g
ramme for Mondays
1 - 3 See also 7:08. 7:09 and 7:10
7:06:01
|
Tue Sched. Choose defrost pro
g
ramme for Tuesdays
1 - 3 See also 7:08. 7:09 and 7:10
7:06:02
|
Wed Sched. Choose defrost pro
g
ramme for Wednesdays
1 - 3 See also 7:08. 7:09 and 7:10
7:06:03
|
Thu Sched. Choose defrost pro
g
ramme for Thursdays
1 - 3 See also 7:08. 7:09 and 7:10
7:06:04
|
Fri Sched. Choose defrost pro
g
ramme for Fridays
1 - 3 See also 7:08. 7:09 and 7:10
7:06:05
|
Sat Sched. Choose defrost pro
g
ramme for Saturdays
1 - 3 See also 7:08. 7:09 and 7:10
7:06:06
|
Sun Sched. Choose defrost pro
g
ramme for Sundays
1 - 3 See also 7:08. 7:09 and 7:10
7:06:07
|
Def. Schedules Help function for settin
g
of defrost times
Auto pro
g
rammin
g
The defrost periods are distributed evenly durin
g
a defined
7:07 period of time within a 24-hour period.
No. Per Day Number of defrosts/24 hours
2 - 8
7:07:01
|
FirstDef Setting of time the 1st defrost begins
00:00
7:07:02
FirstDef Hour Setting of hours
0 - 23
07.07.02.01
|
FirstDef Min. Settin
g
of minutes
0 - 59
07.07.02.02
16 Menu operation RC.1M.B3.02 © Danfoss 11/1998 AKC 114A-116A Version 1.5x
|
LastDef Settin
g
of time the last defrost be
g
ins
00:00
7:07:03
LastDef Hour Settin
g
of hours
0 - 23
07.07.03.01
|
LastDef Min. Settin
g
of minutes
0 - 59
07.07.03.02
|
Auto Set Transfer the values to the three subsequent defrost pro
g
rammes.
OFF/ON Help In pos. ON they are entered in "7:08", "7:09" and "7:10".
7:07:04 If the three defrost pro
g
rammes are not to be identical,
corrections subsequent must be made in the individual
pro
g
rammes.
|
Schedule 1 Settin
g
s for defrost pro
g
ramme 1
Def. Start Times See 07:06
7:08
No. Per Day Number of defrosts/24 hours
0 - 8
7:08:01
|
Def1 Sc1 Setting of time the 1st defrost begins
00:00
7:08:02
Def1 Sc1 Hour Settin
g
of hours
0 - 23
07:08:02:01
|
Def1 Sc1 Min. Settin
g
of minutes
0 - 59
07:08:02:02
|
Def2 Sc1 Settin
g
of time the 2nd defrost be
g
ins
00:00 See 7:08:02
7:08:03
|
Def3 Sc1 Settin
g
of time the 3rd defrost be
g
ins
00:00
7:08:04
|
Def4 Sc1 Settin
g
of time the 4th defrost be
g
ins
00:00
7:08:05
|
Def5 Sc1 Settin
g
of time the 5th defrost be
g
ins
00:00
7:08:06
|
Def6 Sc1 Settin
g
of time the 6th defrost be
g
ins
00:00
7:08:07
|
Def7 Sc1 Settin
g
of time the 7th defrost be
g
ins
00:00
7:08:08
|
Def8 Sc1 Settin
g
of time the 8th defrost be
g
ins
00:00
7:08:09
|
Schedule 2 Settin
g
s for defrost pro
g
ramme 2
Def. Start Times See 7:06 / 7:08
7:09
|
Schedule 3 Settin
g
s for defrost pro
g
ramme 3
Def. Start Times See 7:06 / 7:08
7:10
AKC 114A-116A Version 1.5x Menu operation RC.1M.B3.02 © Danfoss 11/1998 17
|
Service mode Service function
8
Measurements of Measurements on inlets
input terminals
8:01
P0 Bar Suction pressure (measured with P0 pressure transmitter)
8:01:01
|
To °C Evaporatin
g
temperature
8:01:02
|
S2 A °C Gas temperature at evaporator outlet
8:01:03
|
S3 A °C Air temperature at evaporator inlet (air on)
8:01:04
|
S4 A °C Air temperature at evaporator outlet (air off)
8:01:05
|
S5 A °C Temperature at defrost sensor
8:01:06
|
S2 B °C Only AKC 115A
/
Gas temperature at evaporator outlet
8:01:07 AKC 116A
|
S3 B °C Only AKC 115A
/
Air temperature at S3 sensor (air on)
8:01:08 AKC 116A
|
S4 B °C Only AKC 115A
/
Air temperature at evaporator outlet (air off)
8:01:09 AKC 116A
|
S5 B °C Only AKC 115A
/
Temperature at defrost sensor
8:01:10 AKC 116A
|
S2 C °C Only AKC 116A Gas temperature at evaporator outlet
8:01:11
|
S3 C °C Only AKC 116A Air temperature at S3 sensor (air on)
8:01:12
|
S4 C °C Only AKC 116A Air temperature at evaporator outlet (air off)
8:01:13
|
S5 C °C Only AKC 116A Temperature at defrost sensor
8:01:14
|
Def. Start Statement of defrost start si
g
nal
8:01:15 (terminal 30 - 31)
|
ON input Statement of forced closin
g
input
8:01:16 (terminal 32 - 33)
|
DI input Statement of DI input
8:01:17
|
S6 Input Statement of S6 inlet
8:01:18 (terminal 60 - 61)
|
Ext.Ref. V Volta
g
e si
g
nal on "Ext.Ref." input
8:01:19
|
Manual Control Forced operation of outlets durin
g
service
of Outputs "Main switch" must be set to be "-1" (see 2:02:01)
8:02
Man Ctrl. ON: Manual control is permitted when "Main Switch"= -1.
OFF / ON NOTE: No monitorin
g
8:02:01 When manual settin
g
is finished, settin
g
must be chan
g
ed to OFF.
|
Fan Forced operation of fan outlet
OFF / ON (terminal 10-11)
8:02:02
18 Menu operation RC.1M.B3.02 © Danfoss 11/1998 AKC 114A-116A Version 1.5x
|
Railheat Forced operation of railheat outlet
OFF / ON (terminal 12-13)
8:02:03
|
AKV OD % A Forced operation of expansion valve openin
g
de
g
ree
0 - 100 (terminal 14-15)
8:02:04 (Fans must be operatin
g
durin
g
forced control operation)
|
DO Output Forced operation of DO Output
OFF / ON (terminal 16-17)
8:02:05
|
Compressor Forced operation of compressor outlet
OFF / ON (terminal 18-19)
8:02:06
|
Alarm Forced opertion of alarm outlet (terminal 20 - 21)
OFF / ON ON: Relay switch closed (no alarm)
8:02:07 OFF: Relay switch interrupted (alarm)
|
Defrost A Forced operation of defrost outlet
OFF / ON (terminal 22-23)
8:02:08
|
AKV OD % B Only AKC 115A
/
Forced operation of expansion valve openin
g
de
g
ree
0 - 100 AKC 116A (terminal 110-111)
8:02:09 (Fans must be operatin
g
durin
g
forced control operation)
|
Defrost B Only AKC 115A
/
Forced operation of defrost outlet
OFF / ON AKC 116A (terminal 112-113)
8:02:10
|
AKV OD % C Only AKC 116A Forced operation of expansion valve openin
g
de
g
ree
0 - 100 (terminal 120-121)
8:02:11 (Fans must be operatin
g
durin
g
forced control operation)
|
Defrost C Only AKC 116A Forced operation of defrost outlet
OFF / ON (terminal 122-123)
8:02:12
AKC 114A-116A Version 1.5x Menu operation RC.1M.B3.02 © Danfoss 11/1998 19
Error Log:
The followin
g
display read-outs are only visible if there is an active error.
A, B or C in brackets show in which re
g
ulation an active error i recorded.
When the error is corrected, the error messa
g
e can be removed by pressin
g
ENTER.
(If the code function has been selected, a code must also be entered).
S2 ( ) Error S2 sensor error Check sensor connection / sensor resistance
S3 ( ) Error S3 sensor error Check sensor connection / sensor resistance
S4 ( ) Error S4 sensor error Check sensor connection / sensor resistance
S5 ( ) Error S5 sensor error Check sensor connection / sensor resistance
AKS 32 Error AKS 32 sensor error Check sensor connection
Hi
g
h Air Temp ( ) Too hi
g
h air temperature
Low Air Temp ( ) Too low air temperature
Low S4 Temp. ( ) Too low S4 temperature See "3:05:06"
Overfloated Overfilled evaporator
evaporator ( )
Max. Def. period Max. defrostin
g
period exceeded Defrostin
g
finished accordin
g
to time not as selected accordin
g
exceeded
(
)
to temperature
Max. fan del time Max. fan delay exceeded When defrost has been completed, the fan start will be based on
exceeded ( ) time, and not on temperature (6:04:01)
230 Volt on Wron
g
defrost demand Active defrost si
g
nal on terminal 30 - 31 contrary to just finished
Def. start input defrostin
g
.
Check clock After power failure, timer must be set
settin
g
s
Standby mode The Main switch is either set in the position
"Controller stop" or "Service" (see 2:02:01).
Refri
g
erant No selection of refri
g
erant Select refri
g
erant
not selected
Rf
g
. Chan
g
ed Chan
g
ed refri
g
erant Check chosen refri
g
erant. Re
g
ulation with chan
g
ed refri
g
erant
has come into force.
DI Alarm
/
Alarm on di
g
ital input Check the function
Door Alarm
/
Safety cutout
/
Fan failure
/
Leak alarm
AI Max Alarm Too hi
g
h level on analo
g
input
limit exceeded
AI Min Alarm Too low level on analo
g
input
limit exceeded
Liquid supply Flash
g
as or missin
g
Check for flash
g
as / liquid
fault alarm ( ) liquid
20 Menu operation RC.1M.B3.02 © Danfoss 11/1998 AKC 114A-116A Version 1.5x
Communications/messages from AKA 21
Message not sent There is no contact between Check the data communication system
control panel and a controller
Regulator message - ll - Check the data communication system
not received
No node - ll - Check the data communication system
(There is no gateway on the data communication system)
Initialisation error - ll - Check the data communication system
(There is a
g
ateway on the data communication system)
The messa
g
e may be removed, if you disconnect AKA 21 briefly
Message not Temporary communication Wait, or if it is a newly started system, check the setup of the data
understood problem or wrong setup communication system
Dansett supervising Pause function When you push a key, the display disappears.
Supervising Lack of contact to a controller Check the data communication system
no answer
AKC AKA 21 had been disconnected Wait. The message disappears on its own after three minutes.
Occupied for a brief period
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
AC-RDT
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Danfoss Controller type AKC 114A, 115A, and 116A for controlling evaporators. Verx. 1.5x. AKA 21 Installation guide