Vega VEGAPULS C 11 Operating instructions

Type
Operating instructions
Operating Instructions
Radar sensor for continuous level
measurement
VEGAPULS C 11
Two-wire 4 … 20 mA
Document ID: 58340
2
Contents
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
Contents
1 About this document ............................................................................................................... 4
1.1 Function ........................................................................................................................... 4
1.2 Target group ..................................................................................................................... 4
1.3 Symbols used................................................................................................................... 4
2 For your safety ......................................................................................................................... 5
2.1 Authorised personnel ....................................................................................................... 5
2.2 Appropriate use ................................................................................................................ 5
2.3 Warning about incorrect use ............................................................................................. 5
2.4 General safety instructions ............................................................................................... 5
2.5 Modes for worldwide use.................................................................................................. 6
2.6 Installation and operation in the USA and Canada ........................................................... 6
3 Product description ................................................................................................................. 7
3.1 Conguration .................................................................................................................... 7
3.2 Principle of operation........................................................................................................ 9
3.3 Adjustment ....................................................................................................................... 9
3.4 Packaging, transport and storage ..................................................................................... 9
3.5 Accessories.................................................................................................................... 10
4 Mounting ................................................................................................................................. 11
4.1 General instructions ....................................................................................................... 11
4.2 Mounting versions .......................................................................................................... 11
4.3 Mounting instructions ..................................................................................................... 12
4.4 Measurement setup - Flow ............................................................................................. 15
5 Connecting to power supply ................................................................................................. 18
5.1 Preparing the connection ............................................................................................... 18
5.2 Wiring plan ..................................................................................................................... 18
5.3 Switch-on phase............................................................................................................. 18
6 Access protection .................................................................................................................. 19
6.1 Bluetooth radio interface ................................................................................................ 19
6.2 Protection of the parameterization .................................................................................. 19
6.3 Storing the codes in myVEGA ........................................................................................ 20
7 Setup with smartphone/tablet (Bluetooth) .......................................................................... 21
7.1 Preparations ................................................................................................................... 21
7.2 Connecting ..................................................................................................................... 21
7.3 Parameter adjustment .................................................................................................... 22
8 Setup with PC/notebook (Bluetooth) ................................................................................... 23
8.1 Preparations ................................................................................................................... 23
8.2 Connecting ..................................................................................................................... 23
8.3 Parameter adjustment .................................................................................................... 24
9 Adjustment menu ................................................................................................................... 25
9.1 Menu overview ............................................................................................................... 25
9.2 Description of the applications ....................................................................................... 27
10 Diagnostics and servicing .................................................................................................... 31
10.1 Maintenance .................................................................................................................. 31
10.2 Rectify faults ................................................................................................................... 31
3
Contents
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
10.3 Diagnosis, fault messages ............................................................................................. 32
10.4 Status messages according to NE 107 .......................................................................... 32
10.5 Treatment of measurement errors .................................................................................. 34
10.6 Software update ............................................................................................................. 38
10.7 How to proceed if a repair is necessary .......................................................................... 39
11 Dismount................................................................................................................................. 40
11.1 Dismounting steps.......................................................................................................... 40
11.2 Disposal ......................................................................................................................... 40
12 Certicatesandapprovals .................................................................................................... 41
12.1 Radio licenses ................................................................................................................ 41
12.2 EU conformity ................................................................................................................. 41
12.3 NAMUR recommendations ............................................................................................ 41
12.4 Environment management system ................................................................................. 41
13 Supplement ............................................................................................................................ 42
13.1 Technical data ................................................................................................................ 42
13.2 Dimensions .................................................................................................................... 48
13.3 Industrial property rights ................................................................................................. 49
13.4 Licensing information for open source software ............................................................. 49
13.5 Trademark ...................................................................................................................... 49
Safety instructions for Ex areas
TakenoteoftheExspecicsafetyinstructionsforExapplications.
These instructions are attached as documents to each instrument
with Ex approval and are part of the operating instructions.
Editing status: 2021-03-09
4
1 About this document
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
1 About this document
1.1 Function
This instruction provides all the information you need for mounting,
connection and setup as well as important instructions for mainte-
nance,faultrectication,theexchangeofpartsandthesafetyofthe
user. Please read this information before putting the instrument into
operation and keep this manual accessible in the immediate vicinity
of the device.
1.2 Target group
This operating instructions manual is directed to trained personnel.
Thecontentsofthismanualmustbemadeavailabletothequalied
personnel and implemented.
1.3 Symbols used
Document ID
This symbol on the front page of this instruction refers to the Docu-
ment ID. By entering the Document ID on www.vega.com you will
reach the document download.
Information, note, tip: This symbol indicates helpful additional infor-
mation and tips for successful work.
Note: This symbol indicates notes to prevent failures, malfunctions,
damage to devices or plants.
Caution: Non-observance of the information marked with this symbol
may result in personal injury.
Warning: Non-observance of the information marked with this symbol
may result in serious or fatal personal injury.
Danger: Non-observance of the information marked with this symbol
results in serious or fatal personal injury.
Ex applications
This symbol indicates special instructions for Ex applications.
List
The dot set in front indicates a list with no implied sequence.
1 Sequence of actions
Numbers set in front indicate successive steps in a procedure.
Battery disposal
This symbol indicates special information about the disposal of bat-
teries and accumulators.
5
2 For your safety
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
2 For your safety
2.1 Authorised personnel
All operations described in this documentation must be carried out
onlybytrained,qualiedpersonnelauthorisedbytheplantoperator.
During work on and with the device, the required personal protective
equipment must always be worn.
2.2 Appropriate use
VEGAPULS C 11 is a sensor for continuous level measurement.
Youcannddetailedinformationabouttheareaofapplicationin
chapter " Product description".
Operational reliability is ensured only if the instrument is properly
usedaccordingtothespecicationsintheoperatinginstructions
manual as well as possible supplementary instructions.
2.3 Warning about incorrect use
Inappropriate or incorrect use of this product can give rise to applica-
tion-specichazards,e.g.vesseloverllthroughincorrectmounting
or adjustment. Damage to property and persons or environmental
contamination can result. Also, the protective characteristics of the
instrument can be impaired.
2.4 General safety instructions
This is a state-of-the-art instrument complying with all prevailing
regulations and directives. The instrument must only be operated in a
technicallyawlessandreliablecondition.Theoperatorisresponsi-
ble for the trouble-free operation of the instrument. When measuring
aggressive or corrosive media that can cause a dangerous situation
if the instrument malfunctions, the operator has to implement suitable
measures to make sure the instrument is functioning properly.
The safety instructions in this operating instructions manual, the na-
tional installation standards as well as the valid safety regulations and
accident prevention rules must be observed by the user.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbi-
traryconversionsormodicationsareexplicitlyforbidden.Forsafety
reasons,onlytheaccessoryspeciedbythemanufacturermustbe
used.
To avoid any danger, the safety approval markings and safety tips on
the device must also be observed.
The low transmitting power of the radar sensor is far below the inter-
nationally approved limits. No health impairments are to be expected
with intended use. The band range of the measuring frequency can
be found in chapter " Technical data".
6
2 For your safety
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
2.5 Modes for worldwide use
Countryspecicsettingsfortheradarsignalsaredeterminedviathe
operating mode. The operating mode must be set in the operating
menu via the respective adjustment tool at the beginning of the setup
(see chapter " Setup" resp. " Menu overview".
Caution:
Operating the device without selecting the appropriate country group
constitutes a violation of the regulations of the radio approvals of the
respective country.
Further information can be found in the document " Regulations for
radar level measuring instruments with radio licenses" on our home-
page.
2.6 Installation and operation in the USA and
Canada
This information is only valid for USA and Canada. Hence the follow-
ing text is only available in the English language.
Installations in the US shall comply with the relevant requirements of
the National Electrical Code (ANSI/NFPA 70).
Installations in Canada shall comply with the relevant requirements of
the Canadian Electrical Code.
7
3 Product description
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
3 Product description
3.1 Conguration
The scope of delivery encompasses:
Radar sensor
Counter nut G1
1)
Information sheet " Documents and software" with:
Instrument serial number
QR code with link for direct scanning
Information sheet " PINs and Codes" (with Bluetooth versions)
with:
Bluetooth access code
Information sheet " Access protection" (with Bluetooth versions)
with:
Bluetooth access code
Emergency Bluetooth unlock code
Emergency device code
The further scope of delivery encompasses:
Documentation
Ex-specic"Safety instructions" (with Ex versions)
Radio licenses
Ifnecessary,furthercerticates
Note:
Optional instrument features are also described in this operating
instructions manual. The respective scope of delivery results from the
orderspecication.
This operating instructions manual applies to the following instrument
versions:
Hardware version from 1.0.0
Software version from 1.2.0
Scope of delivery
Scope of this operating
instructions
1)
With G thread
8
3 Product description
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
3
5
4
6
1
2
Fig. 1: Components of VEGAPULS C 11
1 Radar antenna
2 Processtting
3 Electronics housing
4 Counter nut
5 Mounting thread
6 Connection cable
Thetypelabelcontainsthemostimportantdataforidenticationand
use of the instrument.
0044
12...35V
4...20mA
1
4
5
6
2
3
www.vega.com
D-77761 SCHILTACH,
Made in Germany
VEGAPULS C 1.
RA - 222 2N 123
s/n 12345678
0...8m IP66/IP68, TYPE 6P
MWP 3bar (300kPa)
PVDF
L=5m
1½ NPT / 1 NPT
123456
Fig. 2: Layout of the type label (example)
1 Instrument type
2 Field for approvals
3 Technical data
4 QR code for device documentation
5 Bluetooth access code
6 Order number
Move to " www.vega.com"andenterinthesearcheldtheserial
number of your instrument.
Thereyoucanndthefollowinginformationabouttheinstrument:
Order data
Documentation
Software
Alternatively,youcanndallviayoursmartphone:
Scan the QR-code on the type label of the device or
Enter serial number manually in the VEGA Tools app (available
free of charge in the respective stores)
Constituent parts
Type label
Documents and software
9
3 Product description
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
3.2 Principle of operation
VEGAPULS C 11 is a radar sensor for non-contact, continuous level
measurement. It is suitable for liquids and solids in practically all
industries.
The instrument emits a continuous, frequency-modulated radar signal
throughitsantenna.Theemittedsignalisreectedbythemedium
andreceivedbytheantennaasanechowithmodiedfrequency.The
frequency change is proportional to the distance and is converted into
the level.
3.3 Adjustment
Devices with integrated Bluetooth module can be adjusted wirelessly
via standard adjustment tools:
Smartphone/tablet (iOS or Android operating system)
PC/notebook with Bluetooth USB adapter (Windows operating
system)
1
3
2
Fig. 3: Wireless connection to standard operating devices with integrated
Bluetooth LE
1 Sensor
2 Smartphone/Tablet
3 PC/Notebook
3.4 Packaging, transport and storage
Your instrument was protected by packaging during transport. Its
capacity to handle normal loads during transport is assured by a test
based on ISO 4180.
The packaging consists of environment-friendly, recyclable card-
board. For special versions, PE foam or PE foil is also used. Dispose
of the packaging material via specialised recycling companies.
Transport must be carried out in due consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause
damage to the device.
Application area
Functional principle
Wireless adjustment
Packaging
Transport
10
3 Product description
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
The delivery must be checked for completeness and possible transit
damage immediately at receipt. Ascertained transit damage or con-
cealed defects must be appropriately dealt with.
Up to the time of installation, the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated, the packages must be stored only under
the following conditions:
Not in the open
Dry and dust free
Not exposed to corrosive media
Protected against solar radiation
Avoiding mechanical shock and vibration
Storage and transport temperature see chapter " Supplement -
Technical data - Ambient conditions"
Relative humidity 20 … 85 %
3.5 Accessories
Screwedangesareavailableindierentversionsaccordingtothe
following standards: DIN 2501, EN 1092-1, BS 10, ASME B 16.5,
JIS B 2210-1984, GOST 12821-80.
Welded sockets are used to connect the devices to the process.
Threaded adapters enable simple adaptation of devices with stand-
ardthreadedttings,e.g.toprocess-sidehygieneconnections.
The mounting accessories are used for stable mounting of the device
at the measuring point. The parts are available in various versions and
sizes.
Transport inspection
Storage
Storage and transport
temperature
Flanges
Welded sockets and
adapters
Mounting strap
11
4 Mounting
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
4 Mounting
4.1 General instructions
The instrument is suitable for standard and extended ambient condi-
tions acc. to DIN/EN/IEC/ANSI/ISA/UL/CSA 61010-1. It can be used
indoors as well as outdoors.
Note:
For safety reasons, the instrument must only be operated within the
permissibleprocessconditions.Youcannddetailedinformationon
the process conditions in chapter " Technical data" of the operating
instructions or on the type label.
Hence make sure before mounting that all parts of the instrument ex-
posed to the process are suitable for the existing process conditions.
These are mainly:
Active measuring component
Processtting
Process seal
Process conditions in particular are:
Process pressure
Process temperature
Chemical properties of the medium
Abrasionandmechanicalinuences
4.2 Mounting versions
For a rigid mounting, a mounting bracket with opening for thread G1
is recommended. The mounting of the device in the bracket is carried
out via the supplied G1 counter nut of plastic. Take note of chapter "
Mounting instructions" for the recommended distance to the wall.
> 200 mm
(7.87
")
Fig. 4: Mounting via a mounting bracket
Ambient conditions
Process conditions
Mounting bracket
12
4 Mounting
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
4.3 Mounting instructions
Radar sensors for level measurement emit electromagnetic waves.
The polarization is the direction of the electrical component of these
waves.
The position of the polarisation is in the middle of the type label on the
instrument.
1
Fig. 5: Position of the polarisation
1 Middle of the type label
Note:
When the device is rotated, the direction of polarization changes and
hencetheinuenceofthefalseechoonthemeasuredvalue.Please
keep this in mind when mounting or making changes later.
When mounting the device, keep a distance of at least 200 mm
(7.874 in) from the vessel wall. If the device is installed in the center
of dished or round vessel tops, multiple echoes can arise. However,
these can be suppressed by an appropriate adjustment (see chapter
" Setup").
If you cannot maintain this distance, you should carry out a false
signal suppression during setup. This applies particularly if buildup on
the vessel wall is expected. In such cases, we recommend repeating
the false signal suppression at a later date with existing buildup.
> 200 mm
(7.87
")
Fig. 6: Mounting of the radar sensor on round vessel tops
In vessels with conical bottom it can be advantageous to mount the
device in the centre of the vessel, as measurement is then possible
down to the bottom.
Polarisation
Installation position
13
4 Mounting
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
Fig. 7: Mounting of the radar sensor on vessels with conical bottom
The centre of the antenna lens is the beginning of the measuring
range and at the same time the reference plane for the min./max.
adjustment, see following diagram:
1
Fig. 8: Reference plane
1 Reference plane
Donotmounttheinstrumentsinorabovethellingstream.Makesure
thatyoudetectthemediumsurface,nottheinowingproduct.
Fig.9:Mountingoftheradarsensorwithinowingmedium
For nozzle mounting, the nozzle should be as short as possible and
itsendrounded.Thisreducesfalsereectionsfromthenozzle.
With threaded socket, the antenna end should protrude at least 5 mm
(0.2 in) out of the socket.
Reference plane
Inowingmedium
Nozzle
14
4 Mounting
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
ca. 5 mm
Fig. 10: Recommended threaded socket mounting of VEGAPULS C 11
Ifthereectivepropertiesofthemediumaregood,youcanmount
VEGAPULS C 11 on sockets longer than the antenna. The socket end
should be smooth and burr-free, if possible also rounded.
Note:
When mounting on longer nozzles, we recommend carrying out a
false signal suppression (see chapter " Parameter adjustment").
Youwillndrecommendedvaluesforsocketheightsinthefollowing
illustration or the table. The values come from typical applications.
Deviating from the proposed dimensions, also longer sockets are
possible, however the local conditions must be taken into account.
d
h
Fig. 11: Socket mounting with deviating socket dimensions
Socket diameter d Socket length h
40 mm 1½" ≤150mm ≤5.9in
50 mm 2" ≤200mm ≤7.9in
80 mm 3" ≤300mm ≤11.8in
100 mm 4" ≤400mm ≤15.8in
150 mm 6" ≤600mm ≤23.6in
The mounting location of the radar sensor should be a place where no
otherequipmentorxturescrossthepathoftheradarsignals.
Vessel installations, such as e.g. ladders, limit switches, heating spi-
rals, struts, etc., can cause false echoes and impair the useful echo.
Make sure when planning your measuring point that the radar sensor
has a " clear view" to the measured product.
In case of existing vessel installations, a false signal suppression
should be carried out during setup.
If large vessel installations such as struts or supports cause false
echoes, these can be attenuated through supplementary measures.
Small,inclinedsheetmetalbaesabovetheinstallations"scatter"
theradarsignalsandpreventdirectinterferingreections.
Vessel installations
15
4 Mounting
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
Fig.12:Coverat,large-areaproleswithdeectors
In liquids, direct the device as perpendicular as possible to the me-
dium surface to achieve optimum measurement results.
Fig. 13: Alignment in liquids
If there are agitators in the vessel, a false signal suppression should
be carried out with the agitators in motion. This ensures that the
interferingreectionsfromtheagitatorsaresavedwiththebladesin
dierentpositions.
Fig. 14: Agitators
Throughtheactionoflling,stirringandotherprocessesinthevessel,
compact foams which considerably damp the emitted signals may
form on the medium surface.
If foams lead to measurement errors, you should use the biggest pos-
sible radar antennas or sensors with guided radar.
4.4 Measurement setup - Flow
In general, the following must be observed while mounting the device:
Orientation
Agitators
Foam generation
Mounting
16
4 Mounting
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
Mounting the sensor on the upstream or inlet side
Installationinthecentreoftheumeandverticaltotheliquid
surface
DistancetotheoverfalloriceorVenturiume
Min. distance to the max. height of damming for optimum accu-
racy: 250 mm (9.843 in)
2)
Everyumegeneratesadierentlevelofbackwaterdependingonits
typeandversion.Thespecicationsofthefollowingumesareavail-
able in the instrument:
Predenedcurves
Aowmeasurementwiththesestandardcurvesisveryeasytoset
up,asnodimensionalinformationoftheumeisrequired.
Palmer-Bowlusume(Q=kxh
1.86
)
Venturi,trapezoidalweir,rectangularume(Q=kxh
1.5
)
V-Notch,triangularoverfall(Q=kxh
2.5
)
Dimensions (ISO standard)
Whenselectingthesecurves,thedimensionsoftheumemustbe
known and entered via the assistant. As a result, the accuracy of the
owmeasurementishigherthanwiththespeciedcurves.
Rectangularume(ISO4359)
Trapezoidalume(ISO4359)
U-shapedume(ISO4359)
Triangular overfall thin-walled (ISO 1438)
Rectangularumethin-walled(ISO1438)
Rectangular weir broad crown (ISO 3846)
Flow formula
Iftheowformulaofyourumeisknown,youshouldselectthisop-
tion,astheaccuracyoftheowmeasurementishighesthere.
Flowformula:Q=kxh
exp
Manufacturerdenition
IfyouuseaParshallumefromthemanufacturerISCO,thisoption
mustbeselected.Thisgivesyouahighaccuracyofowmeasure-
mentwitheasyconguration.
Alternatively, you can also take over Q/h table values provided by the
manufacturer here.
ISCOParshallume
Q/htable(assignmentofheightwithcorrespondingowinatable)
Detailed project planning data can be found at the channel manufac-
turers and in the technical literature.
Thefollowingexamplesserveasanoverviewforowmeasurement.
Flume
2)
At smaller distances the measuring accuracy is reduced, see "Technical
data".
17
4 Mounting
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
3 ... 4 h
max
90°
2
3
1
h
max
≥ 2 x h
max
90°
42 3
≥ 250 mm
(
9.84")
≥ 250 mm
(
9.84")
Fig.15:Flowmeasurementwithrectangularume:h
max.
=max.llingofthe
rectangularume
1 Overfallorice(sideview)
2 Upstream water
3 Tailwater
4 Overfallorice(viewfromtailwater)
2
3 ... 4 x h
max
90°
h
max
B
1
≥ 250 mm
(
9.84")
Fig.16:FlowmeasurementwithKhafagi-Venturiume:h
max.
=max.llingofthe
ume;B=tightestconstrictionintheume
1 Position sensor
2 Venturiume
Rectangular overfall
Khafagi-Venturiume
18
5 Connecting to power supply
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
5 Connecting to power supply
5.1 Preparing the connection
Always keep in mind the following safety instructions:
Carryoutelectricalconnectionbytrained,qualiedpersonnel
authorised by the plant operator
Warning:
Only connect or disconnect in de-energized state.
Thedataforpowersupplyarespeciedinchapter"Technical data".
Note:
Power the instrument via an energy-limited circuit (power max. 100 W)
acc. to IEC 61010-1, e.g.
Class 2 power supply unit (acc. to UL1310)
SELV power supply unit (safety extra-low voltage) with suitable
internal or external limitation of the output current
Keepinmindthefollowingadditionalfactorsthatinuencetheoperat-
ing voltage:
Lower output voltage of the power supply unit under nominal load
(e.g. with a sensor current of 20.5 mA or 22 mA in case of fault)
Inuenceofadditionalinstrumentsinthecircuit(seeloadvaluesin
chapter " Technical data")
Thedeviceissuppliedwithaxedconnectedcable.Ifanextensionis
required, a standard two-wire cable can be used.
5.2 Wiring plan
1
2
Fig. 17: Wire assignment in permanently connected connection cable
Wire colour Function Polarity
1 Brown Voltage supply, signal output Plus (+)
2 Blue Voltage supply, signal output Minus (-)
5.3 Switch-on phase
After connection to the power supply, the device carries out a self-
test:
Internal check of the electronics
Output signal is set to failure
The current measured value is then output on the signal cable.
Safety instructions
Voltage supply
Connection cable
Wire assignment, con-
nection cable
19
6 Access protection
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
6 Access protection
6.1 Bluetooth radio interface
Devices with a Bluetooth radio interface are protected against un-
wanted access from outside. This means that only authorized persons
can receive measured and status values and change device settings
via this interface.
A Bluetooth access code is required to establish Bluetooth com-
munication via the adjustment tool (smartphone/tablet/notebook).
This code must be entered once when Bluetooth communication is
establishedforthersttimeintheadjustmenttool.Itisthenstoredin
the adjustment tool and does not have to be entered again.
The Bluetooth access code is individual for each device. It is printed
on the device housing and is also supplied with the device in the infor-
mation sheet " PINs and Codes". It can be changed by the user after
therstconnectionhasbeenestablished.IftheBluetoothaccess
code has not been entered correctly, a new entry can only be made
after a waiting period has elapsed. The waiting time increases with
each additional incorrect entry.
The emergency Bluetooth access code enables Bluetooth communi-
cation to be established in the event that the Bluetooth access code
is no longer known. It can't be changed. The emergency Bluetooth
access code can be found in information sheet " Access protection".
If this document is lost, the emergency Bluetooth access code can
be retrieved from your personal contact person after legitimation.
The storage and transmission of Bluetooth access codes is always
encrypted (SHA 256 algorithm).
6.2 Protection of the parameterization
The settings (parameters) of the device can be protected against un-
wanted changes. The parameter protection is deactivated on delivery,
all settings can be made.
To protect the parameterization, the device can be locked by the user
with the aid of a freely selectable device code. The settings (param-
eters) can then only be read out, but not changed. The device code
is also stored in the adjustment tool. However, unlike the Bluetooth
access code, it must be re-entered for each unlock. When using the
adjustment app or DTM, the stored device code is then suggested to
the user for unlocking.
The emergency device code allows unlocking the device in case the
device code is no longer known. It can't be changed. The emergency
device code can also be found on the supplied information sheet " Ac-
cess protection". If this document is lost, the emergency device code
can be retrieved from your personal contact person after legitimation.
The storage and transmission of the device codes is always encrypt-
ed (SHA 256 algorithm).
Bluetooth access code
Emergency Bluetooth
unlock code
Device code
Emergency device code
20
6 Access protection
VEGAPULS C 11 • Two-wire 4 … 20 mA
58340-EN-210318
6.3 Storing the codes in myVEGA
If the user has a " myVEGA" account, then the Bluetooth access code
as well as the device code are additionally stored in his account under
" PINs and Codes".Thisgreatlysimpliestheuseofadditionaladjust-
ment tools, as all Bluetooth access and device codes are automati-
cally synchronized when connected to the " myVEGA" account
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

Vega VEGAPULS C 11 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI