Ê800-24127-Š
800-24127 2/18 Rev A Part 1 (BETA)
TESTING THE SYSTEM
Using the Test mode allows each detection point to be checked for proper
operation. Testing should be conducted weekly to ensure proper
operation.
• The keypad sounds a single beep about every 60 seconds as a
reminder that the system is in the Test mode.
• Alarm messages are not sent to Central Station when Test mode is on.
If a problem is experienced with any detection point (no confirming sounds,
no display), call for service immediately.
1.
Disarm the system and close all protected windows, doors, etc. The
READY indicator light should come on if all zones are intact
2.
Enter 4-digit Master code +
(walk)
3. Listen. The external sounder should sound for about 1 second then
turn off. If the sounder does not sound, CALL FOR SERVICE. The
“Test in Progress” display appears only on the keypad that started
the test.
4. Fault zones. Open each protected door and window in turn and listen
for three beeps from the keypad. Each faulted detection point should
appear on the display. The display clears when the door or window is
closed.
5. Walk in front of any interior motion detectors (if used) and listen for
three beeps. Each detector should appear on the display when it is
activated. The display clears when no motion is detected. Note that if
wireless motion detectors
are used, there is a 3-minute delay
between activations to conserve battery life.
6.
Test all smoke detectors, following the manufacturer's instructions.
7.
When all detection points have been c
hecked and are intact
(closed), there should be no zone numbers displayed.
8.
Exit test mode 4-digit code +
COMMUNICATION TEST
Perform a Communication Test to verify the communication paths to
the Central Station are working properly.
Enter 4-digit Master code +
SHUTTING DOWN/REBOOTING THE SYSTEM
Hard Reboot
To avoid corrupting the control’s memory, before removing power from
the system perform the following:
1. Disarm the system
2. Enter 4-digit Master code +
3. Wait until all of the LEDs are blank before removing power
Soft Reboot
Perform the following when instructed by an ADT Service
Representative.
1. Enter 4-digit Master code +
NOTES
TROUBLE CONDITIONS
The word CHECK on the keypad's display, accompanied by a
"beeping" at the keypad, indicates a trouble condition in the system at
the displayed zone number sensor and requires your attention.
Determine if the zone(s) displayed are intact and make them so if they
are not. If the display persists, CALL FOR SERVICE.
To silence the beeping for these conditions, press any key.
Typical Trouble conditions include the following:
COMM. FAILURE
(or FC)
A failure has occurred in the telephone
communication portion of your system.
SYSTEM LO BAT
(or BAT with no zone No.)
Low system battery condition exists.
LO BAT+ zone descriptor
(or BAT with zone No.)
Low battery condition in the wireless
transmitter. Either replace the battery
yourself, or CALL FOR SERVICE.
Rcvr Jam (or CHECK 90) RF interference in wireless system which
may impede reception from wireless
sensors.
ALARM 1xx (or 91)
FAULT 1xx
CHECK 1xx
A communication problem between the
control and a connected device (e.g., RF
receiver, zone expander) where the “xx”
indicates the device address.
MODEM COMM (or CC) Indicates that the control is on-line with the
Central Monitoring Station's remote
computer.
AC LOSS (or NO AC) The system is operating on battery power
only due to an AC power failure.
If only some lights are out on the premises,
check circuit breakers and fuses and
reset or replace as needed.
TELCO FAULT (or CHECK
94)
The telephone line has a problem.
Busy-Standby (or dI) If this message remains displayed for more
than 1 minute, system is disabled. CALL
FOR SERVICE.
SERVICING INFORMATION
Your local ADT Installer is the person best qualified to service your
alarm system. Arranging some kind of regular service program with
him is advisable. Your local Honeywell dealer is:
Name:
AD T S ec ur i t y S er vi c es
15 0 1 Ya ma to Ro ad
Bo ca Ra to n, FL 3 34 3 1
© 20 1 8 AD T S ec ur i t y S e rv ic es
Quick Guide to User Functions
User Guide Available Online: This Quick Guide describes the most frequently used features and functions of your system. For
full details of all user functions, please see the system’s User Guide located online at: https://www.adt.com/help/faq/system-
user-guides (see ADTHYBWL Series Security System User Guide P/N 800-24128 or higher). The full version User Guide is
also available from your installer upon request.
