Omega LVCN11 and 12 Series Owner's manual

Type
Owner's manual
1
2
3
INTRODUCTION/TABLEOFCONTENTS StepOne
Offeredinsmallandlargesizes,thecompactjunctionboxisidealforsensorwiringandconduittermination.
The junction box isuniversally compatiblewith our level switch, flow switch and fitting products.The small
enclosure(LVCN12series)has6polesandistypicallyusedwithasinglelevelorflowswitchsensor.Thelarge
enclosure(LVCN11series)has12polesformultiplelevelswitchesandistypicallyusedwithSmartTrak.
Features
PolypropyleneenclosureratedNEMA4Xwith300°conduitswivelbase.
CompatiblewithOmegaEngineeringsensors,installationfittingsandalarms.
Removableterminalstripswithupperandlowerscrewpoles.
Offeredinlargeandsmallsizesforsingleormultipointinstallations.
TableofContents
Specifications:.........................................................................................................................................................4
Dimensions:.............................................................................................................................................................4
SafetyPrecautions:.................................................................................................................................................5
MakeaFailSafeSystem:............................................................................................................................6
Components:...............................................................................................................................................6
Installation..............................................................................................................................................................7
MountingtoaSensor:...............................................................................................................................7
MountingtoaLVM10seriesorLVM51series:.......................................................................................8

4
SPECIFICATIONS/DIMENSIONS StepTwo
Sensorinput: LVCN11:1‐4sensors
LVCN12:1‐2sensors
Terminalstrip: LVCN11:12polesocket
LVCN12:6polesocket
Max.currentcapacity: 26Amps
Max.voltage: 380V
Wirestripping: 0.5mmor0.2”
Terminalscrewtorque:3.5inlbs.
Wiregauge: 2214AWGCu(copper)
Enclosurerating: NEMA4X(IP65)
Enclosurematerial: Polypropylene(U.L.94VO)
Enclosurerotation: 300°swivelbase
Temperaturerange.: F:‐40°to158°
C:‐40°to70°
Conduitentrance: Single,½”NPT
Mountingconnection: Single,¾”NPT
TopVieww/oCap
LVCN11Series
TopVieww/oCap
LVCN12Series
SideView
LVCN11Series
SideView
LVCN12Series

5
SAFETYPRECAUTIONS StepThree
AboutThisManual:PLEASEREADTHE ENTIREMANUALPRIORTOINSTALLINGORUSINGTHISPRODUCT.
Thismanualincludesinformationon theCompactJunctionBoxes fromOmegaEngineering:LVCN11and
LVCN12Series.Pleaserefertothepartnumberlocatedonthelabeltoverifytheexactmodelwhichyou
havepurchased.Manyaspectsofinstallationandusearesimilarbetweenmodels.
User’s Responsibilityfor Safety:OMEGA ENGINEERINGmanufactures several modelsof controller, with
different mounting and switching configurations.It is the user’s responsibility to select a junction box
modelthatisappropriatefortheapplication,installitproperly,performtestsoftheinstalledsystem,and
maintainallcomponents.
ElectricalShockHazard:Itispossibletocontactcomponentsonthejunctionboxthatcarryhighvoltage,
causingseriousinjuryordeath.AllpowertothecircuitsintheterminalstripshouldbeturnedOFFpriorto
workingonthecontroller.Ifitisnecessarytomakeadjustmentsduringpoweredoperation,useextreme
caution and use only insulated tools.Making adjustments to powered controllers is not recommended.
Wiring should be performed by qualified personnel in accordance with all applicable national, state and
localelectricalcodes.
Flammable or Explosive Applications: Sensor mount controllers should not be used with explosive or
flammable liquids, which require an intrinsically safe or explosion proof rating.If you are unsure of the
suitabilityof acontrollerforyour installation,consultyourOmega Engineeringrepresentativeforfurther
information.
InstallInaDryLocation:Whilethecompact junctionbox isliquidresistantwheninstalledproperly, itis
not designed to be immersed.Itshould be mounted in such a waythat it does not normally comeinto
contactwithfluid.ItshousingismadeoutofPP(propylene).Refertoanindustry referencetoensurethat
compoundsthatmay splashontothecontroller housingwillnotdamageit.Suchdamageisnotcovered
bythewarranty.
Application:The LVCN11 series junction box is commonly used for the local termination of multiple
switches installed on a LVM10 series mounting system.The LVCN12 series junction box is commonly
used for the local termination of a single level or flow switch.Combine these junction boxes with any
switchorfittingassemblytocompleteyourapplication.

6
SAFETYPRECAUTIONS(cont.) StepThree
Make a FailSafe System: Design a failsafe system that accommodates the possibility of relay or power
failure.If power is cut off to the controller, it will deenergize the relay.Make sure that the deenergized
stateoftherelayisthesafestateinyourprocess.Forexample,ifcontrollerpowerislost,apumpfillingatank
willturnoffifitisconnectedtotheNormallyOpensideoftherelay.
Allpowertothesystemmustbeturnedoffbeforeinstallingthehousing.
Important:Donotstripmorethat0.25”ofinsulationfromany wirethatwillbeconnectedtotheterminal
strip.Longer uninsulated wire may contact the terminal strip panel, causing a short circuit leading to a
systemfailure.
All wiring between a controller and sensor(s) should be in conduit.The power entrance of the terminal
strip housing is a stand a rd ½” NPT female fitting that will attach to a standard electrical conduit, either
plastic or metal, as specified by local codes.Keep in mind that the housing may have to be unscrewed
fromthesens
orforperiodiccleaningofthesensor.Forthisreasontheuseofflexibleconduit,providing
enoughslackforeasyaccessisrecommended.
Usecaution wheninstalling theconduit.Excessivetightening maybreak thefitting.Suchdamage isnot
coveredbythewarranty.
In some cases, additional userprovided components may need to be attached to the terminals.If so,
make sure that both wires and/or components entering the terminal are secure after the screws are
tightened.
Components:
LVCN11 ‐MultiInput(12pole)JunctionBox,NPTThread
LVCN12 ‐SingleInput(6pole)JunctionBox,NPTThread
Owner’sManual

7
INSTALLATION StepFour
MountingonaSensor:Thefollowingprocedureshouldbeusedwhenmountingthejunctionboxdirectlyona
sensor.Allpowertothesystemmustbeoffbeforeinstallingthejunctionbox.
1. Preparethesensor:Thefollowinginstructionsassumethesensorisalreadymountedinapositionon
itstank orfitting (asdescribed inthe sensormanual).Note thatbecause theinsulation jacketof the
sensorislessflexiblethanmost(toensurechemicalcompatibility),itisimportantthatyoufollowthe
instructionsexactly.
a. Cutthewire41/4”fromthetopofthesensor.
b. Usinga10gaugewirestripper,stripthewhiteouterlayerofinsulationfromthelast11/4”of
thesensorwire.Trimoffanddiscardtheexposedfoilshieldflushwiththeinsulationjacket.In
longcableruns,donotcutoffthedrainwire.
c. Usinga20gaugewirestripper,stripthelast¼”ofinsulationfromthesignalwires.
Important:Donotstripmorethan0.2”(5mm)ofinsulationfromanywirethatwillbeconnectedto the
terminal strip.Longer insulated wire may contact the terminal strip panel, causing a short circuit
leadingtoasystemfailure.
2. Position the junction box on the sensor:To make the mounting and wiring easier, you must first
removetheterminalstripfromthejunctionbox.
a. Unscrewthelidofthejunctionbox.
b. Gentlytipthejunctionboxtoslideouttheterminalstrippanel,andplace
itaside.
c. Threadthepre trimmedsensorwiresthroughthe¾”NPTentrancetothe
junctionbox,andplacethejunctionboxinpositionoverthesensor.
d. Being careful not to cross the threads, screw the junction box on the
sensor.Stopwhenthecapofthesensorbecomesflushwiththebottom
wallofthejunctionbox,orwhenthe½”powerconduit entranceisinthe
desiredlocation.
3. Connectthesensorinputwires:
a. Routethesensorwiresoit staysasclose tothehousingaspossible,but
donotbendthewiresharplyatthecapofthesensor.(Iftheinstallation
allows,youmayrotatethejunction boxand/or thesensoruntil thewire
outletofthesensorisinthebestposition.)
b. Position the terminal strip panel in the housing aligned with the two
channelsdesignedtoholdit.Donotinsertthepanelalltheway intothe
housing,butletitrestonthetopofthehousingtofacilitatethewiring.
c. Usinga smallscrewdriver,loosen theterminalscrews.Insert thesensor
wiresintotheholeonthelowersideoftheterminalstrip,andtightenthe
terminalscrews.
4. Mechanicalconnectiontoconduit:Allwiringbetweenacontrollerandsensors
should be in conduit.The power entrance of the junction box is a standard ½”
NPTfemalefittingthatwillattachtostandardelectricalconduit,eitherplasticor
metal,asspecifiedbylocalcodes.Keepinmindthatthehousingmayhavetobe
unscrewed from the sensor for periodic cleaning of the sensor.
For this reason the use of flexible
conduit,providingenoughslackforeasyaccessisrecommended.
8
INSTALLATION(continued) StepFour
5. Connecttheextensionwiring:
Beforemakingconnections,makesureallpowertothesystem(controller,motor,valve,alarm,etc.)
isOFFwithasafetylockoutonthecircuitbreaker.
a. Theextensionwiringtosensorsshouldbeofthesametypeasthesensors.Iftherunislong,it
mayneedtobeaslightlythickergaugesotheseriesresistanceiskelpwithinallowablelimits.
b. Threadtheextensionwiringthroughthepowerconduitentranceofthehousing.
c. Strip¼”oftheinsulationfromtheendsofthewires.
d. Loosentheupperterminalscrews.Inserttheextensionwiresintothecorrespondingterminals,
matchingthesensorwires.
e. Tightentheterminalscrews.
f. Slidetheterminalstrippanelbackintothehousing,makingsureitisinthegroveprovidedon
eachsideofthehousing.Thepanel“floats”inthehousing,heldinpositionbythewiring.
g. Screwthelidofthehousingbackon.
Note:In somecases,additional userprovidedcomponentsmayneed tobe attachedtothe terminals.If
so, make sure that both wires and/or components entering the terminal are secure after the screws are
tightened.
MountingonaLVM10seriesorLVM51series:AterminalstripmaybemounteddirectlyonaLVM10series
or LVM51 series mounting system.The only differenc
e between mounting on a LVM10 series, a LVM51
seriesor directly on asensor is inthe length ofthe wiring from the sensor(s).Assumingthat eachsensor is
already mounted in position, cut the sensor wires to the length approximately 11/2” above the top of the
housing.However,besuretomake allowanceswhencuttingthe sensorleadsfor futureadjustmentstothe
sensorposition.
MountingtoLVM10Series
MountingSystem
MountingtoLVM51Series
MountingSystem
Note:Alwaystightenthecontrollerfromthe wrenchflatlocatedonthe
swivelbase.Nevertightenfromthebodyofthecontroller.
9

10
11

12
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Omega LVCN11 and 12 Series Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI