Generac 15kW RD01523ADAS User manual

  • Hello! I am an AI chatbot trained to assist you with the Generac 15kW RD01523ADAS User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
  • What is the minimum recommended concrete pad size for the installation of the generator?
    What are the lifting provisions for the generator?
    What is the overall height of the generator?
    What is the overall width of the generator?
    What is the overall length of the generator?
    What is the total fuel tank capacity?
    What is the usable fuel tank capacity?
4 3 2 1
4 3 1
A
B
A
B
302
[11.9]
1954 [76.9]
OVERALL LENGTH
182
[7.2]
1408
[55.4]
OVERALL
HEIGHT
888 [35.0]
OVERALL WIDTH
758 [29.8]
DOOR TYP
173 [6.8]
146 [5.8]
1322 [52.0]
892 [35.1]
CENTER OF GRAVITY
SEE NOTE 5
SERVICE ITEM 3.4L
OIL FILL CAP RIGHT SIDE
OIL DIP STICK RIGHT SIDE
OIL FILTER RIGHT SIDE
OIL DRAIN HOSE RIGHT SIDE
RADIATOR DRAIN HOSE LEFT SIDE
AIR CLEANER ELEMENT RIGHT SIDE
MUFFLER FRONT
FAN BELT EITHER SIDE
BATTERY LEFT SIDE
WEIGHT DATA WITH EMPTY BASETANK
(SEE NOTE 5)
GENERATOR AS SHOWN (STEEL ENCL) 886 [1953]
WITH WOODEN SHIPPING SKID 925 [2039]
TITLE
INSTALL CPL PROT D3.4L SW
ISSUE DATE:
SIZE CAGE NO DWG NO
0K6968A
REV
B
A
SCALE
0.050
WT-KG SEE ABOVESHEET
1 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH
1/2
REV
A
WINDCHILL VERSION
A.4
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194 (47") WIDE X 2261
(89") LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT
FOR CONCRETE PAD GUIDELINES
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUEL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR
4. REMOVE THE REAR TANK AND REAR ENCLOSURE COVER PANEL TO ACCESS THE
STUB-UP AREAS AS FOLLOWS:
-HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
-LOW VOLTAGE CONNECTIONS INCLUDE TRANSFER SWITCH CONTROL WIRES
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. ENGINE SERVICE CONNECTIONS
OIL DRAIN: 3/8" NPT
EXHAUST OUTLET: 2" O.D.
7. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
8. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 35 INCHES H20.
9. REFERNCE OWNERS MANUAL FOR LIFTING WARNINGS.
10. MOUNTING BOLTS OR STUDS TO CONCRETE PAD SHALL BE 5/8-11 GRADE 5
UNITS: WEIGHT - KG [LBS]
DIMENSION - MM [INCH]
REFERENCE OWNERS MANUAL FOR PERIODIC
REPLACEMENT PART LISTINGS.
TOP VIEW
RIGHT SIDE VIEW
REAR VIEW
LEFT SIDE VIEW
RADIATOR/EXHAUST
DISCHARGE AIR
EXHAUST MUFFLER ENCLOSED WITHIN
GENERATOR ENCLOSURE
REAR TANK COVER
SEE NOTE 4
FRONT TANK
COVER
CUSTOMER ACCESS
ASSEMBLY, CONTROL PANEL
ACCESS, BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
CIRCUIT BREAKER
SEE NOTE 3
REAR ENCLOSURE COVER
PANEL
SEE NOTE 4
LIFTING PROVISIONS
(4 PLACES)
SEE NOTE 10 AND CENTER
OF GRAVITY DIMENSIONS
VISE ACTION LATCH,
ONE PER DOOR, ONE LIFT-OFF
DOOR PER SIDE OF GENERATOR
AIR INTAKE
(BOTH SIDES)
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
REMOVE COVER
FOR ACCESS TO
RADIATOR FILL CAP
BATTERY 12 VOLT
NEGATIVE GROUND
4 3 2 1
4 3 1
A
B
A
B
1044 [41.1]
1194 [47.0]
828 [32.6] TYP
923 [36.4] TYP
757 [29.8]
TYP
621 [24.5]
TYP
267 [10.5]
TYP
181 [7.1]
TYP
1431 [56.3]
1554 [61.2]
1764 [69.4] 187 [7.3]
STUB-UP
AREA
112 [4.4]
51 [2.0]
38 [1.5]
125 [4.9]
786 [30.9]
STUB-UP
AREA
112 [4.4] TYP
712 [28.0] TYP
1242 [48.9] TYP
1842 [72.5] TYP
1954 [76.9]
353 [13.9]
888 [35.0]
851 [33.5] TYP
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
TITLE
INSTALL CPL PROT D3.4L SW
ISSUE DATE:
SIZE CAGE NO DWG NO
0K6968A
REV
B
A
SCALE
0.075
WT-KG SEE ABOVESHEET
2 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
SH
2/2
REV
A
WINDCHILL VERSION
A.4
FUEL TANK
TOTAL CAPACITY 253.6 [67]
USABLE CAPACITY 230.9 [61]
CAPACITY: LITER [GALLONS]
DIMENSIONS: MM [INCH]
REMOVABLE STUB-UP
COVER
REMOVABLE COVER
CIRCUIT BREAKER,
NEUTRAL AND CUSTOMER
CONNECTION OPENING
HIGH AND LOW
VOLTAGE STUB-UP
INNER TANK NORMAL VENT
(2" NPT FEMALE)
INNER TANK EMERGENCY VENT
(2" NPT FEMALE)
FUEL LEVEL
GAUGE/SENDER
FUEL FILL
(2" NPT FEMALE)
FUEL RETURN
FUEL SUPPLY
16.7 [.66] MOUNTING HOLES
(8 PLACES)
/