WURM rECO-S-RLT Product information

Type
Product information
Retrofit solution for enabling ventilation plants
rECO-S-RLT_V1.2.0_PI_2021-06_EN 1
Subject to technical changes
rECO-S-RLT
1 rECO-S-RLT
Retrofit solution for enabling ventilation plants
1.1 Front view
Fig. 1: Front view
1.2 Features
Demand-based enabling of existing ventilation plants based on the temperature, air quality and
opening time
Room temperature recording
Outside temperature recording
Air quality recording by means of a CO2 air quality sensor
Real-time clock with power reserve
Switchover between day and night setpoint by means of integrated weekly timer with holiday cal-
endar
Support for higher baud rates on the Wurm CAN communication bus (C-BUS)
Can be locked to prevent unwanted parameter adjustment (SAC - Security Access Control)
Plain text designation for each parameter on the display, language selectable
Unique parameter identification with Quicklinks
BLUELINE operation
Plug-in screw terminals
Internal data memory for recording operating data
Direct connection of a CAN-USB to the service socket
Connection to the Wurm system via C-BUS and FRIGODATA XP
Retrofit solution for enabling ventilation plants
2 rECO-S-RLT_V1.2.0_PI_2021-06_EN
Subject to technical changes
rECO-S-RLT
1.3 Safety instructions
Writing conventions
WARNING
Avoid the described hazard: otherwise, electric voltage represents a danger that could lead to
fatal or serious bodily injury.
CAUTION
Avoid the described hazard: otherwise minor or medium bodily injury or damage to property will
result.
For your safety
For safe operation and to avoid personal injury and equipment damage through operator error, always
read these instructions, become familiar with the device, and follow all safety instructions on the prod-
uct and in this document, as well as the safety guidelines of Wurm GmbH & Co. KG Elektronische
Systeme. Keep these instructions ready to hand for quick reference and pass them on with the device
if the product is sold.
Wurm GmbH & Co. KG Elektronische Systeme accepts no liability in case of improper use or use for
other than the intended purpose.
WARNING
DANGER TO LIFE FROM ELECTRIC SHOCK AND/OR FIRE!
Switch off the power to the entire plant when carrying out installation, wiring or removal work.
Otherwise a mains voltage and/or external voltage may still be present even if the control voltage
is switched off. Always remove both power plugs (L and N).
The wiring of the device must be carried out only by qualified electricians.
Use only the correct tools for all work.
Check all wiring after connection.
Take note of the maximum loads on all connections.
Never expose the device to moisture, for example due to condensation or cleaning agents.
Take the device out of operation if it is faulty or damaged and is therefore compromising safe
operation.
Do not open the device.
Do not repair the device yourself. If the device requires repairs, send it in with an exact descrip-
tion of the fault.
CAUTION
ELECTROMAGNETIC INTERFERENCE CAN CAUSE FAULTS!
Always use shielded data cables and place them far away from power lines.
Target group This manual is intended for "service technician" personnel.
Intended use rECO-S-RLT is a controller from the FRIGOENTRY BLUELINE series
and is a retrofit solution for enabling ventilation plants.
Wurm Infocenter paperless info
Retrofit solution for enabling ventilation plants
rECO-S-RLT_V1.2.0_PI_2021-06_EN 3
Subject to technical changes
rECO-S-RLT
Version and validity of the documentation
Any versions not listed are special solutions for individual projects and are not described in detail in this document.
This document automatically ceases to be valid if a new technical description is issued.
Manufacturer: Wurm GmbH & Co. KG Elektronische Systeme, Morsbachtalstraße 30, D-42857 Remscheid
You can find more information on our website at www.wurm.de.
1.4 Connection diagram
Fig. 2: Connection diagram
Version Date
V1.2.0 and higher 2021-06 Documentation status
Pos. Designation Function
1C-BUS interface Data communication (H = CAN high, S = shield, L = CAN low)
2Service socket For connecting a CAN USB adapter
3ADSP No function yet
4Output relays K 1...K 4 Floating contact, 230V~, 4(2)A
5Power supply L 230V~/50Hz
6X-tra interface Expansion module connection
7Power supply N Neutral conductor
8Digital inputs DI 1...DI 4 Inputs for voltage-free contacts
9Analogue output Uout 2 0...10V
10 Analogue inputs Iin 1...Iin 2 Current inputs 4...20mA
11 Analogue output Uout 1 0...10V
12 Sensor input S 2 or 0...10V
input
Temperature sensor
13 Sensor input S 1 Temperature sensor

*1'
8RXW
*1'
8
8LQ
6
       

       


       

       


*1'
1/
.
.
.
.
6HUYLFH
$'63
+
9
6
/
 

8RXW
*1'
6


U(&265/7
VHF

G
F
,LQ
,LQ
',
',
',
',
8
Retrofit solution for enabling ventilation plants
4 rECO-S-RLT_V1.2.0_PI_2021-06_EN
Subject to technical changes
rECO-S-RLT
1.5 Installing the device
This device is designed for top-hat rail installation. The housing has standard DIN 43880 dimensions
and is also suitable for operation in fuse boxes and distribution cabinets.
The device can be positioned immediately adjacent to another device without gaps.
WARNING
DANGER TO LIFE FROM ELECTRIC SHOCK AND/OR FIRE!
Switch off the power to the entire plant before installing. Otherwise, mains voltage and/or exter-
nal voltage may still be present, even if the control voltage is switched off. Always remove both
power plugs (L and N).
The entire plant must be free of voltage.
1. (A) Place the device with the leading edge at an acute angle to the top-hat rail.
2. (B) Push the device downwards onto the top-hat rail.
The device snaps into place with the fastening safety catch (a) on the top-hat rail.
You can now connect the device.
Fig. 3: Top-hat rail installation
1.6 Technical data
Power supply 230V~, +10% / -15%, max. 9VA
Display 1 x display with plain text display
2 x green LED, C-BUS data traffic (CAN Tx, CAN Rx)
C-BUS communication 3-wire CAN bus interface with integrated power supply, galvani-
cally isolated, separate service socket
Expansion module
communication
Interface for connecting X-tra module
Analogue inputs 2 x 4...20mA
Temperature sensor 2 x TRK
Control input 0...10V= or an NTC temperature sensor
Digital inputs 4 x floating
Output relay 4 x normally open contact 230V~, 4(2)A, rated voltage 230V~
Analogue outputs 2 x 0...10V=, non-floating, max. load 10mA
Real-time clock Power reserve
Monitoring system Monitoring of data memory and connected sensors
Dimensions (W x H x D) 106mm x 90mm x 58mm (DIN 43880)
Fastening Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)
Ambient temperature Operation: 0...+55°C, storage: -25...+70°C
Weight About 320g
CE conformity - 2014/30/EU (EMC Directive)
- 2014/35/EU (Low Voltage Directive)
RoHS II
Valid from Version 1.2.0
A
B
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

WURM rECO-S-RLT Product information

Type
Product information

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI