• R temperature:‐45~45
Cangeofset
(‐40~120
F)
• Temperaturesensor:NTC,doublesensor.
• Outputcontactcapacityforcompressor:N.O.
20A/250V~;50/60Hz.Theinrushcurrentfor
compressorcontrolmaybe20Ainsteadof8A
duringtheperiodof1satstart.(applicableto1H.P.
compressorifmoreconnectedtoACcontactor)
• OutputcontactcapacityforEvap.Fan:N.O.
20a/250V~;50/60Hz.
• Maincontrollerpaneldim ension 78
X35X76mm.
Mountingdimension:71:29mm
Indicator
• Refrigerant:Whentherefr igerantLEDison,the
compressorisworking.
• Constanttemperature:WhentherefrigerantLEDis
off,thecompressorhasstopped.
• Delay:WhentherefrigerantLEDflashes,the
compressorstops.
• Defrost:WhenthedefrostLEDison,the
compressorandfanstopandtheheaterworks.
• Evaporatorfan:WhenthefanLEDison,thefanis
working.
FrontPanelOperation
• Settemperature:Press button,theset
temperatureisdisplayed;Pressorbuttontomodify
andstorethedisplayedvalue,pressbuttonto
exittheadjustmentanddisplaythecold‐room
temperature.
• Manualstart/stopdefrost:Pressbuttonand
holdfor6secondstodefrostorstopdefrost.
• Displaytheevaporatortemperature:Press
buttonandholdfor6seconds.Theevaporator
temperaturewillbedispla yed.After10seconds,the
cold‐roomtemperatureisresumedtobedisplayed.
ParameterSetup
• Indicationforsettingparameter: Theparametercan
beadjustedonlyaftercorrectPAhasbeenentered.
Allparameterscanonlybechecked,notadjusted;
however,itisavailablefortemperaturecontrolling.
• SettingParameter:Pressfor6seconds.Start
parametermenuandPA(menupassword)flashing.
Enterthepasswordbypressing or .Press
againtochoosetheparameter.Pressor
thentheparametercan bedisplayedandadjusted.
Aftertheadjustment,ifnobuttonhasbeenpressed
after30seconds,thesystemwillrestorethenew
parameterandgobacktonormalopera tions.
• Changingmenupassword(CPA):TheCPAcanbe
checkedorchangedonlyafterthecorrectmenu
passwordhasbeenentered.WhenitshowsCPA,
pressorthenthepresent passwordis
displayedandcanbechangedtoanewpassword.
Presstoconfirmthenewpassword.(Please
memorizethenewpasswordoryoucannever
adjustotherparameters.)
• Thefactorydefaultresumption:Pressbuttonfor
1secondandthenpressbuttonsimultaneously
for6seconds.Theindicatorwillflashandthenall
parameterswillberestoredtobacktothefactory
defaults.After10seconds,itwillreturntonormal
operation.
Parameterdetails
• Temperaturecontrolling:Afterturningonforthe
delaytime(e4),thecompressorstartsoperating
whencold‐roomtemperature(settemperature
+hysteresis),andwilloffwhencold‐room
temperaturesettemperature.Toprotectthe
compressoritcanbere‐started,unlessthetime
whenthecompressorstopseverytimeislonger
thanthedelaytime(E4).
• Evaporatorfanoperatingfunction:
F5isset“00”,parallelwithcompressor.
F5isset“01”,continuousrunning(exceptdefrost).
• Electricheaterdefrost:evaporatorsensor
temperature<defrostterminationtemperature
(F3),theheat erwillswitchonandthedefrostwill
start.
Afteradefrostinterval,itbeginstheautomaticdefrost
function.e.g.:Whentheevaporatorsensor
temperature<defrosttermination temperature(F3),
thedefrostLEDwillturnon,thecompressorandfanwill
stop,andtheheaterwillstart.Whentheevaporator
6