Congratulations on your ownership of an ADT Security System. This system provides:
• Three forms of detection: burglary, fire and emergency (see your installer for which forms of detection are installed)
• At least one keypad which provides control of system and displays system status
• Various sensors for perimeter and interior burglary detection
• Optional smoke or combustion detectors designed to provide early warning in case of fire.
Your system may also be programmed to automatically send alarm and status messages to a Central Monitoring Station.
SYSTEM BASICS
The following is a list of some of the most common features and
functions of your system:
• Several modes of burglary detection: Stay, Night-Stay, Away,
Instant, Maximum.
• Bypass feature lets you bypass selected zones while leaving the
rest of the system armed.
• Chime mode alerts you to the opening of protected doors and
windows while the system is disarmed.
• Fire and carbon monoxide detection are always active (if installed);
an alarm sounds if a fire or carbon monoxide condition is detected.
• Fire, Police and Personal Panic keys (if programmed) let you
manually initiate fire and personal alarms using the keypad.
• 4-digit security codes are used in conjunction with keypad
commands to perform system functions.
• Each user can be assigned a different security code, each with
different authority levels.
• The system sensors have been assigned to various “zones,” which
are specific areas of detection (e.g., front door, kitchen window, etc.).
• Zone numbers (points of detection) are displayed at the keypad
when an alarm or trouble condition occurs.
• Partitions provide independent areas of detection with each partition
containing a group of zones that can be armed and disarmed
without affecting other zones or users.
ENTRY/EXIT DELAYS
• Entry Delays give you time to disarm the system when you enter
through the designated entrance door.
• You must disarm the system before the entry delay period ends, or
an alarm will occur (keypad beeps during the entry delay period,
reminding you to disarm the system).
• Exit delay gives you time after arming the system to leave through
the designated exit door(s) without setting off an alarm. If
programmed, a slow beeping will sound during the exit delay period
until the last 10 seconds, which then changes to fast beeping
(alerting you to the end of exit delay). If you cannot leave within this
delay time period, you should stop, disarm the system, and start
over to avoid a false alarm.
•
••
• See your installer for your delay times. See the full User Guide for
details on Exit Error alarms.
NOTES ON BURGLARY DETECTION
• The system must be armed before the burglary detection can
sense intrusions.
• To arm your system, enter your security code followed by the
desired arming key.
• To disarm the system, enter your security code then press
the OFF key.
• When an alarm occurs, the keypad sounds and displays the
zone(s) causing the alarm. The external sounder may also
sound.
• If your system is connected to a Central Monitoring Station,
an alarm message is also sent (delayed 30 seconds by
default to reduce false alarms).
• To stop the alarm sounding, simply disarm the system.
• Memory of Alarm: When an alarm condition occurs, the
keypad displays the number(s) of the zone(s) that caused the
problem, and displays the type of alarm. Clear the Memory of
Alarm display by entering another “off” sequence.
IMPORTANT: If you return to the premises and
the main burglary sounder is on, or the keypad
beeps rapidly upon entering the premises, it
indicates that an alarm has occurred during your
absence and an intruder may still be on the
premises. LEAVE IMMEDIATELY and CONTACT
THE POLICE from a nearby safe location.
NOTES ON FIRE AND CO DETECTION
• Your fire alarm system (if installed) is on 24 hours a day,
for continuous detection. In the event of an emergency,
the smoke and heat detectors sound their alarms,
triggering a loud, interrupted pulsed sound from the
Keypad(s) and any external sounders.
• You can silence the alarm at any time by pressing the OFF
key (the security code is not needed to silence fire alarms).
• Carbon monoxide (CO) detectors, if installed, provide
continuous detection. If a high level of carbon monoxide is
detected, an interrupted pulsed alarm sound occurs at the
keypads and the detector(s). Immediately move to a spot
where fresh air is available, preferably outdoors. From a safe
area, call your security service provider for further
instructions. To silence the keypad sounding, press the OFF
key. To silence the detector, see its instructions.