Aerco B+10 User manual

Type
User manual
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
OMM-0063_0D
HE-110
USER MANUAL
Revised: 11/28/2018
Water Wizard
1B+ II
Water Heaters
SW1B+II Packaged Water Heater with
Pneumatically Controlled Valve (CXT-P)
Installation, Operation, and Maintenance
Covers all 1B+ II models
including units with
pneumatically controlled valve
(Type CXT-P) or with an
Electronic Control System (ECS)
and electronically controlled
valve (CXT-E):
B+03
B+04
B+05
B+06
B+07
B+08
B+09
B+10
B+11
B+12
B+13
B+14
B+15
Note: Number indicates number of
heating coils used (3 to 15).
SB-2006-02: ECS Retrofit Instructions
AC-105: Electronic Controls System (ECS) Manual
AC-103: Pneumatic Temperature Controller Manual
HE-110 1B+ II Water Wizard Water Heaters
OMM-0063_0D Installation, Operation & Maintenance Manual
Page 2 of 50 11/28/2018
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Disclaimer
The information contained in this manual is subject to change without notice from AERCO International,
Inc. AERCO makes no warranty of any kind with respect to this material, including but not limited to
implied warranties of merchantability and fitness for a particular application. AERCO International is not
liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in
connection with the furnishing, performance, or use of this material.
Technical Support:
(MonFri, 8am-5pm EST)
1-800-526-0288
www.aerco.com
1B+ II Water Wizard Water Heaters HE-110
Installation, Operation & Maintenance Manual OMM-0063_0D
11/28/2018 Page 3 of 50
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
TABLE OF CONTENTS
CHAPTER 1. SAFETY PRECAUTIONS ........................................................................................................................ 5
CHAPTER 2. GENERAL INFORMATION .................................................................................................................... 6
2.1. MODEL NAMES ........................................................................................................................................... 6
2.2. HEAT EXCHANGER CONFIGURATIONS ........................................................................................................ 6
2.3. ACCESSORIES .............................................................................................................................................. 6
2.4. ALL OTHER ITEMS ........................................................................................................................................ 7
CHAPTER 3. INSTALLATION .................................................................................................................................. 12
3.1. INSTALLING THE WATER WIZARD ............................................................................................................. 12
CHAPTER 4. PRINCIPLE OF OPERATION ................................................................................................................ 17
4.1. HEAT EXCHANGER OPERATION WITH PNEUMATIC CONTROL .................................................................. 17
4.2. HEAT EXCHANGER OPERATION WITH ELECTRONIC CONTROL SYSTEM (ECS) ........................................... 18
CHAPTER 5. OPERATING PROCEDURES ................................................................................................................ 19
CHAPTER 6. ROUTINE MAINTENANCE .................................................................................................................. 22
6.1. DRAINING THE HEATER ............................................................................................................................. 22
6.2. CHECKING THE DRAINED WATER .............................................................................................................. 22
6.3. CHECKING THE TEMPERATURE CONTROL ................................................................................................. 22
CHAPTER 7. TROUBLESHOOTING ......................................................................................................................... 23
CHAPTER 8. CORRECITVE MAINTENANCE ............................................................................................................ 24
CHAPTER 9. DE-SCALING BY THERMAL SHOCK METHOD ...................................................................................... 26
CHAPTER 10. MAINTENANCE DISASSEMBLY ........................................................................................................ 27
10.1. TOOLS AND EQUIPMENT .......................................................................................................................... 27
10.1.1. Common Tools and Equipment ....................................................................................................... 27
10.1.2. SPECIAL TOOLS AND EQUIPMENT REQUIRED: ................................................................................ 27
10.2. ISOLATING THE HEATER ............................................................................................................................ 29
10.3. DISCONNECTING THE HEATER FROM THE FACILITY .................................................................................. 30
10.4. ANTICIPATOR CHECK VALVE DISASSEMBLY .............................................................................................. 31
10.4.1. Special Tools Required..................................................................................................................... 31
10.5. PREPARING TO REMOVE THE HEATER SHELL ............................................................................................ 32
10.6. REMOVING THE HEATER SHELL ................................................................................................................. 33
10.7. REMOVING COILS AND RISERS .................................................................................................................. 33
CHAPTER 11. CLEANING AND INSPECTION ........................................................................................................... 34
10.8. PREPARATION OF BOTTOM HEAD ............................................................................................................ 34
10.9. PREPARATION OF RISER AND RETURN ...................................................................................................... 34
10.10. PREPARATION OF COIL ASSEMBLIES .................................................................................................... 35
10.11. PREPARATION OF COIL GASKETS .......................................................................................................... 37
CHAPTER 12. MAINTENANCE REASSEMBLY ......................................................................................................... 38
12.1. REASSEMBLY OF RISERS, SUB-COOLING COIL, AND STEAM COILS ............................................................ 38
12.1.1. Riser Installation ............................................................................................................................. 38
12.2. SUB-COOLING COIL INSTALLATION ........................................................................................................... 40
................................................................................................................................................................................ 40
12.3. STEAM COIL INSTALLATION ...................................................................................................................... 40
12.4. HYDROSTATICALLY TESTING COILS & RISERS ....................................................................................................... 42
12.5. ANTICIPATOR CHECK VALVE REASSEMBLY ........................................................................................................... 42
12.6. REASSEMBLY OF SHELL .................................................................................................................................... 43
12.7. REINSTALLING HEATER IN FACILITY .................................................................................................................... 43
12.8. STARTUP PROCEDURE ..................................................................................................................................... 43
HE-110 1B+ II Water Wizard Water Heaters
OMM-0063_0D Installation, Operation & Maintenance Manual
Page 4 of 50 11/28/2018
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
CHAPTER 13. RECOMMENDED SPARE PARTS ....................................................................................................... 44
1B+ II Water Wizard Water Heaters HE-110
Installation, Operation & Maintenance Manual OMM-0063_0D
11/28/2018 Page 5 of 50
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
CHAPTER 1. SAFETY PRECAUTIONS
Installing or operating personnel must, at all times, observe all safety regulations. The following warnings
are general and must be given the same attention as specific precautions included in the instructions.
WARNING
FLUIDS UNDER PRESSURE MAY CAUSE INJURY TO PERSONNEL OR
DAMAGE TO EQUIPMENT WHEN RELEASED.
SHUT OFF ALL INCOMING AND OUTGOING STEAM AND HOT WATER STOP VALVES AND
CAREFULLY DECREASE ALL TRAPPED TRESSURES TO ZERO (see SHUTDOWN IN
OPERATERING PROCEDURES) BEFORE PERFORMING ANY MAINTENANCE.
WARNING
LIVE STEAM CAN CAUSE SEVERE BURNS.
NEVER SEARCH FOR LEAKAGE IN A LIVE STEAM LINE BY SIGHT ALONE OR BY “FEEL.” USE A
MIRROR OR OTHER SUITIBLE POLISHED OBJECT. ALSO, ALWAYS WEAR GLOVES AND LONG
SLEEVES.
! !
! !
HE-110 1B+ II Water Wizard Water Heaters
OMM-0063_0D Installation, Operation & Maintenance Manual
Page 6 of 50 11/28/2018
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
CHAPTER 2. GENERAL INFORMATION
This instruction covers the AERCO Helitherm Model B+ WATER WIZARD Steam to Water
Heat Exchangers. STEAM is the PRIMARY or TUBE SIDE FLUID. The WATER BEING
HEATED is the Heat Exchanger (service or domestic water or other fluid) is the SECONDARY
or SHELL SIDE FLUID.
2.1. MODEL NAMES
The number of coils in a particular Heat Exchanger is denoted by the two digits following the
“B+” in the Heat Exchanger Model Number. That is: B+03 = 3 coils, B=07 = 7 coils, B+11 = 11
coils, and B+15 = 15 coils.
The Style designation for a Heat Exchanger denotes materials of construction for the various
components of the assembly. If this information is required for a specific Heat Exchanger,
contact the nearest AERCO Sales Representative.
2.2. HEAT EXCHANGER CONFIGURATIONS
There are three basic heat exchanger configurations; those with a pneumatically controlled
valve (CXT-P), those with Electronic Control System (ECS) with an electronically controlled
valve (CXT-E), and a “bare” heat exchanger without controls or valve. See separate ECS
Controls manual, AC-105, for information about the Electronic controls System and
electronically operated CXT-E valve. See Section 3 for available accessories.
2.3. ACCESSORIES
Accessories included in the AERCO B+ Heater Package Assembly (See Figures 1a, 1b, 1c,
21, 22, and 23) include:
Steam Flow Control Valve either Air-Operated or Self-Contained as ordered and
furnished, sized as required for the service.
Temperature Controller installed in the Control Box when an Air Operated Control Valve is
furnished (See Fig. 20, Item 134).
Over-Temperature Limit System, including the following:
Temperature Switch installed in the Control Box (Figure 20, Item 126).
Solenoid Valves:
o Water installed in the Heater Top Head.
o Air installed in the Control Box when an Air Operated Control Valve is furnished
(Fig. 20, Item 135).
o Steam installed on the Self-Contained Control Valve when such valve is furnished.
o Indicator Lights: “Power On” and “Tripped” installed in the Control Box (Figure 20,
Items 129 and 130).
Steam Compound Pressure Gage mounted below the Control Box (Figure 20, Item 133).
Shell Hot Water Outlet Temperature Gage mounted below the Control Box (Figure 20,
Item 132).
1B+ II Water Wizard Water Heaters HE-110
Installation, Operation & Maintenance Manual OMM-0063_0D
11/28/2018 Page 7 of 50
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Pressure & Temperature Relief Valves size and number furnished as required in
accordance with the design BTU output of the heater first two located in the heater Top
Head as shown in Figure 1a, 1b, 1c, and 1d. The third, if furnished, to be installed in the hot
water outlet piping by the user as shown in Figure 2.
Union Orifice located in the Condensate Outlet (Figure 12, Item 55) required in place of
a steam trap to ensure complete condensation of the steam within the heater.
Check Valve located in the Condensate Outlet (Figure 12, Item 53).
2.4. ALL OTHER ITEMS
Stop valves, check valves, strainers, unions or flanges, and other piping and fittings as shown in
Figures 3 through 6 are to be furnished by USER.
NOTE:
This instruction covers only the heat exchanger portion of the model B+
packaged heater assembly. Separate instructions are included in this package
covering steam control valve, the over-temperature limit system and its
components, and other accessories included in the heater package.
NOTE:
The AERCO Helitherm heat exchanger carries the standard AERCO warranty
against defective material and workmanship. However, AERCO cannot honor its
warranty if the installer or user deviates in any way from the instructions and
precautions included herein and/or make any alteration of the equipment from
that furnished without the written approval of AERCO.
HE-110 1B+ II Water Wizard Water Heaters
OMM-0063_0D Installation, Operation & Maintenance Manual
Page 8 of 50 11/28/2018
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Figure 1a – Dimensions for AERCO Helitherm Heat Exchanger (Packaged Water Heater),
Model Water Wizard SW1B+II with Pneumatic CXT-P Valve
Chapter 2
General Information
1B+ II Water Wizard Water Heaters HE-110
Installation, Operation & Maintenance Manual OMM-0063_0D
11/28/2018 Page 9 of 50
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Figure 1b Dimensions for AERCO Helitherm Heat Exchanger (Packaged Water Heater),
Model Water Wizard SW1B+II with Bronze Heads, ECS, and CTX-E Valve
HE-110 1B+ II Water Wizard Water Heaters
OMM-0063_0D Installation, Operation & Maintenance Manual
Page 10 of 50 11/28/2018
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Figure 1cDimensions for AERCO Helitherm Heat Exchanger (Packaged Water Heater),
Model Water Wizard SW1B+II with Stainless Steel Heads, ECS, and CTX-E Valve
1B+ II Water Wizard Water Heaters HE-110
Installation, Operation & Maintenance Manual OMM-0063_0D
11/28/2018 Page 11 of 50
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Figure 1d – Dimensions for AERCO Bare Helitherm Replacement Heat Exchanger for
Model Water Wizard SW1B+II
Chapter 3
Installation
HE-110 1B+ II Water Wizard Water Heaters
OMM-0063_0D Installation, Operation & Maintenance Manual
Page 12 of 50 11/28/2018
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
CHAPTER 3. INSTALLATION
3.1. INSTALLING THE WATER WIZARD
To install the Water Wizard SW1B+II water Heater, follow the steps below:
Installing the Water Wizard Heater Instructions
1) Dimensions for three versions of AERCO Model SW1B+II are shown in Figures 1a, 1b, and
1c.
2) Uncrate the Heater carefully. Set the Heater upright by using a block and tackle or hoist
attached to the lifting lug on the top of the Heater (the eye-bolts shown in Figure 15). Always
use the lifting lugs to lift and/or move the Heater.
3) If possible, for easy in-place maintenance, locate the Heater where there is at least 2 feet
clearance all around the Heater and where the head room clearance from the top of
dimension B in Figure 1 is at least equal to dimension A for the Heater Model, less 24
inches.
4) It is suggested that the Heater stand assembly be secured to the floor, however, any other
means for securing the Heater may be used. If piping is used to secure the Heater, the
piping must include ample provision for expansion.
5) Make all piping connections as instructed in Step 6 below and per the appropriate Figures
shown:
a) Single Heater Figure 3
b) Parallel Heaters Figure 4
c) Single Heater used with an Accumulator Figure 5
d) Single Heater used with a Stratified Storage Tank Figure 6
or with any specific piping diagram which may have been furnished by AERCO for this
installation.
6) For the best Heater performance, OBSERVE THE FOLLOWING VERY CAREFULLY in
making the piping installation:
a) Do not use cement or red lead in making up pipe joints
b) For Heater connection types, sizes, and exact locations, see Figure 1.
c) All piping to the Heater top head should be provide with unions or flanges which are
LOCATED BEYOND THE OUTSIDE DIAMETER OF THE HEATER HEAD to permit
removal of the head and shell for in-place maintenance.
d) Include all of the stop valves, check valves, steam traps, and other elements in the
piping as shown in Figure 3, 4, 5, or 6, or as separately specified by AERCO. Note
that the check valve shown at the Heater in the Condensate return line is furnished in
the piping package assembly by AERCO.
e) The Condensate return piping MUST be arranged to permit Condensate to drain
freely by gravity from the Heater Bottom Head. Failure to do so may result in
improper Heater operation and/or in damage to the Heater Steam/Condensate
system.
(Continued)
1B+ II Water Wizard Water Heaters HE-110
Installation, Operation & Maintenance Manual OMM-0063_0D
11/28/2018 Page 13 of 50
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Installing the Water Wizard Heater Instructions (Cont.)
f) All drain discharges relief valve(s) in the Top Head of the Heater, outlet of the
Water Solenoid Valve in the top head of the Heater, and Drain Valve in the Bottom
Head of the Heater should be piped directly to a convenient floor drain.
7) When a third P&T Relief Valve is furnished with the Heater (the first two furnished have
been assembled in the top head of the Heater by AERCO), the third Valve is to be installed
in the Heater hot water outlet piping, by the user, as illustrated in Figure 2.
8) Before making final piping connections to and from the Heater and Control Valve, blow out
all piping thoroughly.
9) If an air-operated Control Valve is furnished in the Heater package, make the necessary
supply air connection to the connector through the side of the Control Box (see Figure 20,
Item 136). The supply air pressure must be maintained at 20 PSIG.
10) Connect 110 volt 60 Hz power supply wiring through the side of the Control Box to the
electrical Junction Box (see Figure 20, Item 127).
Figure 2 P&T Relief Valve Located in the Heater Hot Water Outlet Piping
HE-110 1B+ II Water Wizard Water Heaters
OMM-0063_0D Installation, Operation & Maintenance Manual
Page 14 of 50 11/28/2018
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Figure 3 Piping Connections for a Single Heater
1B+ II Water Wizard Water Heaters HE-110
Installation, Operation & Maintenance Manual OMM-0063_0D
11/28/2018 Page 15 of 50
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Figure 4 – Piping Connections for Parallel Heaters
HE-110 1B+ II Water Wizard Water Heaters
OMM-0063_0D Installation, Operation & Maintenance Manual
Page 16 of 50 11/28/2018
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Figure 5 Piping Connections for a Single Heater used with an Accumulator
Figure 6 Piping Connections for a Single Heater used with a Stratified Storage Tank
Chapter 4
Principal of Operation
HE-110 1B+ II Water Wizard Water Heaters
OMM-0063_0B Installation, Operation & Maintenance Manual
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
CHAPTER 4. PRINCIPLE OF OPERATION
The AERCO Helitherm Heat Exchanger (Heater) consists of three parts (see Figure 7);
1. Shell with Top and Bottom Heads
2. Coils assembled to Steam Riser and Condensate Return
3. Integral Demand Anticipator Temperature Control Unit
Cold Water (or other liquid) enters the heater through the inlet connection and Orifice in the
Bottom Head and strikes the Deflector. The Orifice serves to divert some Cold Water into the
Shut Tube, whereas the Deflector disperses the incoming Cold Water evenly into the bottom of
the Shell. The Cold Water in the Shell, then, flow upward among the Coils (heating surfaces)
and, heated, is discharged through the Check Valve and Hot Water Outlet Connection in the
Top Head.
Steam enters through the Control Valve and the Steam inlet connection in the Heater Bottom
and is fed through the Steam Riser to the inlet of each Heat Exchanger Coil unit as shown in
Figure 7. The Steam flows through these Coils units simultaneously in parallel and enters the
Condensate Return as Condensate. The Condensate is fed through the Sub-Cooling Coil unit
and leaves the Heater through the Condensate outlet connection in the Bottom Head of the
Heater. The Sub-Cooling Coil unit is included in the assembly to provide the maximum possible
condensing of the Steam, thus providing the greatest amount of heat transfer, the lowest
Condensate outlet temperature, and the greatest reduction in energy loss from flash steam.
As noted above, the Cold Water being heated flows through the Heater from bottom to top. In
addition, Heater Water, being of less density than Cold Water, migrates to the top of the Shell
by convection. These actions result in the hottest Water always being at the top of the Heater
at the Heater outlet and at the How Water inlet to the Anticipator Temperature Sensing Tube
See Figure 7.
Hot Water from the top of the Heater Shell enters the open end of the Sensing Tube and Cold
Water enters the Sensing Tube from the Shunt Tube at a rate proportional to the load (call for
Hot Water) on the Heater. The mixture of Hot and Cold Water in the Sensing Tube creates an
average temperature which necessarily will be cooler than the temperature of the Hot Water in
the top of the Heater Shell.
4.1. HEAT EXCHANGER OPERATION WITH PNEUMATIC CONTROL
The Temperature Sensing Element “reads” the average temperature of the Water in the
Sensing Tube at any given moment and signals the Water in the Sensing Tube at any given
moment and signals the Steam Control Valve to modulate between full open or closed as
necessary to maintain the required Heater Hot Water outlet temperature. With no demand or
load on the Heater, the Temperature Sensing Element reads only the temperature of the Water
in the top of the Heater and at the Heater outlet. If that Water is at the required outlet
temperature or above, the Sensing Element signals the Steam Control Valve to close.
However, the moment that there is a demand for Hot Water, Cold Water flows from the Shunt
Tube to mix with the Hot Water I the Sensing Tube, cooling the Sensing Element so that is
signals the Steam Control Valve to open. The need for Steam (heat) to the Coils is satisfied at
once, the incoming Cold Water passing over the Coils is heated, and the Hot Water outlet
temperature does not fall below that required.
The Demand Anticipator Temperature Control Unit, as its name implies, is constantly alert to
lead conditions and changes, as well as to changes in the temperature of the incoming Cold
Water, and provides FEED-FORWARD temperature control at all times.
HE-110 1B+ II Water Wizard Water Heaters
OMM-0063_0D Installation, Operation & Maintenance Manual
Page 18 of 50 11/28/2018
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Figure 7 Schematic of AERCO Model B+II Water Heater showing Anticipator
Temperature Control
4.2. HEAT EXCHANGER OPERATION WITH ELECTRONIC CONTROL SYSTEM
(ECS)
The Electronic Control System (ECS) available for the Water Wizard SW1B+II offers
features and functions not described in this manual. Refer to the separate manual, AC-
105, for detailed descriptions of the function and operation of the ECS and electronically
operated valve, type CXT-E.
1B+ II Water Wizard Water Heaters HE-110
Installation, Operation & Maintenance Manual OMM-0063_0D
11/28/2018 Page 19 of 50
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
CHAPTER 5. OPERATING PROCEDURES
Water Wizard Operating Procedure Instructions
1) With the installation entirely completed, including:
1) All piping connections have been made,
2) All connecting piping has been cleaned (blown) out,
3) All connections per Steps 8 and 9 under INSTALLATION have been made,
Open the stop valve in the Cold Water inlet line and hold the relief valve (or any one of the
relief valves) in the Heater top head open to allow air to come out (otherwise an air pocket
will be built up and the Heater will not fill). When water flows out of the relief valve, the
Heater is full.
2) Temporarily set the Over-Temperature Limit System Temperature Switch in the Control Box
(Figure 20, Item 126) to its high temperature limit.
3) If the Steam Control Valve furnished is air operated and there is a Temperature Controller in
the Control Box (see Figure 8), set the Controller at the temperature desired to be held at
the Heater Hot Water outlet.
4) Open the stop valve in the Hot Water outlet line. Open a Hot Water faucet or faucets in the
building or process to insure a flow of water through the heater. For best results in adjusting
the temperature control, a water flow of 10% to 25% of heater rating is desirable. Slowly
open all stop valves in the Steam inlet and condensate outlet lines.
5) Slowly open all stop valves in the Steam inlet and Condensate outlet lines.
6) Follow the instructions furnished with the air-operated Temperature Controller and Control
Valve or with self-contained Temperature Regulator Valve, and:
a) Introduce Steam to the Heater.
b) Adjust the air-operated Temperature Controller OR self-contained Temperature
Regulator Valve until the Heater hot water outlet temperature is being held steady at
the desired temperature. If the hot water outlet temperature is erratic, see Step 7
below.
c) Close the hot water faucet or faucets opened in Step 4.
7) Open any stop valves in the building recirculation system if such is included in the Heater
installation.
8) If the hot water outlet temperature is erratic especially during load changes:
a) Put a load on the Heater, by opening a hot water faucet or faucets in the building or
process, as quickly as possible.
b) Adjust the Temperature Controller of Temperature Regulator to provide best
response on load changes. See the instruction furnished with the Controller or
Regulator.
9) Adjust the Over-Temperature Limit System Temperature Switch in the Control Box to its
proper setting in accordance with the instructions furnished which cover the Over-
Temperature Limit System usually 15°F to 20°F higher than the desired hot water outlet
temperature.
(Continued)
HE-110 1B+ II Water Wizard Water Heaters
OMM-0063_0D Installation, Operation & Maintenance Manual
Page 20 of 50 11/28/2018
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913
Phone: 800-526-0288
Water Wizard Operating Procedure Instructions (Cont.)
10) The Heater installation is now set for operation. No further operation procedure is
necessary unless or until further temperature control adjustments may be required. If so,
repeat Steps 4, 5, 6, 7, and, if necessary, Step 8.
11) To SHUT DOWN the System:
a) Close all stop valves in the Steam inlet and Condensate outlet lines.
b) In this order, close the stop valves in
i. the hot water outlet line,
ii. the recirculation line, if any, and
iii. the cold water inlet line (see Step 11c, which follows).
c) If the system includes an accumulator or stratified storage tank, DO NOT SHUT OFF
THE COLD WATER UNTIL THE HEATER HAS COOLED DOWN. If the system is
allowed to cool while the cold water is shut off, the Heater liner may collapse
because of formation a vacuum in the Heater.
12) For DRAINING THE HEATER, see the instruction included under ROUTINE
MAINTENANCE, Chapter 6, Section 6.1.
13) To START UP again, with the shell filled per Step 1 above, open the stop valves in the
following order:
1) stop valve in the Cold Water inlet line,
2) any stop valve in the recirculation line, if any,
3) stop valve in the Hot Water outlet line, and
4) stop valves in the Steam inlet line and Condensate outlet lines.
14) After each startup, check the temperature control. If necessary, make adjustments per
Steps 4 through 9.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50

Aerco B+10 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI