York DM072 User manual

Category
Heat pumps
Type
User manual
036-21502-002-A-0303
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
SINGLE PACKAGE GAS/ELECTRIC UNITS
AND SINGLE PACKAGE
AIR CONDITIONERS
DM 036, 048, 060 & 072
3, 4, 5 & 6 NOMINAL TONS
10.0 SEER (3, 4 & 5 TONS), 9.0 EER (6 TONS)
®
TECHNICAL GUIDE
DESCRIPTION
YORK Sunline 2000™ units are convertible single package
air conditioners with a common cabinet and a common roof
curb for the 3, 4, 5 and 6 ton sizes. The units were designed
for light commercial and commercial applications. They can
easily be installed on a roof curb, slab, roof jack or frame.
All units include:
Powder Paint finish that meets ASTM-B-117 750 hour
salt spray standards
Permanently lubricated motors
Bottom or side air discharge configuration capability
(field convertible)
Manufactured under the quality standards of ISO9001
TM
Control Board
Copper tube/aluminum fin coils
Easy access to all components
Rigging holes in base rails for lifting
Fork lift slots on three sides
Single point power connection
Complete factory package - tested, charged and wired
CSA agency listing on all units
WARRANTY
Factory Limited Parts Warranty
One-year parts warranty
A Five-year parts warranty on the compressor and
electric heat elements.
Ten-year parts warranty on the gas-fired heat
exchangers.
036-21502-002-A-0303
2 Unitary Products Group
TABLE OF CONTENTS
DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE. . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 9
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 10
GUIDE SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . 38
Fig. # Pg. #
LIST OF FIGURES
1 UNIT CUTAWAY. . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 TYPICAL FIELD POWER & CONTROL
WIRING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3 UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/
ELECTRIC HEAT) FRONT VIEW. . . . . . . . . . . . 32
4 UNIT DIMENSIONS (3 - 6 TON COOLING/GAS
HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . 32
5 UNIT WITH ECONOMIZER RAINHOOD . . . . . . 33
6 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD. . . . . . . . . . . . . . . . . . . . . 33
7 UNIT DIMENSIONS (REAR VIEW). . . . . . . . . . . 34
8 DISCONNECT/BLOWER ACCESS LOCATION. 34
9 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . 35
10 FOUR AND SIX POINT LOADING . . . . . . . . . . . 36
11 ROOF CURB DIMENSIONS. . . . . . . . . . . . . . . . 37
Tbl. # Pg. #
LIST OF TABLES
1 SOUND POWER RATING . . . . . . . . . . . . . . . . . 11
2 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . 11
3 GAS HEAT RATINGS. . . . . . . . . . . . . . . . . . . . . 11
4 DM036 COOLING CAPACITIES (3 TON). . . . . . 12
5 DM048 COOLING CAPACITIES (4 TON). . . . . . 13
6 DM060 COOLING CAPACITIES (5 TON). . . . . . 14
7 DM072 COOLING CAPACITIES (6 TON). . . . . . 15
8 SUPPLY AIR BLOWER PERFORMANCE (3 TON
BELT DRIVE) - SIDE DUCT APPLICATION. . . . 16
9 SUPPLY AIR BLOWER PERFORMANCE (4 TON
BELT DRIVE) - SIDE DUCT APPLICATION. . . . 17
10 SUPPLY AIR BLOWER PERFORMANCE (5 TON
BELT DRIVE) - SIDE DUCT APPLICATION. . . . 18
11 SUPPLY AIR BLOWER PERFORMANCE (6 TON
BELT DRIVE) - SIDE DUCT APPLICATION. . . . 19
12 SUPPLY AIR BLOWER PERFORMANCE (3 - 6
TON DIRECT DRIVE) . . . . . . . . . . . . . . . . . . . . 20
13 BELT DRIVE MOTOR AND DRIVE DATA . . . . . 20
14 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . 21
15 ELECTRIC HEATER CFM LIMITATIONS. . . . . . 21
16 ELECT DATA - DM036 & 048 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 22
17 ELECT DATA - DM060 & 072 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 23
18 ELECTRICAL DATA - DM036 & 048 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 24
19 ELECTRICAL DATA - DM060 & 072 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 25
20 ELECTRICAL DATA - DM036 & 048 DIRECT
DRIVE WITH POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
21 ELECTRICAL DATA - DM060 & 072 DIRECT
DRIVE WITH POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
22 ELECTRICAL DATA - DM036 & 048 BELT DRIVE
WITH POWR’D CONVENIENCE OUTLET. . . . . 28
23 ELECTRICAL DATA - DM060 & 072 BELT DRIVE
WITH POWR’D CONVENIENCE OUTLET. . . . . 29
24 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . 30
25 ELECTRIC HEAT CORRECTION FACTORS . . 30
26 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . 30
27 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . 34
28 MINIMUM CLEARANCES. . . . . . . . . . . . . . . . . . 34
29 DM 4 POINT LOADS WEIGHT DISTRIBUTION. 36
30 DM 6 POINT LOADS WEIGHT DISTRIBUTION. 36
31 CENTER OF GRAVITY. . . . . . . . . . . . . . . . . . . . 36
32 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . 37
036-21502-002-A-0303
Unitary Products Group 3
PRODUCT NOMENCLATURE
3-6 Ton Sunline Model Number Nomenclature
D M N04
A2A
AA 1048
Product Catagory
D = Air Cond., Single Package
B = Heat Pump, Single Package
Product Identifier
M = R-22 Standard Efficiency (DCG/DCE)
F = R-22 Medium Efficiency (DEG/DEE)
H = R-22 High Efficiency (DHG/DHE)
Q = R-22 Std. Effic Heat Pump (BCH)
Airflow
A= Direct Drive
B = Direct Drive/Single Input Econo
D = Direct Drive/Motorized Damper
L = Direct Drive/BAS Ready Econ (No BAS Controller)/2" Pleated Filters/Extra xfrmr & circuit bkr.
N = Belt Drive
P = Belt Drive/Single Input Econo
R = Belt Drive/Motorized Damper
Y = Belt Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4, & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv Oultet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Additional Options
(See Next Page)
Product Generation
1 = First Generation
Voltage
1 = 208/230-1-60
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Nominal Cooling
Capacity - MBH
036 = 3 Ton
048 = 4 Ton
060 = 5 Ton
072 = 6 Ton
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
Gas Heat Options
N04 = 40 MBH Output Aluminized Steel (036)
N06 = 60 MBH Output Aluminized Steel (048)
N08 = 79 MBH Output Aluminized Steel (036,060,072)
N10 = 99 MBH Output Aluminized Steel (048,060,072)
S04 = 40 MBH Output Stainless Steel (036)
S06 = 60 MBH Output Stainless Steel (048)
S08 = 79 MBH Output Stainless Steel (036,060,072)
S10 = 99 MBH Output Stainless Steel (048,060,072)
Electric Heat Options
E05 = 5 kW Electric Heat
E07 = 7 kW Electric Heat
E10 = 10 kW Electric Heat
E15 = 15 kW Electric Heat
E20 = 20 kW Electric Heat
E30 = 30 kW Electric Heat
036-21502-002-A-0303
4 Unitary Products Group
PRODUCT NOMENCLATURE - Continued
3-6T Sunline Model Number Nomenclature
Additional Options
AA None
AB Phase Monitor
AC Coil Guard
AD Dirty Filter Switch
AE Phase Monitor & Coil Guard
AF Phase Monitor & Dirty Filter Switch
AG Coil Guard & Dirty Filter Switch
AH Phase Monitor, Coil Guard, & Dirty Filter Switch
AS Bottom Condensate Pan
BA Hinged Filter Door & Toolless Access Panels
BB Phase Monitor, Hinged Filter Door & Toolless Access Panels
BC Coil Guard, Hinged Filter Door & Toolless Access Panels
BD Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BE Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels
BF Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
CA CPC Controller with Dirty Filter Switch & Air Proving Switch
CB CPC Controller, DFS, APS & Phase Monitor
CC CPC Controller, DFS, APS & Coil Guard
CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE CPC Controller, DFS, APS & Technicoat Cond. Coil
CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil
CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
DA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
DB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
DD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
DF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DJ CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
DK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
DP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
036-21502-002-A-0303
Unitary Products Group 5
EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access
Panels
GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless
Access Panels
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Additional Options
036-21502-002-A-0303
6 Unitary Products Group
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
JB Johnson UNT Controller, DFS, APS & Phase Monitor
JC Johnson UNT Controller, DFS, APS & Coil Guard
JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC Novar ETC-3 Controller, DFS, APS & Coil Guard
ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
PD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
PF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
PK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
PP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
TA Technicoat Condenser Coil
TB Technicoat Condenser Coil & Phase Monitor
TC Technicoat Condenser Coil & Coil Guard
Additional Options
036-21502-002-A-0303
Unitary Products Group 7
TD Technicoat Condenser Coil & Dirty Filter Switch
TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard
TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ Technicoat Evaporator Coil
TK Technicoat Evaporator Coil & Phase Monitor
TL Technicoat Evaporator Coil & Coil Guard
TM Technicoat Evaporator Coil & Dirty Filter Switch
TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS Technicoat Evaporator & Condenser Coils
TT Technicoat Evaporator & Condenser Coils & Phase Monitor
TU Technicoat Evaporator & Condenser Coils & Coil Guard
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Additional Options
036-21502-002-A-0303
8 Unitary Products Group
FEATURES
All models are available with a wide variety of factory-
mounted options such as stainless steel heat exchangers,
phase monitor, dirty filter switch, and coil guard to make them
suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for over-
head rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. For bottom
duct, remove the sheet metal panels from the supply and
return air openings through the base of the unit. For horizon-
tal duct, remove the supply and return air panels on the rear
of the unit.
All models are available with these “factory mounted” outdoor
air damper options:
Single enthalpy economizer
Motorized outdoor air damper
Supply air blowers are equipped with either a direct drive or a
belt drive that can be adjusted to meet the exact require-
ments of the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system compo-
nents.
™ Controls - ™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully pro-
grammable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All units have long lasting powder paint cabinets with 750
hour salt spray test approval under ASTM-B117 procedures.
All models are CSA listed.
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
Gas Heat Operation - All gas heat units have a mini-
mum AFUE of 80%. Each section includes a durable
heat exchanger with aluminized steel or optional stain-
less steel tubes, a redundant gas valve, spark ignition,
power venting, an ignition module for 100% shut-off and
all of the safety controls required to meet the latest ANSI
standards.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uni-
form distribution of air across the heating elements.
Every element is fully protected against excessive tem-
perature by thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
BAS Controls - Yorks Sunline™ series units offer fac-
tory mounted BAS controls such as Novar, Honeywell,
Johnson, and CPC.
036-21502-002-A-0303
Unitary Products Group 9
FACTORY-INSTALLED OPTIONS
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
Technicoat 10-1
TM
processes. Coating is applied by total
immersion of the complete coil for maximum protection.
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
BAS - See “Additional Options” section in the product
nomenclature.
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
FIGURE 1: UNIT CUTAWAY
036-21502-002-A-0303
10 Unitary Products Group
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
STAINLESS STEEL HEAT EXCHANGER - For applica-
tions in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
NOTE:Knobs are shipped inside the unit to prevent ship-
ping damage. These must be field installed for
tool-less operation.
FIELD-INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the fin-
ished roof. These full perimeter curbs meet the require-
ments of the National Roofing Contractors Association
(NRCA) and are shipped knocked-down for field assem-
bly.
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
LOW NOX KIT- Required to reduce the emission of
nitrogen oxides below 40 nanograms per joule.
POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the condi-
tioned space from being over-pressurized during econo-
mizer operation.
The power exhaust option can only be used on bot-
tom duct configurations.
BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
CO
2
SENSOR - Senses CO
2
levels and automatically
overrides the economizer when levels rise above the
present limits.
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
036-21502-002-A-0303
Unitary Products Group 11
TABLE 1: SOUND POWER RATING
1
UNIT
SIZE
CFM
ESP BLOWER
SOUND POWER (db 10
-12
Watts)
Octave Band Centerline Frequency (Hz)
SWL
dB(A)
dB(A)
@
10Ft.
2
IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000
036 1,2000.6LOW0.6084847467696257527441
048 1,6000.55HIGH0.8085857568706358537542
060 2,0000.45HIGH1.0086867669716459547643
072 2,200 0.3 HIGH 1.35 87 87 77 70 72 65 60 55 77 44
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-
tee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
TABLE 2: CAPACITY RATINGS - (ARI 210/240)
1
1. 80/67°F Indoor and 95°F outdoor.
MODEL MBH
EER
2
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
SEER
3
3. SEER = Seasonal Energy Efficiency Ratio.
DM036
