ABB FEPL-02 Ethernet POWERLINK User manual

Type
User manual
OPTION FOR ABB DRIVES, CONVERTERS AND INVERTERS
FEPL-02 Ethernet POWERLINK adapter
module
User’s manual
List of related manuals
See section Related manuals on page 15.
You can find manuals and other product documents in PDF format on the
Internet. See section Document library on the Internet on the inside of the
back cover. For manuals not available in the Document library, contact your
local ABB representative.
The code below opens an online listing of the manuals applicable to the
product:
Fieldbus connectivity webpage
FEPL-02 manual
6. Start-up
User’s manual
FEPL-02 Ethernet POWERLINK adapter
module
3AUA0000123527 Rev B
EN
EFFECTIVE: 2018-03-16
2018 ABB Oy
All Rights Reserved.
1. Safety instructions
Table of contents
4. Mechanical installation
5. Electrical installation
Table of contents 5
Table of contents
1. Safety instructions
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Use of warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety in installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2. About the manual
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Purpose of the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Target audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Related manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Terms and abbreviations used in this manual . . . . . . . . . . . . . . 17
General terms and abbreviations . . . . . . . . . . . . . . . . . . . . 17
Ethernet POWERLINK terms and abbreviations . . . . . . . . . 17
Cybersecurity disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3. Overview of the Ethernet POWERLINK network and
the FEPL-02 module
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Ethernet POWERLINK network . . . . . . . . . . . . . . . . . . . . . . . . . 21
Example topology of the Ethernet POWERLINK link . . . . . 22
FEPL-02 Ethernet POWERLINK adapter module . . . . . . . . . . . 23
Layout of the FEPL-02 adapter module . . . . . . . . . . . . . . . . 24
4. Mechanical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Necessary tools and instructions . . . . . . . . . . . . . . . . . . . . . . . . 25
Unpacking and examining the delivery . . . . . . . . . . . . . . . . . . . 25
Installing the adapter module . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6 Table of contents
5. Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Necessary tools and instructions . . . . . . . . . . . . . . . . . . . . . . . . 29
General cabling instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Connecting the adapter module to the Ethernet POWERLINK net-
work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
6. Start-up
What this chapter contains: . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Drive configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Ethernet POWERLINK connection configuration . . . . . . . . . 32
FEPL-02 configuration parameters – group A (group 1) 33
FEPL-02 configuration parameters – group B (group 2) 38
FEPL-02 configuration parameters – group C (group 3) 38
Control locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Starting up ACS355 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Parameter setting examples – ACS355 . . . . . . . . . . . . . . . . 41
Speed control using the CiA 402 velocity mode (vl) . . . . 41
Speed and torque control using ABB Drives
communication profile. . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Starting up ACSM1 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Parameter setting examples – ACSM1 . . . . . . . . . . . . . . . . 47
Position control with the CiA 402 profile position
mode (pp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Starting up ACS850 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Parameter setting examples – ACS850 . . . . . . . . . . . . . . . . 51
Speed control using the CiA 402 velocity mode (vl) . . . . 51
Speed control using the ABB Drives communication
profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Starting up ACS380, ACS580 and ACS880 drives . . . . . . . . . . 55
Parameter setting examples – ACS380, ACS580 and ACS880
56
Speed control using the ABB Drives communication
profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Configuring the master station . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Downloading an XML Device Description File (XDD) . . . . . 58
Table of contents 7
Configuring a B&R PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Adding the .xdd file. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Associating the adapter module with the PLC . . . . . . . . 61
Mapping objects required for controlling the drive . . . . . 66
Building a project and transfering it to the PLC . . . . . . . 68
Forcing values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
7. Communication profiles
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Communication profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
CANopen device profile CiA 402 . . . . . . . . . . . . . . . . . . . . . . . . 75
Supported modes of operation . . . . . . . . . . . . . . . . . . . . . . 75
Velocity mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Profile torque mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Profile velocity mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Profile position mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Homing mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Process data scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Torque data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Velocity data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Position data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Process feedback values . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Control word and Status word . . . . . . . . . . . . . . . . . . . . . . . 78
Control word contents . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Status word contents . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
State machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
ABB Drives communication profile . . . . . . . . . . . . . . . . . . . . . . . 83
Control word and Status word . . . . . . . . . . . . . . . . . . . . . . . 83
Control word contents . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Status word contents . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
State machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Actual values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
8 Table of contents
8. Communication protocol
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Ethernet POWERLINK communication cycle . . . . . . . . . . . . . . . 91
Ethernet POWERLINK state machine . . . . . . . . . . . . . . . . . . . . 92
NMT_GS_INITIALISATION . . . . . . . . . . . . . . . . . . . . . . . . . 92
NMT_GS_COMMUNICATING . . . . . . . . . . . . . . . . . . . . . . . 93
NMT_CS_NOT_ACTIVE . . . . . . . . . . . . . . . . . . . . . . . . 93
The NMT_CS_PREOPERATIONAL states . . . . . . . . . . 94
NMT_CS_READY_TO_OPERATE . . . . . . . . . . . . . . . . 94
NMT_CS_OPERATIONAL . . . . . . . . . . . . . . . . . . . . . . . 94
NMT_CS_STOPPED . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
DS 301 and DS 402 specification . . . . . . . . . . . . . . . . . . . . . . . . 96
Process Data Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Service Data Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
SDO Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Network Management Services . . . . . . . . . . . . . . . . . . . . . . . . . 98
NMT State Command Services . . . . . . . . . . . . . . . . . . . . . . 98
NMT Response Services . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Error entry specification . . . . . . . . . . . . . . . . . . . . . . . . . 99
9. Diagnostics
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Fault and warning messages . . . . . . . . . . . . . . . . . . . . . . . . . . 101
LED indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
10. Technical data
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
FEPL-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Ethernet POWERLINK link . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
11. Appendix A – CANopen Object Dictionary
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Object Dictionary structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Communication profile objects . . . . . . . . . . . . . . . . . . . . . . . . . 111
Manufacturer-specific profile objects . . . . . . . . . . . . . . . . . . . . 119
Actual signals and parameters of the drive . . . . . . . . . . . . . . . 121
Table of contents 9
CiA 402 profile objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
12. Appendix B – CANopen error codes
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
13. Appendix C IdentResponse Frame
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
NMT Service Slot structure of IdentResponse . . . . . . . . . . . . . 136
NMT Service Slot data fields of IdentResponse . . . . . . . . . . . 137
Further information
10 Table of contents
Safety instructions 11
1
Safety instructions
What this chapter contains
The chapter contains the warning symbols used in this manual and
the safety instructions which you must obey when you install or
connect an optional module to a drive, converter or inverter. If you
ignore the safety instructions, injury, death or damage can occur.
Read this chapter before you start the installation.
Use of warnings
Warnings tell you about conditions which can cause injury or death
and, or damage to the equipment. They also tell you how to
prevent the danger. The manual uses these warning symbols:
Electricity warning tells you about hazards from
electricity which can cause injury or death, or damage to
the equipment.
12 Safety instructions
General warning tells you about conditions, other than
those caused by electricity, which can cause injury or
death, or damage to the equipment.
Safety in installation
These instructions are for all who install or connect an optional
module to a drive, converter or inverter and need to open its front
cover or door to do the work.
WARNING! Obey these instructions. If you ignore them,
injury or death, or damage to the equipment can occur.
If you are not a qualified electrician, do not do installation or
maintenance work.
Disconnect the drive, converter or inverter from all possible
power sources. After you have disconnected the drive,
converter or inverter, always wait for 5 minutes to let the
intermediate circuit capacitors discharge before you continue.
Disconnect all dangerous voltages connected to other control
signal connectors in reach. For example, it is possible that 230
V AC is connected from outside to a relay output of the drive,
converter or inverter.
Always use a multimeter to make sure that there are no parts
under voltage in reach. The impedance of the multimeter must
be at least 1 Mohm.
About the manual 13
2
About the manual
What this chapter contains
This chapter introduces this manual.
Purpose of the manual
The manual provides information on installing, commissioning and
using the FEPL-02 Ethernet POWERLINK adapter module.
Applicability
This manual applies to the FEPL-02 Ethernet POWERLINK
adapter module, software version 1.0 or later.
Target audience
This manual is intended for people who plan the installation, install,
start up, use and service the adapter module. Before you do work
on the module, read this manual and the applicable drive manual
that contains the hardware and safety instructions for the product
in question.
You are expected to know the fundamentals of electricity, wiring,
electrical components and electrical schematic symbols.
The manual is written for readers worldwide. Both SI and imperial
units are shown.
14 About the manual
Compatibility
The FEPL-02 Ethernet POWERLINK adapter module is compatible
with different ABB drives and solar inverters.
ACS355
ACSM1
ACH580
ACS580
ACS850
ACQ810
ACS880.
The FEPL-02 Ethernet POWERLINK adapter module is compatible
with all master stations that support the Ethernet POWERLINK
protocol.
Note: The adapter module is compatible with more drives that may
not be listed here. For details of compatibility, check the drive’s
firmware manual.
Before you start
It is assumed that the drive is installed and ready to operate before
you start the installation of the adapter module.
In addition to conventional installation tools, have the drive
manuals available during the installation as they contain important
information not included in this manual. The drive manuals are
referred to at various points of this manual.
About the manual 15
Related manuals
Drive user’s manuals Code (English)
ACS355 drives (0.37…22 kW,
0.5…30 hp) user’s manual
3AUA0000066143
Drive hardware manuals and
guides
ACSM1 manuals 00578051
ACQ810 manuals 00598718
ACS850-04 manuals 00592009
ACS850-04 manuals 00592009
ACH580-01 manuals 9AKK10103A0587
ACH580-04 manuals 9AKK106930A9059
ACH580-07 manuals 9AKK106930A5241
ACS580-01 manuals 9AKK105713A8085
ACS580-04 manuals 9AKK106930A9060
ACS580-07 (75 to 250 kW) manuals 9AKK106930A5239
ACS580-07 (250 to 500 kW) manuals 9AKK106713A0278
ACS880-01 manuals 9AKK105408A7004
ACS880-04 manuals 9AKK105713A4819
ACS880-07 manuals 9AKK105408A8149
ACS880-07 (560 to 2800 kW) 9AKK105713A6663
ACS880-17 (132 to 355 kW) 9AKK106930A3466
ACS880-17 (160 to 3200 kW) 9AKK106354A1499
ACS880-37 (132 to 355 kW) 9AKK106930A3467
ACS880-37 (160 to 3200 kW) 9AKK106354A1500
Option manuals and guides
FEPL-02 Ethernet POWERLINK
adapter user’s manual
3AUA0000123527
16 About the manual
Contents
The manual consists of the following chapters:
Safety instructions contains the safety instructions which you
must follow when installing a fieldbus adapter module.
About the manual introduces this manual.
Overview of the Ethernet POWERLINK network and the FEPL-
02 module contains a short description of the Ethernet
POWERLINK network and the adapter module.
Mechanical installation contains a delivery checklist and
instructions to install the adapter module.
Electrical installation contains instructions on cabling and
connecting the module to the Ethernet POWERLINK network.
Start-up presents the steps to take during the start-up of the
drive with the adapter module and gives examples of
configuring the master.
Communication profiles describes the communication profiles
used in the communication between the master, the adapter
module and the drive.
Communication protocol describes the Ethernet POWERLINK
protocol for the adapter module.
Diagnostics explains how to trace faults with the status LEDs
on the adapter module.
Technical data contains the technical data of the adapter
module and the Ethernet POWERLINK link.
Appendix A – CANopen Object Dictionary contains a list of the
CANopen objects supported by the adapter module.
Appendix B – CANopen error codes contains a list of the
CANopen error codes.
Appendix C IdentResponse Frame contains the contents of
the IdentResponse Frame.
About the manual 17
Terms and abbreviations used in this manual
General terms and abbreviations
Ethernet POWERLINK terms and abbreviations
Term/abbreviation Explanation
Command word See Control word.
Communication module Communication module is a name for a device
(eg, a fieldbus adapter) through which the drive
is connected to an external communication
network (eg, a fieldbus). The communication
with the module is activated with a drive
parameter.
Control word 16-bit or 32-bit word from master to slave with
bit-coded control signals (sometimes called the
Command word).
FEPL-02 Ethernet
POWERLINK adapter
module
One of the optional fieldbus adapter modules
available for ABB drives. FEPL-02 is a device
through which an ABB drive is connected to an
Ethernet POWERLINK network.
Parameter Operating instruction for the drive. Parameters
can be read and programmed with the drive
control panel, drive PC tools or through the
adapter module.
Profile Adaptation of the protocol for certain application
field, for example, drives.
In this manual, drive-internal profiles (eg, DCU
or FBA) are called native profiles.
Status word 16-bit or 32-bit word from slave to master with
bit-coded status messages.
Term/abbreviation Explanation
CN Controlled Node; A node in a POWERLINK
network without the ability to manage the
SCNM mechanism.
Device description file All device-specific information is stored in the
Device Description File (XDD) of each device.
18 About the manual
MN Managing Node; A node capable of managing
the SCNM mechanism in a POWERLINK
network.
Object Dictionary A local storage of all communication objects
recognized by the device.
OSI Open Systems Interconnection.
PDO Process Data Object; Used for transmitting time
critical data, such as control commands,
references and actual values.
PReq PollRequest; A frame used in the isochronous
phase of the cyclic communication. With
PollRequest, the MN requests the CN to send
its data.
PRes PollResponse; A frame used in the isochronous
phase of the cyclic communication. The CN
responses with a PollResponse frame when it
receives a PollRequest from the MN.
R Read-only access.
RW Read-write access.
SCNM Slot Communication Network Management; In a
POWERLINK network, the MN allocates data
transfer time for data from each node in a cyclic
manner within a guaranteed cycle time. Within
each cycle there are slots for Isochronous Data,
and for Asynchronous Data for ad-hoc
communication.
The SCNM mechanism ensures that there are
no collisions during physical network access in
any of the networked nodes. Thus, it provides
deterministic communication via Legacy
Ethernet.
SDO Service Data Object; Used for transmitting non
time critical data, such as parameters.
Term/abbreviation Explanation
About the manual 19
Cybersecurity disclaimer
This product is designed to be connected to and to communicate
information and data via a network interface. It is Customer's sole
responsibility to provide and continuously ensure a secure
connection between the product and Customer network or any
other network (as the case may be). Customer shall establish and
maintain any appropriate measures (such as but not limited to the
installation of firewalls, application of authentication measures,
encryption of data, installation of anti-virus programs, etc.) to
protect the product, the network, its system and the interface
against any kind of security breaches, unauthorized access,
interference, intrusion, leakage and/or theft of data or information.
ABB and its affiliates are not liable for damages and/or losses
related to such security breaches, any unauthorized access,
interference, intrusion, leakage and/or theft of data or information.
Note: The web pages are meant only for configuring the device
during commissioning. For security reasons, it is recommended to
disable the web pages after commissioning.
20 About the manual
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142