Operating Instructions
Air-to-Water Heatpump
Indoor Unit
Outdoor Unit
WH-SD24BE5 WH-UD24BE5
WH-SD30BE5 WH-UD30BE5
ENGLISH
ENGLISH
Before operating the unit, read these operating instructions thoroughly and keep them for future reference.
Before operating the unit, read these operating instructions thoroughly and keep them for future reference.
Before operating the unit, make sure the installation has been carried out correctly by authorized dealer correctly and
precisely following the installation instructions given.
2 ~ 9
2 ~ 9
SVENSKA
SVENSKA
Innan du använder enheten, läs noga igenom denna bruksanvisning och spara den för framtida bruk.
Innan du använder enheten, läs noga igenom denna bruksanvisning och spara den för framtida bruk.
Innan du använder enheten, se till att installationen har utförts noggrant och korrekt av auktoriserad återförsäljare som
följt de givna installationsinstruktionerna.
10 ~ 17
10 ~ 17
NORSK
NORSK
Les bruksanvisningen nøye før du bruker denne enheten, og oppbevar den for fremtidig bruk.
Les bruksanvisningen nøye før du bruker denne enheten, og oppbevar den for fremtidig bruk.
Før du bruker enheten, må du forsikre deg om at autorisert forhandler har utført korrekt og presis installasjon og har
fulgt installasjonsinstruksjonene som er gitt.
18 ~ 25
18 ~ 25
SUOMI
SUOMI
Lue nämä käyttöohjeet huolellisesti ennen yksikön käyttämistä ja säilytä ne tulevaisuutta varten.
Lue nämä käyttöohjeet huolellisesti ennen yksikön käyttämistä ja säilytä ne tulevaisuutta varten.
Varmista ennen laitteen käyttöä, että asennuksen on suorittanut valtuutettu jälleenmyyjä ja että se on tehty oikein ja
Varmista ennen laitteen käyttöä, että asennuksen on suorittanut valtuutettu jälleenmyyjä ja että se on tehty oikein ja
tarkasti annettuja asennusohjeita noudattaen.
tarkasti annettuja asennusohjeita noudattaen.
26 ~ 33
26 ~ 33
DANSK
DANSK
Læs brugsanvisningen grundigt igennem før du benytter anlægget og gem den til fremtidig brug.
Læs brugsanvisningen grundigt igennem før du benytter anlægget og gem den til fremtidig brug.
Sørg for, at anlægget er installeret korrekt af en autoriseret forhandler i overensstemmelse med de følgende
instruktioner, før anlægget tages i brug.
34 ~ 41
34 ~ 41
© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2009.
Unauthorized copying and distribution is a violation
of law.
1F566899_OYTH0907-00_1EN.indd 11F566899_OYTH0907-00_1EN.indd 1 8/19/2009 5:25:53 PM8/19/2009 5:25:53 PM
2
SAFETY PRECAUTIONS SAFETY PRECAUTIONS
Notes :
Notes :
Panasonic Air-to-Water Heatpump is a split system consisting only of an
indoor unit and an outdoor unit. This system designed for combination with
Panasonic Tank Unit. In case of non-Panasonic Tank Unit is being used
with Panasonic Air-to-Water Heatpump System, Panasonic cannot
guarantee neither good operation nor reliability of the system.
This manual describes how to operate the Heatpump system between
indoor and outdoor units only.
Other operation such as water tank, radiator and under oor system,
please refer to respective manufacturer operation manuals.
Thank you for purchasing
Panasonic Product
TABLE OF CONTENTS
TABLE OF CONTENTS
SAFETY PRECAUTIONS
2~3
PRODUCT OVERVIEW
4
BASIC OPERATION
5
ADVANCE OPERATION
6
CARE & CLEANING
7
TROUBLESHOOTING
8
INFORMATION
9
NOTE :
The illustrations in this manual are
for explanation purposes only and
may differ from the actual unit. It is
subjected to change without notice
for future improvement.
This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
Indoor Outdoor
Water outlet
temperature (°C)
Ambient
temperature (°C)
HEATING
Maximum 55 35
Minimum 25 -20
NOTICE :
When the outdoor temperature is out of the above temperature
range, the heating capacity will drop signi cantly and outdoor unit
might stop for protection control.
OPERATION CONDITION
OPERATION CONDITION
H
E
AT
F
O
R
C
H
E
AT
E
R
1
H
E
A
TE
R
2
S
E
T
T
I
N
G
S
T
A
T
U
S
P
U
M
P
D
W
W
A
T
E
R
I
N
L
ET
E
R
R
OR
O
F
F
/
O
N
W
A
T
E
R
O
U
T
LE
T
OU
T
DO
OR
C
C
C
0.
2
0
.
4
0
0
.
3
0
.
1
M
P
a
Indoor Unit
Power Supply
Outdoor Unit
Air inlet
Air inlet
Air inlet
Air inlet
Air outlet
Air outlet
1F566899_OYTH0907-00_1EN.indd 21F566899_OYTH0907-00_1EN.indd 2 8/19/2009 5:25:55 PM8/19/2009 5:25:55 PM
3
ENGLISH
DEFINITION
The instructions to be followed are classi ed by the following symbols:
This symbol denotes an action
that is PROHIBITED.
These symbols denote actions
that are COMPULSORY.
To prevent personal injury, injury to others, or property damage, please comply the following.
Incorrect operation due to failure to follow instructions may cause harm or damage, the seriousness of which is classi ed as below:
Warning
This sign warns of death or
serious injury.
Caution
This sign warns of injury or
damage to property.
Indoor Unit
Indoor Unit
• Do not install, remove and reinstall the unit by
yourself; improper installation will cause leakage,
electric shock or re. Please consult authorized
dealer for the installation work.
• Do not attempt to repair the unit by yourself.
Otherwise, it may cause injury if it is mishandling.
• Do not install the unit at outdoor. This is designed
for indoor installation only.
This unit is equipped with Residue Current Circuit
Breaker (RCCB). It is strongly recommended to
check the operation of the RCCB after installation
and periodically after servicing or maintenance by
authorized dealer to ensure it is in good working
order. Otherwise, it may cause electrical shock or
re in case of malfunction.
• The equipment must be earthed to prevent
electrical shock or re.
Power Supply
Power Supply
• Do not share the same power outlet with other
equipment.
• Do not modify power cords.
• Do not use extension cords.
• Do not operate with wet hands.
• Use the speci ed power supply cord.
• If the power supply cord is damaged, it must be
replaced by the manufacturer, its service agent or
similarly quali ed persons in order to avoid hazard.
• In case of emergency or presence of abnormal
conditions (burnt smell, etc), turn off the power
supply, and consult authorized dealer.
Outdoor Unit
Outdoor Unit
• Do not insert your ngers or other objects into the
unit, rotating parts may cause injury.
Indoor Unit
Indoor Unit
• Do not install the unit in a potentially explosive
atmosphere.
• Do not install the unit close to any combustible
equipment or at bathroom. Otherwise, it may cause
electric shock or re.
• Do not touch the water discharge pipe at the indoor
unit during operation.
• Do not place anything on top or beneath of the unit.
• Ensure that the drainage pipe is connected properly.
Otherwise, leakage may occur.
Control Panel
Control Panel
• Do not let the control panel get wet. Otherwise, it
may cause electric shock or re.
• Do not press the buttons on the control panel with
hard, pointed objects. Otherwise, it may damage
the unit.
• Do not wash the control panel with water, benzene,
thinner or scouring powder.
• Do not inspect or service the control panel by
yourself. Please consult authorized dealer.
Otherwise, it may cause injury if mishandling.
Power Supply
Power Supply
• Switch off the power supply before cleaning or
servicing.
• Turn off the power supply if the unit is not used for
a long period of time.
• This unit is equipped with a built-in surge protective
device. However, in order to further protect your
unit from being damaged by abnormally strong
lightning activity, you may want to disconnect it
from the power supply. Do not touch the unit during
lightning, it may cause electric shock.
• It is recommended to wear gloves during servicing
or maintenance in order to avoid hazard.
Outdoor Unit
Outdoor Unit
• Do not sit or step on the unit, you may fall down
accidentally.
• Do not touch the sharp aluminium n, sharp parts
may cause injury.
• Check the installation rack periodically to make
sure that it is not damaged. After long periods of
use, the strength of the installation rack may have
deteriorated.
OPERATION CONDITION
1F566899_OYTH0907-00_1EN.indd 31F566899_OYTH0907-00_1EN.indd 3 8/19/2009 5:25:55 PM8/19/2009 5:25:55 PM
4
HEAT
SETTING
STATUS
PUMPDW
WATER INLET ERROR
OFF
/
ON
WATER OUTLET OUTDOOR
C
CC
0.2
0.40
0.30.1
MPa
PRODUCT OVERVIEW PRODUCT OVERVIEW
Air-to-Water Heatpump
Air-to-Water Heatpump
Indoor Unit
Indoor Unit
Water Pressure Gauge
Water Pressure Gauge
0.2
0.40
0.30.1
MPa
• Do not press or hit the glass
cover with hard, pointed
objects. This may damage the
unit.
• Ensure that the water
pressure is between 0.05 to
0.2MPa.
• In case the water pressure is
out of the above range, please
consult authorized dealer.
Control Panel
Control Panel
HEA
T
SETT
ING
STA
TUS
PUMPDW
WAT
ER INL
ET
ERR
OR
OFF
/
ON
WAT
ER OUTLET
OUTD
OOR
C
C
C
Open the cover to
use the buttons
WATER OUTLET OUTDOOR
HEAT
SETTING
STATUS
PUMPDW
WATER INLET ERROR
C
CC
SET
SELECT
CANCEL
ERROR
RESET
SETTING
STATUS
SEARCH
PUMPDW
CHECK
OFF
/
ON
11
2
1
12 13
8
10
9
14
7
5
4
3
6
1
OFF/ON Button
8
System Pumpdown Mode Indicator
2
Operation LED
9
System Status Check Mode Indicator
3
System Setting Mode Buttons
10
System Setting Mode Indicator
4
Error Reset Button
11
Heating Operation Indicator
5
System Status Check Mode Buttons
12
Water Outlet Temperature Display
6
System Pumpdown Mode Button
13
Water Inlet Temperature Display
7
System Error Display
14
Outdoor Ambient Temperature Display
1F566899_OYTH0907-00_1EN.indd 41F566899_OYTH0907-00_1EN.indd 4 8/19/2009 5:25:56 PM8/19/2009 5:25:56 PM
5
ENGLISH
Air-to-Water Heatpump
Indoor Unit
Water Pressure Gauge
Control Panel
BASIC OPERATION BASIC OPERATION
WATER INLET ERROR
SET
SETTING
STATUS
CHECK
OFF
/
ON
Operation Start / Stop
Operation Start / Stop
The unit starts by pressing
OFF
/
ON
.
When unit is ON, operation LED is lit and the actual
temperature for water outlet, water inlet and outdoor
ambient are shown on the control panel display.
• Press
OFF
/
ON
again to stop the operation.
Operation details (Default setting)
Operation details (Default setting)
Operation takes place under default settings as follows:
-
-
When Outdoor ambient temperature (Out Lo) is less than 0°C, water outlet set temperature (H2O Lo) is 50°C.
When Outdoor ambient temperature (Out Hi) is more than 15°C, water outlet set temperature (H2O Hi) is 32°C.
In between the speci ed outdoor ambient temperature range (Out Lo and Out Hi), the system will automatically adjust
the water outlet temperature between speci ed range (H2O Lo and H2O Hi).
Lower outdoor ambient temperature will result in higher water outlet temperature and vice versa.
Optional Settings
Optional Settings
ERROR
RESET
Error code reset
• Not usable during normal operation.
PUMPDW
System Pump Down
• Not usable during normal operation.
• If accidentally pressed the
PUMPDW
, press
OFF
/
ON
to stop the pump down operation.
1F566899_OYTH0907-00_1EN.indd 51F566899_OYTH0907-00_1EN.indd 5 8/19/2009 5:25:56 PM8/19/2009 5:25:56 PM
6
Recommendation
Recommendation
It is strongly recommended to have the authorized dealer to change the water temperature range. The temperature range
for water outlet temperature and outdoor ambient temperature could be set by control panel.
