Anderson Greenwood Tank blanketing regulators IOM Owner's manual

Type
Owner's manual

Anderson Greenwood Tank blanketing regulators IOM are designed to provide precise and reliable control of tank blanketing gas pressure in various industrial applications. These regulators feature a rugged construction, ensuring durability and longevity in demanding environments.

Key capabilities of Anderson Greenwood Tank blanketing regulators IOM:

  • Accurate pressure regulation for optimal tank blanketing
  • Remote pressure sensing for stable operation
  • Wide range of models to suit different flow and pressure requirements
  • Easy installation and maintenance
  • Compliance with industry standards for safety and performance

Anderson Greenwood Tank blanketing regulators IOM are designed to provide precise and reliable control of tank blanketing gas pressure in various industrial applications. These regulators feature a rugged construction, ensuring durability and longevity in demanding environments.

Key capabilities of Anderson Greenwood Tank blanketing regulators IOM:

  • Accurate pressure regulation for optimal tank blanketing
  • Remote pressure sensing for stable operation
  • Wide range of models to suit different flow and pressure requirements
  • Easy installation and maintenance
  • Compliance with industry standards for safety and performance
ANDERSON GREENWOOD TANK BLANKETING REGULATORS
InstallatIon and operatIonal safety InstructIons
© 2017 Emerson. All Rights Reserved.
3 INSTALLATION
(See applicable figure)
Many regulators are damaged when first
placed in service because of failure to clean
the connection properly when installed.
Before installation, flange faces or threaded
connections on both the regulator and the
vessel and/or line on which the regulator is
mounted must be thoroughly cleaned of all dirt
and foreign material.
Because foreign materials that pass into and
through regulators can be damaging, the
systems on which the regulator are tested and
finally installed must also be inspected and
cleaned. New systems in particular are prone
to contain foreign objects that inadvertently get
trapped during construction and will destroy
the seating surface when the regulator opens.
The system should be thoroughly cleaned
before the regulator is installed.
The gaskets used must be dimensionally
correct for the specific flanges. The inside
diameters must fully clear the regulator inlet,
outlet, and sense openings so that the gasket
does not restrict flow.
For flanged regulator, draw down all
connection studs or bolts evenly to avoid
possible distortion of the regulator body.
For threaded regulators, use flats on the body
to aid in installation. Use a back-up wrench
when necessary.
1 GENERAL
The intent of these instructions is to acquaint
the user with the storage, installation and
operation of this product.
This regulator should only be used in
accordance with the applicable operating
instructions and within the application
specifications of the purchase order.
These regulators have been tested at the
factory and should be adjusted on site. Contact
the factory or a Emerson Valves and Controls
authorized representative for any questions.
2 STORAGE AND HANDLING
Because cleanliness is essential to the
satisfactory operation and tightness of a
regulator, precautions should be taken during
storage to keep out all foreign materials.
Inlet, outlet, and sense line protectors should
remain in place until the regulator is ready
to be installed in the system. Take care to
keep the regulator inlet absolutely clean. It is
recommended that the regulator be stored
indoors in the original shipping container away
from dirt and other forms of contamination.
Before installation these instructions must be fully read and understood
4 ADJUSTMENT
Remove the cap and back off the pressure
adjustment screw to a no set pressure position
(blanketing valve closed) and pressurize the
regulator. If block valves are installed, pressurize
the blanketing valve by opening the block valves
in the following sequence, B3 (sense) first, B2
(inlet) next, then B4 (gauge) and B1 (outlet)
last. Slowly adjust the set pressure adjustment
screw to obtain the desired tank blanket gas
pressure. Clockwise rotation of the pressure
adjustment screw increases tank pressure. The
recommended set pressure range is stamped
on the regulator nameplate. Adjusting the set
pressure higher than the nameplate limit could
prevent the blanketing regulator from closing
Regulators are intended to open and close
within a narrow pressure range. Regulator
installations require accurate design both as
to inlet, discharge, and sense piping. Refer to
International, National and Industry Standards
for guidelines.
Emerson.com/FinalControl VCIOM-01064-EN 18/06
Regulators must be handled carefully and
never subjected to shocks. Rough handling may
alter the pressure setting, deform regulator
parts and adversely affect seat tightness and
regulator performance.
The regulator should never be lifted or handled
using the tubing. When it is necessary to use a
hoist, use the lifting eye(s) on the main regulator
body. If there are no lifting eyes, a chain or sling
should be placed around the main regulator
body in a manner that will insure that the
regulator is in a position to facilitate installation.
TABLE OF CONTENTS
1. General ........................................................... 1
2. Storage and handling .................................... 1
3. Installation ..................................................... 1
4. Adjustment .................................................... 1
5. Inlet piping ..................................................... 2
6. Discharge piping............................................ 2
7. Remote pressure .......................................... 2
8. Safety precautions ......................................... 3
2
G1
G1
ANDERSON GREENWOOD TANK BLANKETING REGULATORS
InstallatIon and operatIonal safety InstructIons
FIGURE 2: Y-1
FIGURE 1: BV-1
5 INLET PIPING
The regulator inlet should be mounted
horizontally directly on a short connection
fitting to the blanketing gas source. This
connection should be unobstructed, and the
regulator should never be installed on a fitting
having a smaller inside diameter than the inlet
connection of the regulator. If a block valve is
used, it should be a full port type valve sufficient
size to not restrict flow through the regulator.
6 DISCHARGE PIPING
The regulator outlet should be mounted as
close as possible to the vessel.
Discharge piping should be simple and direct.
All discharge piping should be run as direct as
is practicable to the point of final release for
blanketing.
The regulator should be properly be supported
to withstand any swaying or system vibrations.
Fittings or pipe having a smaller inside
diameter than the valve outlet connections
must not be used. If a block valve is installed, it
should be a full port type valve sufficient size to
not restrict flow through the regulator.
Pressure
gauge
Tank
Blanket gas
Sense line
1” Sense line
B4
Optional
B3
Optional
B3
Optional
B1
Optional
B1
Optional
B2
Optional
B2
Optional
Cap
Cap
Flow
Flow
Flow
FIGURE 3: RA
Blanket gas
1” Sense line
Pressure adjustment
B3
Optional
B1
Optional
B2
Optional
Blanket gas supply
Flow
7 REMOTE PRESSURE
In these regulators, remote pressure sensing
is standard. The remote sense port is marked
“SENSE”. Remove the plug and connect the
remote sense line to this port. The sense line
must be connected to the tank properly away
from discharge piping penetration for stable
operation and must be minimum 1” pipe size.
Insure that the pilot sensing port is within the
system protected by the regulator.
A block valve for shut off in the remote sense
line is optional to facilitate maintenance.
However a closed block valve in the remote
sense line renders the regulator inoperative.
3
WARNING!
This product is a safety related component intended
for use in critical applications. The improper
application, installation or maintenance of the
regulator or the use of parts or components not
manufactured by Emerson may result in a failure of
the regulator.
Any obstruction due to polymerization, solidification
or solid deposit will affect the safety performance
of this regulator. Methods to reduce such risk
should be taken.
Any installation, maintenance, adjustment, repair
or test, performed on the regulator must be
done in accordance with the requirements of all
applicable Emerson Procedures and Instructions.
The information, specifications and technical data
(the “Specifications”) contained in this document
are subject to change without notice. Emerson
does not warrant that the specifications are
current and assumes no responsibility for the
use or misuse thereof. The purchaser should
verify that there have been no changes to the
specifications prior to use.
ANDERSON GREENWOOD TANK BLANKETING REGULATORS
InstallatIon and operatIonal safety InstructIons
8 SAFETY PRECAUTIONS
Always wear proper safety gear to protect
head, eyes, ears, etc. anytime you are near
pressurized regulators.
Never attempt to remove the regulator from a
system that is pressurized.
Never perform maintenance on the regulator
while in service unless the regulator is isolated
from the system pressure. If not properly isolated
from the system pressure, the regulator may
inadvertently open resulting in serious injury.
Remove the regulator prior to performing any
pressure testing of the system.
The safety of lives and property often depends
on the proper operation of the regulator.
The regulator must be maintained according
to appropriate instructions and must be
periodically tested and reconditioned to ensure
correct function.
For further information including adjustment,
maintenance, cleaning lapping and detail
illustrations, obtain the appropriate
Operation and Maintenance Manual from
the following table. These manuals may be
requested from the factory or are available at
Emerson.com/FinalControl
Regulator model Operation and maintenance manual
BV-1 Tank blanketing - pilot operated type 05.9040.252
Y-1 Tank blanketing - pilot operated type 05.9040.176
RA Tank blanketing - direct spring operated type 05.9040.176
Service technicians are available to assist with your installation or other field problems. Call your
nearest Emerson Valves and Controls representative or our factory at the addresses below.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Anderson Greenwood is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation
Solutions, Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by
our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without
notice.
Emerson.com/FinalControl
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Anderson Greenwood Tank blanketing regulators IOM Owner's manual

Type
Owner's manual

Anderson Greenwood Tank blanketing regulators IOM are designed to provide precise and reliable control of tank blanketing gas pressure in various industrial applications. These regulators feature a rugged construction, ensuring durability and longevity in demanding environments.

Key capabilities of Anderson Greenwood Tank blanketing regulators IOM:

  • Accurate pressure regulation for optimal tank blanketing
  • Remote pressure sensing for stable operation
  • Wide range of models to suit different flow and pressure requirements
  • Easy installation and maintenance
  • Compliance with industry standards for safety and performance