36.0 9.1 10.0
DM048 47.4 9.0 10.0
DM060 59.0 9.1 10.0
DM072 72.0 9.0 -
TABLE 3: GAS HEAT RATINGS
1
1. All units are single-stage heating.
MODEL
MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
DM036N04
DM036N08
50
100
40
79
80.9
80.5
15 - 45
40 - 70
DM048N06
DM048N10
75
125
59
99
80.9
80.3
25 - 55
45 - 75
DM060N08
DM060N10
100
125
79
99
80.5
80.3
25 - 55
35 - 65
DM072N08
DM072N10
100
125
79
99
80.5
80.3
25 - 55
35 - 65
036-21502-002-A-0303
12 Unitary Products Group
TABLE 4: DM036 COOLING CAPACITIES (3 TON)
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
72 45 3.1 35 30 26 21 17 - - 43 3.3 35 30 26 21 17 - -
67 43 3.0 43 38 34 29 25 20 16 41 3.3 41 38 34 29 25 21 16
62 39 3.0 39 39 39 34 30 25 21 36 3.3 36 36 36 32 27 23 18
57 40 2.9 40 40 40 35 31 26 22 38 3.2 38 38 38 33 29 24 20
72 44 3.1 31 28 24 20 16 - - 42 3.3 31 27 23 20 16 - -
67 41 3.0 39 35 31 27 23 19 16 39 3.3 37 35 31 27 23 19 15
62 38 3.0 38 38 37 33 29 25 21 36 3.3 36 36 35 31 27 23 19
57 39 2.9 39 39 39 35 31 27 23 37 3.2 37 37 36 32 28 25 21
72 42 3.1 28 25 22 18 15 - - 41 3.3 28 24 21 18 14 - -
67 40 3.0 35 32 28 25 22 18 15 38 3.2 34 31 28 25 21 18 15
62 36 3.0 36 36 35 31 28 25 21 35 3.3 35 35 34 30 27 24 20
57 37 2.9 37 37 37 34 31 27 24 36 3.2 36 36 35 32 28 25 22
72 41 3.1 26 23 20 17 14 - - 39 3.2 26 23 20 17 14 - -
67 38 3.0 32 30 27 24 21 18 15 37 3.2 32 29 26 23 20 17 14
62 35 3.0 35 35 33 30 27 24 21 33 3.2 33 33 31 28 25 22 20
57 36 2.9 36 36 35 32 29 26 23 34 3.2 34 34 32 30 27 24 21
72 39 3.1 24 21 19 16 14 - - 38 3.2 23 21 18 16 13 - -
67 37 3.0 30 27 25 22 20 17 15 36 3.2 29 26 24 21 19 16 14
62 34 3.0 34 33 30 28 25 23 20 32 3.2 32 31 29 26 24 21 19
57 34 2.9 34 34 33 30 27 25 22 33 3.1 33 33 30 27 25 22 20
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
72 41 3.7 34 29 25 20 16 - - 39 4.1 33 28 24 19 15 - -
67 38 3.7 38 37 33 28 24 19 15 36 4.0 36 36 32 27 23 18 14
62 34 3.7 34 34 34 30 25 21 16 32 4.0 32 32 32 27 23 18 14
57 35 3.6 35 35 35 31 26 22 17 33 4.0 33 33 33 28 24 19 15
72 40 3.7 30 26 23 19 15 - - 38 4.1 30 26 22 18 14 - -
67 37 3.6 36 34 30 26 22 18 14 35 4.0 34 33 29 25 21 17 13
62 33 3.7 33 33 33 29 25 21 17 31 4.0 31 31 31 27 23 19 15
57 34 3.6 34 34 34 30 26 22 18 32 4.0 32 32 32 28 24 20 16
72 39 3.7 27 24 20 17 14 - - 37 4.1 26 23 20 16 13 - -
67 36 3.6 34 30 27 24 20 17 14 34 4.0 33 30 26 23 20 16 13
62 32 3.6 32 32 32 29 25 22 19 30 4.0 30 30 30 27 24 20 17
57 33 3.6 33 33 33 29 26 23 19 31 3.9 31 31 31 27 24 21 17
72 37 3.6 25 22 19 16 13 - - 36 4.1 24 21 18 15 12 - -
67 35 3.6 31 28 25 22 19 16 13 32 4.0 30 27 24 21 18 15 12
62 31 3.6 31 31 29 27 24 21 18 29 4.0 29 29 28 25 22 19 16
57 32 3.5 32 32 30 27 24 21 18 30 3.9 30 29 28 25 22 19 16
72 36 3.6 22 20 17 15 12 - - 34 4.0 21 19 16 14 11 - -
67 33 3.6 28 25 23 20 18 15 13 31 4.0 27 24 22 19 17 14 11
62 30 3.6 30 29 27 24 22 19 17 28 4.0 28 28 25 22 20 17 15
57 31 3.5 31 30 28 25 22 20 17 28 3.9 28 28 25 23 20 17 15
NOMINAL RATING
900
1050
85°F
POWER
INPUT
2
kW
95°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
1750
1475
1200
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
1050
POWER
INPUT
2
kW
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F 115°F
SENSIBLE CAPACITY
1
SENSIBLE CAPACITY
1
900
TOTAL
CAP.
1
MBH
POWER
INPUT
2
kW
TOTAL
CAP.
1
MBH
TOTAL
CAP.
1
MBH
POWER
INPUT
2
kW
TOTAL
CAP.
1
MBH
1750
1475
1200
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
036-21502-002-A-0303
Unitary Products Group 13
TABLE 5: DM048 COOLING CAPACITIES (4 TON)
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
72 60 4.1 44 39 33 28 23 - - 60 4.5 44 39 33 28 23 - -
67 55 4.1 53 48 42 37 32 26 21 52 4.5 52 47 42 36 31 25 20
62 51 4.0 51 51 51 45 40 34 29 48 4.4 48 48 48 42 37 32 26
57 49 3.9 49 49 49 44 39 33 28 47 4.3 47 47 47 42 36 31 26
72 58 4.1 41 36 31 26 21 - - 57 4.5 41 36 31 26 21 - -
67 53 4.1 49 45 40 35 30 25 20 50 4.5 49 44 39 34 29 24 19
62 49 4.0 49 49 48 43 38 33 28 46 4.4 46 46 46 41 36 31 26
57 47 3.9 47 47 47 43 38 33 28 45 4.3 45 45 45 40 36 31 26
72 56 4.1 38 34 29 25 20 - - 55 4.6 38 33 29 24 20 - -
67 51 4.1 46 41 37 32 28 24 19 48 4.5 45 40 36 31 27 23 18
62 47 4.0 47 47 45 41 36 32 27 44 4.4 44 44 44 40 35 31 26
57 46 3.9 46 46 46 41 37 32 28 44 4.4 44 44 44 39 35 30 26
72 54 4.1 35 31 27 23 19 - - 53 4.5 35 31 27 23 19 - -
67 49 4.1 42 38 34 30 26 22 19 47 4.5 41 38 34 30 26 22 18
62 45 4.0 45 45 42 38 34 30 26 43 4.4 43 43 41 37 33 29 25
57 44 3.9 44 44 43 39 35 31 27 42 4.3 42 42 41 37 33 29 25
72 52 4.1 32 29 25 22 18 - - 51 4.5 32 28 25 21 18 - -
67 47 4.1 39 35 32 28 25 21 18 45 4.4 38 35 31 28 24 21 17
62 43 4.0 43 43 39 36 32 29 25 41 4.3 41 41 38 35 31 28 24
57 42 3.9 42 42 39 36 32 29 25 41 4.3 41 41 38 34 31 27 24
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
72 56 5.1 42 37 31 26 21 - - 53 5.6 40 35 29 24 19 - -
67 49 5.0 49 46 40 35 29 24 19 46 5.5 46 44 39 33 28 23 17
62 45 4.9 45 45 45 39 34 28 23 41 5.4 41 41 41 36 30 25 20
57 44 4.9 44 44 44 39 33 28 22 41 5.4 41 41 41 35 30 25 19
72 55 5.0 39 34 29 24 20 - - 52 5.5 38 33 28 23 18 - -
67 48 5.0 47 43 38 33 28 23 18 45 5.4 45 42 37 32 27 22 17
62 43 4.9 43 43 43 38 33 28 23 40 5.4 40 40 40 35 30 26 21
57 43 4.9 43 43 43 38 33 28 23 40 5.4 40 40 40 35 30 25 20
72 53 5.0 36 32 28 23 19 - - 51 5.5 35 31 26 22 17 - -
67 46 4.9 44 40 35 31 26 22 17 44 5.4 44 39 35 30 26 21 17
62 42 4.9 42 42 42 37 33 28 24 39 5.3 39 39 39 35 30 26 21
57 41 4.8 41 41 41 37 32 28 23 39 5.3 39 39 39 34 30 25 21
72 51 5.0 33 29 26 22 18 - - 48 5.5 32 28 24 20 16 - -
67 44 4.9 41 37 33 29 25 21 17 42 5.3 40 36 32 28 24 20 16
62 40 4.8 40 40 39 35 31 27 23 37 5.3 37 37 36 32 28 24 20
57 40 4.8 40 40 38 34 30 26 22 37 5.3 37 37 36 32 28 24 20
72 49 4.9 30 27 23 20 16 - - 46 5.4 29 26 22 19 15 - -
67 42 4.9 37 34 30 27 23 20 16 39 5.3 36 33 29 26 22 19 15
62 38 4.8 38 38 36 32 29 25 22 35 5.3 35 35 33 29 26 22 19
57 38 4.8 38 38 35 32 28 25 21 35 5.3 35 35 33 29 26 22 19
NOMINAL RATING
1200
1400
85°F
POWER
INPUT
2
kW
95°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
2000
1800
1600
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
1400
POWER
INPUT
2
kW
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F 115°F
SENSIBLE CAPACITY
1
SENSIBLE CAPACITY
1
1200
TOTAL
CAP.
1
MBH
POWER
INPUT
2
kW
TOTAL
CAP.
1
MBH
TOTAL
CAP.
1
MBH
POWER
INPUT
2
kW
TOTAL
CAP.
1
MBH
2000
1800
1600
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
036-21502-002-A-0303
14 Unitary Products Group
TABLE 6: DM060 COOLING CAPACITIES (5 TON)
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
72 68 4.9 50 44 38 32 25 - - 65 5.6 50 43 37 31 24 - -
67 62 4.8 62 56 50 43 37 31 24 60 5.3 60 54 48 42 35 29 23
62 57 4.7 57 57 57 51 44 38 32 53 5.3 53 53 53 47 41 34 28
57 55 4.7 55 55 55 48 42 36 29 51 5.4 51 51 51 44 38 32 25
72 67 4.9 48 42 36 30 24 - - 65 5.4 47 41 35 29 23 - -
67 62 4.8 59 53 47 41 35 30 24 59 5.2 57 51 45 40 34 28 22
62 56 4.7 56 56 56 50 45 39 33 53 5.2 53 53 53 47 41 35 29
57 54 4.7 54 54 54 48 42 36 31 50 5.3 50 50 50 44 39 33 27
72 66 4.9 45 39 34 29 23 - - 64 5.3 44 39 33 28 22 - -
67 61 4.8 55 50 44 39 34 28 23 58 5.1 54 48 43 38 32 27 22
62 55 4.7 55 55 55 50 45 39 34 52 5.1 52 52 52 47 42 36 31
57 53 4.6 53 53 53 48 42 37 32 50 5.2 50 50 50 44 39 34 28
72 63 4.8 41 36 31 27 22 - - 61 5.4 40 35 31 26 21 - -
67 58 4.7 51 46 41 36 32 27 22 56 5.1 49 44 39 35 30 25 21
62 53 4.6 53 53 51 47 42 37 32 50 5.2 50 50 48 43 39 34 29
57 51 4.6 51 51 49 44 40 35 30 47 5.2 47 47 46 41 36 32 27
72 60 4.8 37 33 29 25 21 - - 58 5.4 36 32 28 24 20 - -
67 56 4.7 46 42 38 34 30 26 21 53 5.2 44 40 36 32 28 24 20
62 51 4.6 51 51 47 43 39 35 31 47 5.2 47 47 44 40 36 32 27
57 49 4.6 49 49 45 41 37 33 29 45 5.3 45 45 42 38 34 29 25
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
72 61 6.1 48 41 35 29 22 - - 57 6.7 46 39 33 27 20 - -
67 55 5.9 55 52 46 39 33 27 20 50 6.6 50 50 43 37 31 24 18
62 49 5.9 49 49 49 42 36 30 23 44 6.5 44 44 44 38 31 25 19
57 47 5.9 47 47 47 40 34 28 21 42 6.5 42 42 42 36 30 23 17
72 61 6.0 45 39 33 28 22 - - 57 6.6 43 38 32 26 20 - -
67 54 5.9 53 49 44 38 32 26 20 50 6.5 50 47 42 36 30 24 18
62 48 5.8 48 48 48 42 37 31 25 44 6.4 44 44 44 38 32 26 20
57 46 5.8 46 46 46 40 35 29 23 42 6.4 42 42 42 36 31 25 19
72 60 6.0 42 37 32 26 21 - - 57 6.6 41 36 30 25 20 - -
67 54 5.8 52 47 41 36 31 25 20 50 6.5 50 45 40 34 29 24 18
62 48 5.7 48 48 48 43 37 32 27 44 6.4 44 44 44 38 33 28 22
57 46 5.8 46 46 46 41 35 30 25 42 6.3 42 42 42 37 32 26 21
72 57 6.0 38 34 29 24 19 - - 53 6.5 37 32 27 23 18 - -
67 51 5.8 47 42 38 33 28 24 19 46 6.4 45 41 36 31 26 22 17
62 45 5.7 45 45 44 39 34 30 25 41 6.3 41 41 39 35 30 25 21
57 43 5.8 43 43 42 37 32 28 23 39 6.3 39 39 38 33 29 24 19
72 54 6.0 34 30 26 22 18 - - 49 6.5 33 28 24 20 16 - -
67 48 5.8 42 38 34 30 26 22 18 43 6.4 40 36 32 28 24 20 16
62 43 5.7 43 43 39 35 31 27 23 38 6.3 38 38 35 31 27 23 19
57 41 5.8 41 41 38 34 30 26 21 37 6.2 37 37 34 30 26 22 18
NOMINAL RATING
1500
1750
85°F
POWER
INPUT
2
kW
95°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
2500
2250
2000
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
1750
POWER
INPUT
2
kW
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F 115°F
SENSIBLE CAPACITY
1
SENSIBLE CAPACITY
1
1500
TOTAL
CAP.
1
MBH
POWER
INPUT
2
kW
TOTAL
CAP.
1
MBH
TOTAL
CAP.
1
MBH
POWER
INPUT
2
kW
TOTAL
CAP.
1
MBH
2500
2250
2000
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
036-21502-002-A-0303
Unitary Products Group 15
TABLE 7: DM072 COOLING CAPACITIES (6 TON)
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
72 80 5.7 63 55 47 40 32 - - 77 6.3 63 55 47 40 32 - -
67 80 5.7 76 68 60 53 45 37 30 77 6.3 75 68 60 53 45 37 30
62 70 5.5 70 70 70 62 55 47 39 71 6.3 71 71 71 63 56 48 40
57 68 5.6 68 68 68 60 52 45 37 71 6.3 71 71 71 63 56 48 40
72 82 5.7 60 53 46 38 31 - - 76 6.3 60 53 46 39 31 - -
67 82 5.7 73 65 58 51 43 36 29 76 6.3 73 66 58 51 44 36 29
62 71 5.5 71 71 70 62 55 48 41 70 6.3 70 70 69 62 55 48 40
57 69 5.6 69 69 69 62 55 47 40 70 6.3 70 70 70 62 55 48 40
72 83 5.7 58 51 44 37 30 - - 75 6.3 58 51 44 37 30 - -
67 83 5.7 70 63 56 49 42 35 28 75 6.3 70 64 57 50 43 36 29
62 73 5.5 73 73 70 63 56 49 42 69 6.3 69 69 68 61 54 47 40
57 71 5.6 71 71 71 64 57 50 43 69 6.3 69 69 68 61 54 47 40
72 79 5.7 54 48 41 35 29 - - 73 6.3 53 47 41 35 29 - -
67 79 5.7 65 59 53 47 40 34 28 73 6.3 65 59 52 46 40 34 28
62 69 5.5 69 69 66 60 54 47 41 67 6.3 67 66 63 57 51 45 38
57 67 5.6 67 67 67 61 54 48 42 67 6.3 67 66 63 57 51 45 39
72 74 5.6 50 44 39 34 28 - - 71 6.3 49 43 38 33 27 - -
67 74 5.6 60 55 50 44 39 34 28 71 6.3 59 54 48 43 38 32 27
62 65 5.4 65 65 62 57 51 46 41 65 6.2 65 63 58 53 47 42 37
57 63 5.5 63 63 63 58 52 47 42 65 6.3 65 63 58 53 47 42 37
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
72 76 7.1 61 53 45 38 30 - - 75 7.9 59 51 43 36 28 - -
67 71 7.1 70 66 58 50 43 35 27 65 7.8 65 64 56 48 41 33 25
62 64 7.0 64 64 64 56 49 41 34 57 7.8 57 57 57 50 42 34 27
57 64 7.0 64 64 64 56 49 41 34 57 7.7 57 57 57 50 42 34 27
72 76 7.1 59 51 44 37 29 - - 76 7.9 57 49 42 35 27 - -
67 71 7.1 69 64 56 49 42 34 27 66 7.9 66 61 54 47 40 32 25
62 64 7.0 64 64 64 56 49 42 35 58 7.8 58 58 58 51 43 36 29
57 64 7.0 64 64 64 56 49 42 34 58 7.7 58 58 58 50 43 36 29
72 75 7.1 56 49 43 36 29 - - 76 8.0 55 48 41 34 27 - -
67 70 7.1 68 61 54 48 41 34 27 66 7.9 66 59 52 45 38 32 25
62 64 7.0 64 64 63 56 49 42 35 59 7.8 59 59 59 52 45 38 31
57 64 7.0 64 64 63 56 49 42 35 59 7.7 59 59 58 51 44 37 30
72 73 7.1 52 45 39 33 27 - - 73 7.9 50 44 37 31 25 - -
67 68 7.1 63 56 50 44 38 32 26 63 7.8 61 54 48 42 36 30 24
62 61 7.0 61 61 58 52 46 40 34 56 7.7 56 56 54 48 42 35 29
57 61 7.0 61 61 58 52 46 40 34 56 7.7 56 56 53 47 41 35 29
72 70 7.1 47 41 36 31 25 - - 69 7.8 45 40 34 29 23 - -
67 65 7.0 57 51 46 41 35 30 25 60 7.8 55 49 44 39 33 28 23
62 59 7.0 59 58 54 48 43 38 32 53 7.7 53 53 49 44 39 33 28
57 59 6.9 59 58 53 48 43 37 32 53 7.6 53 53 49 44 38 33 27
NOMINAL RATING
1800
2100
85°F
POWER
INPUT
2
kW
95°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
2700
2550
2400
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
2100
POWER
INPUT
2
kW
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F 115°F
SENSIBLE CAPACITY
1
SENSIBLE CAPACITY
1
1800
TOTAL
CAP.
1
MBH
POWER
INPUT
2
kW
TOTAL
CAP.
1
MBH
TOTAL
CAP.
1
MBH
POWER
INPUT
2
kW
TOTAL
CAP.
1
MBH
2700
2550
2400
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
036-21502-002-A-0303
16 Unitary Products Group
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1700 835 705 880 745 923 795 969 860 1013 970 ----
1600 811 655 854 695 898 740 942 790 986 840 1029 900 - -
1500 782 610 827 650 871 685 917 730 960 775 1003 825 1046 905
1400 - - 798 595 844 640 889 680 932 720 975 765 1018 790
1300 ----816590862635907675951715995750
1200 ------834585881630927665970705
1100 ------809550855590900625942665
1000 ------782510829545872858919625
900--------797500843540890580
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1700 --------------
1600 --------------
1500 --------------
1400 1055 875 ------------
1300 1036 780 1066 850 ----------
1200 1011 735 1047 765 1075 800 --------
1100 987 690 1028 720 1060 750 1084 775 ------
1000 963 655 1005 680 1040 695 1068 715 1089 735 ----
900 936 615 980 645 1020 660 1050 670 1053 680 1090 690 - -
036
1 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90 1.00 1.10 1.20 1.30 1.40 1.50
UNIT
SIZE
(MBH)
AIR
FLOW
CFM
036
1 2
UNIT
SIZE
(MBH)
AIR
FLOW
CFM
0.60 0.70 0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20 0.30 0.40 0.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.
036-21502-002-A-0303
Unitary Products Group 17
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235
1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170
1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100
1700 - - 802 670 840 745 881 815 920 900 961 970 1001 1030
1600 ----818665858740898820940890980950
1500 ------842695882755922835962895
1400 ------833650867705904765942820
1300 --------858665893725932785
1200 --------847640880680916730
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
2000 1103 1270 ------------
1900 1085 1210 ------------
1800 1064 1145 1102 1180 ----------
1700 1040 1075 1081 1115 1121 1140 --------
1600 1020 1005 1060 1050 1100 1085 --------
1500 1003 945 1044 995 1086 1035 --------
1400 982 880 1024 920 1067 965 1107 1000 ------
1300 970 835 1010 870 1053 920 1099 960 ------
1200 953 780 992 815 1034 855 1080 905 ------
0.60 0.70 0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20 0.30 0.40 0.50
UNIT
SIZE
(MBH)
AIR
FLOW
CFM
048
1 2
UNIT
SIZE
(MBH)
AIR
FLOW
CFM
048
1 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90 1.00 1.10 1.20 1.30 1.40 1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
036-21502-002-A-0303
18 Unitary Products Group
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720
2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640
2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535
2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 1440
2100 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 1340
2000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 1225
1900 ----8948859409409809801014 1020 1047 1095
1800 ----8558159038609509059889401022 970
1700 ------8848159258509648801001 910
1600 ------864770908805948835987870
1500 --------882740926780965830
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
2500 --------------
2400 1193 1665 ------------
2300 1170 1580 1202 1620 ----------
2200 1148 1480 1180 1530 ----------
2100 1121 1385 1155 1425 1190 1475 --------
2000 1100 1285 1133 1340 1169 1385 1205 1445 ------
1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 ----
1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 ----
1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 - -
1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150
1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110
060
1 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90 1.00 1.10 1.20 1.30 1.40 1.50
UNIT
SIZE
(MBH)
AIR
FLOW
CFM
060
1 2
UNIT
SIZE
(MBH)
AIR
FLOW
CFM
0.60 0.70 0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20 0.30 0.40 0.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
036-21502-002-A-0303
Unitary Products Group 19
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3200 1150 2325 1182 2425 1212 2525 --------
3000 1100 2010 1129 2090 1157 2150 1185 2225 1215 2290 1242 2360 - -
2800 1045 1700 1074 1780 1102 1850 1131 1940 1160 2025 1190 2075 1217 2130
2600 985 1425 1015 1475 1045 1540 1075 1630 1103 1715 1135 1760 1163 1825
2400 930 1240 958 1300 990 1350 1020 1400 1051 1430 1081 1490 1111 1600
2200 - - 905 1070 933 1160 965 1210 997 1250 1028 1285 1060 1325
2000 ------9191025 950 1100 982 1130 1014 1160
1800 --------9099259391005 968 1030
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3200 --------------
3000 --------------
2800 1245 2190 ------------
2600 1193 1920 1222 1990 1250 2060 --------
2400 1142 1675 1173 1730 1205 1800 1234 1885 ------
2200 1090 1380 1124 1450 1155 1550 1186 1640 1217 1710 1249 1775 - -
2000 1045 1175 1077 1200 1109 1275 1140 1360 1170 1460 1205 1545 1235 1600
1800 998 1050 1028 1060 1058 1060 1087 1075 1118 1150 1148 1250 1176 1360
0.60 0.70 0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20 0.30 0.40 0.50
UNIT
SIZE
(MBH)
AIR
FLOW
CFM
072
1 2
UNIT
SIZE
(MBH)
AIR
FLOW
CFM
072
1 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90 1.00 1.10 1.20 1.30 1.40 1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
036-21502-002-A-0303
20 Unitary Products Group
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON DIRECT DRIVE) - SIDE DUCT APPLICATION
CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS
HI
----1699 825 1650 785 1570 755
MED
1684 800 1631 780 1582 750 1524 720 1410 690
LOW
1487 710 1464 690 1421 670 1367 650 1315 620
HI
1996 960 1933 936 1868 910 1795 880 1722 845
MED
1804 838 1765 810 1714 785 1650 765 1589 735
LOW
1681 760 1640 738 1604 715 1541 695 1490 670
HI
2400 1155 2338 1125 2274 1095 2167 1045 2096 1010
MED
2290 1105 2214 1065 2145 1030 2071 990 1990 950
LOW
2150 1020 2100 990 2029 950 1965 910 1905 880
072
1
HI
2461 1480 2402 1440 2361 1395 2260 1350 2178 1305
CFM WATTS CFM WATTS CFM WATTS CFM WATTS
HI
1430 725 1360 700 1280 680 1180 655
MED
1324 650 1260 630 1185 610 1100 590
LOW
1246 605 1185 590 1110 570 1020 545
HI
1635 820 1544 790 1419 765 1300 740
MED
1508 705 1407 675 1306 645 1195 625
LOW
1416 645 1337 620 1230 595 1120 575
HI
1990 980 1887 945 1771 905 1629 855
MED
1911 920 1828 885 1724 835 1604 798
LOW
1816 838 1724 800 1644 770 1531 710
072
1
HI
2101 1260 2000 1205 1914 1155 1830 1110
036
1
048
1
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
2
0.900.80 1.00
036
1
048
1
060
1
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
2
060
1
0.600.20 0.30 0.40 0.50
UNIT SIZE
(MBH)
MOTOR SPEED
UNIT SIZE
(MBH)
MOTOR SPEED
1. Side Duct application (230/460/575 Volts)
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance
values
TABLE 13: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
MODEL
SIZE
BLOWER
RANGE
(RPM)
MOTOR
1
ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY
BELT
(NOTCHED)
HP FRAME
DESIG-
NATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIG-
NATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIG-
NATION
PITCH
LENGTH
(IN.)
QTY.
3 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1
4 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1
5 TON 850/1220 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK56 5.4 5.2 1 A36 37.3 1
6 TON 900/1250 1 1/2 56 1VL44 3.1-4.1 2.8-3.8 7/8 AK56 5.4 5.2 1 A36 37.3 1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located
in the moving air, upstream of any heating device.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40