Perform the steps below to set preferred temperature range.
SET
SELECT
CANCEL
ERROR
RESET
SETTING
STATUS
SEARCH
PUMPDW
CHECK
2
,
4
1
,
5
3
STEP 1: Press
SET
for 5 seconds to enter SETTING mode. “SETTING” indicator is ON.
STEP 2: Press
or to choose a parameter.
H2O Lo: Water outlet set
temperature at low outdoor
ambient set temperature
Selection range:
25°C ~ 55°C
HEAT
SETTING
STATUS
PUMPDW
C
H2O Hi: Water outlet set
temperature at high outdoor
ambient set temperature
HEAT
SETTING
STATUS
PUMPDW
C
Selection range:
25°C ~ 55°C
Out Lo: Low outdoor
ambient set temperature
HEAT
SETTING
STATUS
PUMPDW
C
Selection range:
-15°C ~ 15°C
Out Hi: High outdoor
ambient set temperature
HEAT
SETTING
STATUS
PUMPDW
C
Selection range:
-15°C ~ 15°C
Note: Please make sure High outdoor ambient set temperature (Out Hi) is always higher than Low outdoor
ambient set temperature (Out Lo).
STEP 3:
After selecting the desired parameter, press
SELECT
to enter the parameter. “ ” indicator will blink when a
parameter is selected.
STEP 4: Press
or to set the desired temperature.
STEP 5: Press
SET
again to con rm the setting.
Repeat steps 2 to 5 to set other parameters.
• Press
C
AN
C
E
L
or wait 30 seconds to exit SETTING mode.
The setting temperature will be stored in the system once con rm.
“SETTING” mode cannot be activated when the “PUMPDW” and “STATUS” indicator is ON.
ADVANCE OPERATION ADVANCE OPERATION
1F566899_OYTH0907-00_1EN.indd 61F566899_OYTH0907-00_1EN.indd 6 8/19/2009 5:25:58 PM8/19/2009 5:25:58 PM
7
ENGLISH
CARE & CLEANING CARE & CLEANING
CAUTION
Switch off the power supply before cleaning.
Indoor Unit & Control Panel
Indoor Unit & Control Panel
Do not splash water directly.
Wipe the unit gently with a soft, dry cloth.
Outdoor Unit
Outdoor Unit
Do not obstruct the air inlet and air outlet vents, it may cause low performance or breakdown. Please remove obstacles to
assure the ventilation.
During winter, please clean and remove the snow near outdoor unit so that the snow does no cover the air inlet and air
outlet vents.
Inspection
Inspection
In order to ensure optimal performance of the unit, seasonal inspections on the unit and eld wiring have to be carried out
at regular intervals. This maintenance should be carried out by authorized dealer.
Clear any obstruction at the air inlet and air outlet vents of outdoor unit.
For Extended Non-Use
For Extended Non-Use
Turn off the power supply.
Perform the steps below to check system status
Perform the steps below to check system status
SET
SELECT
CANCEL
ERROR
RESET
SETTING
STATUS
SEARCH
PUMPDW
CHECK
2
1
STEP 1:
Press
CHECK
for 5 seconds to enter STATUS mode.
STEP 2:
Press
or to check the Compressor Running Frequency or Error History.
• Press
C
AN
C
E
L
or wait 30 seconds to exit STATUS mode.
Once STATUS mode is entered, “STATUS” indicator is ON.
STATUS mode cannot be activated when the “SETTING” indicator is ON.
1F566899_OYTH0907-00_1EN.indd 71F566899_OYTH0907-00_1EN.indd 7 8/19/2009 5:25:58 PM8/19/2009 5:25:58 PM
8
Symptom
Symptom
Check
Check
Heating operation is not working ef ciently. Set the temperature correctly.
Is the panel heater valve closed.
Clear any obstruction at the air inlet and air outlet vents of outdoor unit.
Noisy during operation. Check if the unit has been installed at an incline or the cover is not
closed properly.
The unit does not work. Check if the circuit breaker is tripped.
Operation LED is no lit or control panel display
is blank.
Is the power supply off or power failure.
Check the following before calling for servicing.
Check the following before calling for servicing.
TROUBLESHOOTING TROUBLESHOOTING
Symptom
Symptom
Cause
Cause
Water owing sound during operation. Refrigerant ow inside the unit.
Operation is delayed a few minutes after
restart.
The delay is a protection to the unit’s compressor.
Outdoor unit emits water/steam. Condensation or evaporation occurs on pipes.
Outdoor unit emits steam during heating
mode.
This is due to defrost operation happens at the heat exchanger.
Outdoor unit does not operate. When the outdoor temperature is out of the operation condition range,
the heatpump system enter protection control.
System dif cult to heat-up. When heating is operated by indoor unit together with oor heating or
panel heater simultaneously, there may be case where warm water
temperature is getting lower and cause oor heating or panel heater
heat-up is weaken.
When outdoor air temperature is low, it may be dif cult to get warm.
Is the snow pile blocking the discharge outlet or intake inlet of outdoor
unit.
When water outlet set temperature is low, it may be dif cult to get warm.
System cannot get warm instantly. Due to the nature of the heatpump system, it may take some time to
heat-up the water if the unit is operated from cold-start.
Operation starts after power resumes. Auto restart is in function and operates under.
The following symptoms do not indicate malfunction.
The following symptoms do not indicate malfunction.
The operation LED blinks and error code appear on control panel display
The operation LED blinks and error code appear on control panel display
WATER INLET ERROR
C
CC
Turn the unit off and reveal the error code to authorized dealer.
1F566899_OYTH0907-00_1EN.indd 81F566899_OYTH0907-00_1EN.indd 8 8/19/2009 5:25:59 PM8/19/2009 5:25:59 PM
9
ENGLISH
The operation LED blinks and error code appear on control panel display
NON SERVICEABLE CRITERIAS
NON SERVICEABLE CRITERIAS
TURN OFF POWER SUPPLY then please consult authorized dealer under the following conditions:
Abnormal noise during operation.
Water/foreign particles have entered the control panel.
Water leaks from Indoor unit.
Circuit breaker switches off frequently.
Power cord becomes unnaturally warm.
Switches or buttons are not functioning properly.
Information for Users on Collection and Disposal of Old Equipment
These symbols on the products, packaging, and/or accompanying documents mean that used electrical and
electronic products should not be mixed with general household waste.
For proper treatment, recovery and recycling of old products, please take them to applicable collection points,
in accordance with your national legislation and the Directives 2002/96/EC and 2006/66/EC.
By disposing of these products correctly, you will help to save valuable resources and prevent any potential
negative effects on human health and the environment which could otherwise arise from inappropriate waste
handling.
For more information about collection and recycling of old products, please contact your local municipality,
your waste disposal service or the point of sale where you purchased the items.
Penalties may be applicable for incorrect disposal of this waste, in accordance with national legislation.
For business users in the European Union
If you wish to discard electrical and electronic equipment, please contact your dealer or supplier for further
information.
[Information on Disposal in other Countries outside the European Union]
These symbols are only valid in the European Union. If you wish to discard these items, please contact your
local authorities or dealer and ask for the correct method of disposal.
INFORMATION INFORMATION
1F566899_OYTH0907-00_1EN.indd 91F566899_OYTH0907-00_1EN.indd 9 8/19/2009 5:25:59 PM8/19/2009 5:25:59 PM
F566899
Printed in Malaysia
OYTH0907-00
Panasonic Corporation
Website: http://panasonic.net/
Pursuant to at the directive 2004/108/EC, article 9(2)
Panasonic Testing Centre
Panasonic Service Europe, a division of
Panasonic Marketing Europe GmbH
Winsbergring 15, 22525 Hamburg, F.R. Germany
1F566899_OYTH0907-00_1EN.indd Sec1:441F566899_OYTH0907-00_1EN.indd Sec1:44 8/19/2009 5:25:59 PM8/19/2009 5:25:59 PM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Panasonic WHSD30BE5 Operating instructions

Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI