Retrofit solution for enabling ventilation plants
4 rECO-S-RLT_V1.2.0_PI_2021-06_EN
Subject to technical changes
rECO-S-RLT
1.5 Installing the device
This device is designed for top-hat rail installation. The housing has standard DIN 43880 dimensions
and is also suitable for operation in fuse boxes and distribution cabinets.
The device can be positioned immediately adjacent to another device without gaps.
DANGER TO LIFE FROM ELECTRIC SHOCK AND/OR FIRE!
• Switch off the power to the entire plant before installing. Otherwise, mains voltage and/or exter-
nal voltage may still be present, even if the control voltage is switched off. Always remove both
power plugs (L and N).
The entire plant must be free of voltage.
1. (A) Place the device with the leading edge at an acute angle to the top-hat rail.
2. (B) Push the device downwards onto the top-hat rail.
The device snaps into place with the fastening safety catch (a) on the top-hat rail.
You can now connect the device.
Fig. 3: Top-hat rail installation
1.6 Technical data
Power supply 230V~, +10% / -15%, max. 9VA
Display 1 x display with plain text display
2 x green LED, C-BUS data traffic (CAN Tx, CAN Rx)
C-BUS communication 3-wire CAN bus interface with integrated power supply, galvani-
cally isolated, separate service socket
Expansion module
communication
Interface for connecting X-tra module
Analogue inputs 2 x 4...20mA
Temperature sensor 2 x TRK
Control input 0...10V= or an NTC temperature sensor
Digital inputs 4 x floating
Output relay 4 x normally open contact 230V~, 4(2)A, rated voltage 230V~
Analogue outputs 2 x 0...10V=, non-floating, max. load 10mA
Real-time clock Power reserve
Monitoring system Monitoring of data memory and connected sensors
Dimensions (W x H x D) 106mm x 90mm x 58mm (DIN 43880)
Fastening Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)
Ambient temperature Operation: 0...+55°C, storage: -25...+70°C
Weight About 320g
CE conformity - 2014/30/EU (EMC Directive)
- 2014/35/EU (Low Voltage Directive)
RoHS II
Valid from Version 1.2.0