Daikin VAM800J7VEB Installer And User Reference Manual

Category
Split-system air conditioners
Type
Installer And User Reference Manual
Installer and user reference guide
Heat reclaim ventilation unit English
Name Plate
Installer and user
reference guide
Heat reclaim ventilation unit
VAM350J7VEB
VAM500J7VEB
VAM650J7VEB
VAM800J7VEB
VAM1000J7VEB
VAM1500J7VEB
VAM2000J7VEB
Table of contents
Installer and user reference guide
2
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
Table of contents
1 General safety precautions 3
1.1 About the documentation .......................................................... 3
1.1.1 Meaning of warnings and symbols.............................. 3
1.2 For the user ............................................................................... 3
1.3 For the installer.......................................................................... 3
1.3.1 General ....................................................................... 3
1.3.2 Installation site ............................................................ 4
1.3.3 Refrigerant .................................................................. 5
1.3.4 Brine............................................................................ 6
1.3.5 Water .......................................................................... 6
1.3.6 Electrical ..................................................................... 6
2 About the documentation 7
2.1 About this document.................................................................. 7
For the installer 8
3 About the box 8
3.1 Overview: About the box ........................................................... 8
3.2 Heat reclaim ventilation unit ...................................................... 8
3.2.1 To unpack the heat reclaim ventilation unit................. 8
3.2.2 To remove the accessories......................................... 9
3.2.3 To handle the heat reclaim ventilation unit ................. 10
4 About the units and options 10
4.1 Overview: About the units and options...................................... 10
4.2 Identification .............................................................................. 10
4.2.1 Identification label: Heat reclaim ventilation unit......... 10
4.3 About the heat reclaim ventilation unit ...................................... 10
4.4 Combining units and options ..................................................... 11
4.4.1 Possible options for the heat reclaim ventilation unit.. 11
5 Preparation 11
5.1 Overview: Preparation............................................................... 11
5.2 Preparing the installation site .................................................... 11
5.2.1 Installation site requirements for the heat reclaim
ventilation unit ............................................................. 11
5.3 Preparing the unit ...................................................................... 12
5.3.1 To install the optional adapter PCB ............................ 12
5.3.2 To install the duct joints .............................................. 13
5.4 Preparing electrical wiring ......................................................... 13
5.4.1 Wiring connection ....................................................... 13
5.4.2 Component electrical specifications............................ 13
5.4.3 Specifications for field supplied fuses and wires......... 13
5.5 Preparing the installation of the ducts ....................................... 14
6 Installation 15
6.1 Service space: Heat reclaim ventilation unit.............................. 15
6.2 Unit orientation .......................................................................... 15
6.3 To install the anchor bolts ......................................................... 16
6.4 Duct connections....................................................................... 16
6.5 Electrical wiring ......................................................................... 17
6.5.1 Precautions when connecting electrical wiring ........... 17
6.5.2 Opening the switch box............................................... 17
6.5.3 Electrical connections for additional field supplied
damper........................................................................ 20
6.5.4 Power supply connection, control wire terminals and
switches on the PCB................................................... 20
6.5.5 Guidelines when connecting the electrical wiring ....... 21
7 System configuration 21
7.1 About control systems ............................................................... 21
7.2 Independent system .................................................................. 22
7.3 Linked operation control system................................................ 23
7.4 Central control system............................................................... 23
8 Configuration 23
8.1 Operating procedure .................................................................. 24
8.1.1 To change settings....................................................... 24
8.2 List of settings ............................................................................ 25
8.3 Settings for all configurations ..................................................... 29
8.3.1 About setting 19(29)-0-04 and 19(29)-0-05 ................. 30
8.3.2 Independent system..................................................... 30
8.3.3 1-group linked-control system...................................... 30
8.3.4 Linked control with more than 2 groups ....................... 30
8.3.5 Direct duct connection ................................................. 31
8.3.6 Central control system ................................................. 31
8.4 About the controller .................................................................... 32
8.4.1 Controller for VRV system air conditioner.................... 33
8.4.2 Controller for heat reclaim ventilation units.................. 34
8.5 Detailed explanation of settings ................................................. 35
8.5.1 To monitor the unit's operation..................................... 35
8.5.2 About fresh-up operation ............................................. 35
8.5.3 About the external damper operation........................... 36
8.5.4 About the CO2 sensor ................................................. 36
8.5.5 About nighttime free cooling operation ........................ 38
8.5.6 About the precool and preheat function....................... 38
8.5.7 About preventing a feeling of draft............................... 39
8.5.8 About 24-hour ventilation ............................................. 39
8.5.9 About the ultra-low setting ........................................... 39
8.5.10 About the electrical heater operation ........................... 39
8.5.11 About external linkage input......................................... 39
8.5.12 About filter contamination check .................................. 39
9 Commissioning 39
9.1 Overview: Commissioning.......................................................... 39
9.2 Precautions when commissioning .............................................. 39
9.3 Checklist before commissioning................................................. 39
9.4 Checklist during commissioning ................................................. 40
9.4.1 About the test run......................................................... 40
10 Hand-over to the user 40
11 Maintenance and service 40
11.1 Overview: Maintenance and service .......................................... 40
11.2 Maintenance safety precautions................................................. 40
11.2.1 To prevent electrical hazards....................................... 40
11.3 Checklist for maintenance of the heat reclaim ventilation unit ... 41
12 Troubleshooting 41
12.1 Overview: Troubleshooting......................................................... 41
12.2 Precautions when troubleshooting ............................................. 41
12.3 Solving problems based on error codes ..................................... 41
12.3.1 Error codes: Overview ................................................. 41
13 Disposal 42
14 Technical data 42
14.1 Wiring diagram: Heat reclaim ventilation unit ............................. 42
For the user 43
15 Controller 43
16 Before operation 43
17 Energy saving and optimum operation 43
18 Maintenance and service 43
18.1 Maintenance of the air filter ........................................................ 43
18.2 Maintenance of the heat exchange element .............................. 44
19 Troubleshooting 44
20 Relocation 45
21 Disposal 45
1 General safety precautions
Installer and user reference guide
3
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
22 Glossary 45
1 General safety precautions
1.1 About the documentation
The original documentation is written in English. All other
languages are translations.
The precautions described in this document cover very important
topics, follow them carefully.
The installation of the system, and all activities described in the
installation manual and the installer reference guide MUST be
performed by an authorised installer.
1.1.1 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of
extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious
injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate
injury.
NOTICE
Indicates a situation that could result in equipment or
property damage.
INFORMATION
Indicates useful tips or additional information.
Symbol Explanation
Before installation, read the installation and
operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks,
read the service manual.
For more information, see the installer and user
reference guide.
1.2 For the user
If you are NOT sure how to operate the unit, contact your installer.
This appliance can be used by children aged from 8 years and
above and persons with reduced physical, sensory or mental
capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in
a safe way and understand the hazards involved. Children shall
NOT play with the appliance. Cleaning and user maintenance
shall NOT be made by children without supervision.
WARNING
To prevent electric shocks or fire:
Do NOT rinse the unit.
Do NOT operate the unit with wet hands.
Do NOT place any objects containing water on the unit.
NOTICE
Do NOT place any objects or equipment on top of the
unit.
Do NOT sit, climb or stand on the unit.
Units are marked with the following symbol:
This means that electrical and electronic products may NOT be
mixed with unsorted household waste. Do NOT try to dismantle
the system yourself: the dismantling of the system, treatment of
the refrigerant, of oil and of other parts must be done by an
authorized installer and must comply with applicable legislation.
Units must be treated at a specialized treatment facility for reuse,
recycling and recovery. By ensuring this product is disposed of
correctly, you will help to prevent potential negative consequences
for the environment and human health. For more information,
contact your installer or local authority.
Batteries are marked with the following symbol:
This means that the batteries may NOT be mixed with unsorted
household waste. If a chemical symbol is printed beneath the
symbol, this chemical symbol means that the battery contains a
heavy metal above a certain concentration.
Possible chemical symbols are: Pb: lead (>0.004%).
Waste batteries must be treated at a specialized treatment facility
for reuse. By ensuring waste batteries are disposed of correctly,
you will help to prevent potential negative consequences for the
environment and human health.
1.3 For the installer
1.3.1 General
If you are NOT sure how to install or operate the unit, contact your
dealer.
NOTICE
Improper installation or attachment of equipment or
accessories could result in electric shock, short-circuit,
leaks, fire or other damage to the equipment. Only use
accessories, optional equipment and spare parts made or
approved by Daikin.
WARNING
Make sure installation, testing and applied materials
comply with applicable legislation (on top of the
instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective
gloves, safety glasses,…) when installing, maintaining or
servicing the system.
1 General safety precautions
Installer and user reference guide
4
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
WARNING
Tear apart and throw away plastic packaging bags so that
nobody, especially children, can play with them. Possible
risk: suffocation.
DANGER: RISK OF BURNING
Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It
could be too hot or too cold. Give it time to return to
normal temperature. If you must touch it, wear
protective gloves.
Do NOT touch any accidental leaking refrigerant.
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
NOTICE
Do NOT place any objects or equipment on top of the
unit.
Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under
dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary
to provide a logbook with the product containing at least: information
on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an
accessible place at the product:
Instructions for shutting down the system in case of an emergency
Name and address of fire department, police and hospital
Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
1.3.2 Installation site
Provide sufficient space around the unit for servicing and air
circulation.
Make sure the installation site withstands the unit's weight and
vibration.
Make sure the area is well ventilated. Do NOT block any
ventilation openings.
Make sure the unit is level.
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system,
and cause malfunction of the equipment.
In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre,
ignitable dust.
In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause
the refrigerant to leak.
Instructions for equipment using R32 refrigerant
If applicable.
WARNING
Do NOT pierce or burn.
Do NOT use means to accelerate the defrosting
process or to clean the equipment, other than those
recommended by the manufacturer.
Be aware that R32 refrigerant does NOT contain an
odour.
WARNING
The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating ignition sources (example: open flames, an
operating gas appliance or an operating electric heater)
and have a room size as specified below.
NOTICE
Do NOT re-use joints which have been used already.
Joints made in installation between parts of refrigerant
system shall be accessible for maintenance purposes.
WARNING
Make sure installation, servicing, maintenance and repair
comply with instructions from Daikin and with applicable
legislation (for example national gas regulation) and are
executed only by authorised persons.
Installation space requirements
NOTICE
Pipework shall be protected from physical damage.
Installation of pipework shall be kept to a minimum.
WARNING
If appliances contain R32 refrigerant, the floor area of the
room in which the appliances are installed, operated and
stored MUST be larger than the minimum floor area
defined in table below A (m2). This applies to:
Indoor units without a refrigerant leakage sensor; in
case of indoor units with refrigerant leakage sensor,
consult the installation manual
Outdoor units installed or stored indoors (e.g. winter
garden, garage, machinery room)
Pipework in unventilated spaces
To determine the minimum floor area
1Determine the total refrigerant charge in the system (= factory
refrigerant charge + additional refrigerant amount
charged).
Contains fluorinated greenhouse gases
211
1
2
2kg
tCO
2
eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
2Determine which graph or table to use.
For indoor units: Is the unit ceiling-mounted, wall-mounted or
floor-standing?
For outdoor units installed or stored indoors, and field piping
in unventilated spaces, this depends on the installation
height:
1 General safety precautions
Installer and user reference guide
5
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
If the installation height is… Then use the graph or table for…
<1.8m Floor-standing units
1.8≤x<2.2m Wall-mounted units
≥2.2m Ceiling-mounted units
3Use the graph or table to determine the minimum floor area.
0
10 20
30 40
50 60
70 80
90 100
110120
130140
150160
170180
190200
210220
230240
250260
270280
290300
310320
330340
350360
370380
390400
410420
430440
450460
470480
490500
510520
530540
550
1.8 22.22.42.62.8 33.23.43.63.8 44.24.44.64.8 55.25.45.65.8 66.26.46.66.8 77.27.47.67.8
1.843 7.956
8.0
Amin (m2)
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m (kg)
Ceiling-mounted
unit(a)
4.6 13.4 4.6 180
4.8 14.6 4.8 196
5.0 15.8 5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3
7.956 40.1
4.4 165
7.956 539
m (kg) Amin (m2)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
7.956 59.9
Wall-mounted
unit(b)
m (kg) Amin (m2)
Floor-standing
unit(c)
m (kg) Amin (m2)
mTotal refrigerant charge in the system
Amin Minimum floor area
(a) Ceiling-mounted unit (= Ceiling-mounted unit)
(b) Wall-mounted unit (= Wall-mounted unit)
(c) Floor-standing unit (= Floor-standing unit)
1.3.3 Refrigerant
If applicable. See the installation manual or installer reference guide
of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with
applicable legislation. In Europe, EN378 is the applicable
standard.
NOTICE
Make sure the field piping and connections are NOT
subjected to stress.
WARNING
During tests, NEVER pressurize the product with a
pressure higher than the maximum allowable pressure (as
indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If
refrigerant gas leaks, ventilate the area immediately.
Possible risks:
Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
Toxic gas may be produced if refrigerant gas comes
into contact with fire.
1 General safety precautions
Installer and user reference guide
6
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
DANGER: RISK OF EXPLOSION
Pump down Refrigerant leakage. If you want to pump
down the system, and there is a leak in the refrigerant
circuit:
Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the
system into the outdoor unit. Possible consequence:
Self-combustion and explosion of the compressor
because of air going into the operating compressor.
Use a separate recovery system so that the unit's
compressor does NOT have to operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them
directly into the environment. Use a vacuum pump to
evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is
no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
When the refrigerant system is to be opened,
refrigerant MUST be treated according to the applicable
legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant
may only be charged after performing the leak test and the
vacuum drying.
In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging
of refrigerant.
Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign
materials from entering into the system.
Charge the liquid refrigerant as follows:
If Then
A siphon tube is present
(i.e., the cylinder is marked with
"Liquid filling siphon attached")
Charge with the cylinder upright.
A siphon tube is NOT present Charge with the cylinder upside
down.
Open refrigerant cylinders slowly.
Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
CAUTION
When the refrigerant charging procedure is done or when
pausing, close the valve of the refrigerant tank
immediately. If the valve is NOT closed immediately,
remaining pressure might charge additional refrigerant.
Possible consequence: Incorrect refrigerant amount.
1.3.4 Brine
If applicable. See the installation manual or installer reference guide
of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the
applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If
brine leaks, ventilate the area immediately and contact
your local dealer.
WARNING
The ambient temperature inside the unit can get much
higher than that of the room, e.g. 70°C. In case of a brine
leak, hot parts inside the unit can create a hazardous
situation.
WARNING
The use and installation of the application MUST comply
with the safety and environmental precautions specified in
the applicable legislation.
1.3.5 Water
If applicable. See the installation manual or installer reference guide
of your application for more information.
NOTICE
Make sure water quality complies with EU directive
98/83EC.
1.3.6 Electrical
DANGER: RISK OF ELECTROCUTION
Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or
touching electrical parts.
Disconnect the power supply for more than 1 minute,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing.
The voltage MUST be less than 50 V DC before you
can touch electrical components. For the location of the
terminals, see the wiring diagram.
Do NOT touch electrical components with wet hands.
Do NOT leave the unit unattended when the service
cover is removed.
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category III
condition, MUST be installed in the fixed wiring.
2 About the documentation
Installer and user reference guide
7
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
WARNING
ONLY use copper wires.
Make sure the field wiring complies with the applicable
legislation.
All field wiring MUST be performed in accordance with
the wiring diagram supplied with the product.
NEVER squeeze bundled cables and make sure they
do NOT come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
Make sure to install the required fuses or circuit
breakers.
Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may
cause abnormal heat).
When connecting wiring which is the same thickness,
do as shown in the figure above.
For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being
exerted on the terminal board.
Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
damage the head and make proper tightening
impossible.
Over-tightening the terminal screws may break them.
WARNING
After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical
components box is connected securely.
Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the
compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a
momentary black out and the power goes on and off while
the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.
2 About the documentation
2.1 About this document
INFORMATION
Make sure that the user has the printed documentation and
ask him/her to keep it for future reference.
Target audience
Authorised installers + end users
INFORMATION
This appliance is intended to be used by expert or trained
users in shops, in light industry and on farms, or for
commercial use by lay persons.
Documentation set
This document is part of a documentation set. The complete set
consists of:
General safety precautions:
Safety instructions that you MUST read before installing
Format: Paper (in the accessory bag of the heat reclaim
ventilation unit)
Heat reclaim ventilation unit installation and operation
manual:
Installation and operation instructions
Format: Paper (in the accessory bag of the heat reclaim
ventilation unit)
Installer and user reference guide:
Preparation of the installation, good practices, reference data,…
Detailed step-by-step instructions and background information
for basic and advanced usage
Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages
are translations.
Technical engineering data
A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
The full set of latest technical data is available on the Daikin
extranet (authentication required).
3 About the box
Installer and user reference guide
8
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
For the installer
3 About the box
3.1 Overview: About the box
This chapter describes what you have to do after the box with the
heat reclaim ventilation unit is delivered on-site.
It contains information about:
Unpacking and handling the units
Removing the accessories from the units
Keep the following in mind:
At delivery, the unit MUST be checked for damage. Any damage
MUST be reported immediately to the carrier's claims agent.
Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid damage.
Prepare the path along which you want to bring the unit inside in
advance.
3.2 Heat reclaim ventilation unit
3.2.1 To unpack the heat reclaim ventilation
unit
Models 350+500
Models 650~1000
3 About the box
Installer and user reference guide
9
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
Models 1500+2000
2
1
3
3.2.2 To remove the accessories
Models 350+500
Models 650~1000
Models 1500+2000
dcba e
aConnector for additional external damper
bGeneral safety precautions
cInstallation and operation manual
dDuct joints (models 350~1000 4×,models 1500+2000 8×)
4 About the units and options
Installer and user reference guide
10
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
eScrews (models 350+500 16×, models 650~1000 24×,
models 1500+2000 48×)
3.2.3 To handle the heat reclaim ventilation unit
NOTICE
When removing the heat reclaim ventilation unit from the
packing, do NOT place the suction or discharge side of the
unit on the floor. Possible consequence: Deformation of
the suction or discharge openings and damaged expanded
polystyrene parts of the unit.
CAUTION
To avoid injury, do NOT touch the air inlet, the air outlet, or
the fans of the unit.
With packaging.
In case of models 350+500, do NOT use slings or a forklift.
In case of models 650~2000, use a forklift.
Without packaging.
Carry models 350~1000 slowly as shown:
Name Plate
Carry models 1500+2000 slowly as shown:
4 About the units and options
4.1 Overview: About the units and
options
This chapter contains information about:
Identifying the unit
Combining the unit with options
4.2 Identification
NOTICE
When installing or servicing several units at the same time,
make sure NOT to switch the service panels between
different models.
4.2.1 Identification label: Heat reclaim
ventilation unit
Location
Name Plate
Model identification
Example: VAM500J7VEB[*]
Code Explanation
V Ventilation
A Air
M Mounted type
500 Nominal air flow rate (m³/h)
J Major design category (Design category for EC
application)
7 Minor design category
VE Power supply: 1~, 50Hz 220~240V
Power supply: 1~, 60Hz 220V
B European market
[*] Minor model change indication
4.3 About the heat reclaim ventilation
unit
The heat reclaim ventilation unit is intended for indoor installation.
NOTICE
ALWAYS use the air filter. If the air filter is NOT used, the
heat exchange elements can get clogged, possibly causing
poor performance and subsequent failure.
Operation range
Supply air + exhaust
air
Temperature –10°CDB~46°CDB
Relative humidity ≤80%
5 Preparation
Installer and user reference guide
11
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
Operation range
Unit location
Temperature 0°CDB~40°CDB
Relative humidity ≤80%
It is possible that, due to condensation, the paper heat exchanger
deteriorates when the unit operates in conditions with high indoor
humidity combined with low outdoor temperature. If such combined
conditions occur for an extended period of time, the necessary
precautions must be taken to prevent condensation. Example: install
a preheater to heat up outdoor air.
When the heat reclaim ventilation unit is installed upside down, the
minimum allowed outdoor air temperature is 5°C. If this cannot be
guaranteed, you MUST install a heater to heat up the outdoor air to
5°C.
4.4 Combining units and options
4.4.1 Possible options for the heat reclaim
ventilation unit
Adapter PCB
Options BRP4A50A and KRP2A51.
At temperatures below –10°C, it is mandatory to use an electrical
heater. This heater is connected with option PCB BRP4A50A.
CAUTION
If an electrical heater is installed, use non-flammable duct.
For safety reasons, be sure to keep a distance of at least
2 m between the heater and the heat reclaim ventilation
unit.
When installing any of these options on model 650, prepare the
mounting plate (EKMP65VAM).
When installing any of these options on models 1500 or 2000,
prepare the mounting plate (EKMPVAM).
When installing option KRP2A51, prepare the installation box
(KRP1BA101).
Filter
When. This option may be mandatory. Check the local legislation. It
is recommended in places with poor outside air quality.
Where. Install the filter behind the heat exchange element either at
the supply air side or at the exhaust air side. Keep the standard filter
in place. Remove the standard filter ONLY when installing an option
filter both in front of and behind the heat exchange element.
How. For installation instructions, see the installation manual of the
filter kit.
Pressure drop over the filter. See the databook for pressure drop
curves for each capacity class of unit and each class of filter.
Model Filter
class
350+500 650 800~2000
EKAFVJ50F6 M6 — —
EKAFVJ50F7 F7 — —
EKAFVJ50F8 F8 — —
EKAFVJ65F6 M6
EKAFVJ65F7 F7
EKAFVJ65F8 F8
EKAFVJ100F6 M6
EKAFVJ100F7 F7
EKAFVJ100F8 F8
Plenum (EKPLEN200)
When. The plenum is an option for models 1500+2000. This option
can be used to ease the installation of the heat reclaim ventilation
unit.
Where. Replace the 2 duct joints of Ø250mm with the plenum and a
duct joint of Ø350mm.
How. For installation instructions, see the installation manual of the
plenum kit.
CO2 sensor (BRYMA*)
When. The CO2 sensor is optional. This option can be used to adapt
the ventilation rate to the CO2 concentration.
Where. Install the CO2 sensor in the heat reclaim ventilation unit. For
models 1500+2000, install the CO2 sensor in the top heat reclaim
ventilation unit.
How. For installation instructions, see "8.5.4 About the CO2
sensor"on page36.
5 Preparation
5.1 Overview: Preparation
This chapter describes what you have to do and know before going
on-site.
It contains information about:
Preparing the installation site
Preparing the unit
Preparing the electrical wiring
Preparing the installation of the ducts
5.2 Preparing the installation site
Do NOT install the unit in places often used as work place. In case
of construction works (e.g. grinding works) where a lot of dust is
created, the unit MUST be covered.
Choose an installation location with sufficient space for carrying the
unit in and out of the site.
Do NOT install a heat reclaim ventilation unit or air suction/discharge
grille in the following places:
Places, such as machinery plants and chemical plants, where
noxious gases or corrosive components of materials such as acid,
alkali, organic solvent and paint are present.
Places, such as bathrooms, subject to moisture. Moisture can
cause electric shock, electric leakage and other failures.
Places subject to high temperature or direct flames.
Places subject to much soot. Soot clings to air filter and heat
exchange elements, disabling them.
5.2.1 Installation site requirements for the heat
reclaim ventilation unit
INFORMATION
Also read the general installation site requirements. See
the "General safety precautions" chapter.
5 Preparation
Installer and user reference guide
12
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
CAUTION
The appliance is designed to be a built-in appliance. It
must NOT be accessible to the general public.
Adequate measures have to be taken to prevent
access by other than qualified persons.
Check if the installation location can support the unit's
weight. Poor installation is hazardous. It can also cause
vibrations or unusual operating noise.
Provide sufficient service space and inspection holes.
Inspection holes are needed for the air filters, the heat
exchange elements and the fans.
Do NOT install the unit so that it is in contact with a
ceiling or wall, this may cause vibration.
CAUTION
Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.
This unit is suitable for installation in a commercial and
light industrial environment.
For models 800~2000
NOTICE
This is a class A product. In a domestic environment this
product may cause radio interference in which case the
user may be required to take adequate measures.
Service space
See "6.1Service space: Heat reclaim ventilation unit"on page15.
5.3 Preparing the unit
5.3.1 To install the optional adapter PCB
For models 350-500-800-1000
a
c
b
f
g
f
f
aBRP4A50A (optional accessory)
bKRP2A51 (optional accessory)
cKRP1BA101 (installation box)
fScrew
gScrew (supplied with the installation box)
1Remove the screws from the unit.
2Attach the optional adapter PCB (KRP2A51) in the installation
box (KRP1BA101).
3Follow the installation instructions provided with the option kits
(BRP4A50A, KRP2A51 and KRP1BA101).
4Guide the PCB wire through the dedicated holes and attach it
as instructed in "6.5.2Opening the switch box"on page17.
5Attach the options to the unit, as shown in the figure.
6After the wires are connected, fasten the switch box cover.
For model 650
a d
c
b
g
f
f
f
aBRP4A50A (optional accessory)
bKRP2A51 (optional accessory)
cKRP1BA101 (installation box)
dEKMP65VAM (mounting plate)
fScrew
gScrew (supplied with the installation box)
1Remove the screws from the unit.
2Attach the optional mounting plate (EKMP65VAM) to the unit.
3Attach the optional adapter PCB (KRP2A51) in the installation
box (KRP1BA101).
4Follow the installation instructions provided with the option kits
(BRP4A50A, KRP2A51 and KRP1BA101).
5Guide the PCB wire through the dedicated holes and attach it
as instructed in "6.5.2Opening the switch box"on page17.
6Attach the options to the optional mounting plate, as shown in
the figure.
7After the wires are connected, fasten the switch box cover.
For models 1500+2000
b
aBRP4A50A (optional accessory)
bKRP2A51 (optional accessory)
cKRP1BA101 (installation box)
eEKMPVAM (mounting plate)
fScrew
gScrew (supplied with the installation box)
1Remove the screws from the middle of the plate connecting the
2 units.
5 Preparation
Installer and user reference guide
13
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
2Attach the optional mounting plate (EKMPVAM) on top of the
plate connecting the 2 units.
3Attach the optional adapter PCB (KRP2A51) in the installation
box (KRP1BA101).
4Follow the installation instructions provided with the option kits
(BRP4A50A, KRP2A51 and KRP1BA101).
5Guide the PCB wire through the dedicated holes and attach it
as instructed in "6.5.2Opening the switch box"on page17.
6Attach the options to the optional mounting plate, as shown in
the figure.
7After the wires are connected, fasten the switch box cover.
5.3.2 To install the duct joints
1Position the duct joints over the duct holes.
2Secure the duct joints with the provided screws (accessories).
1
2
Model Number of provided
screws
Number of provided
duct joints
350 16 4× Ø200mm
500 16 4× Ø200mm
650 24 4× Ø250mm
800 24 4× Ø250mm
1000 24 4× Ø250mm
1500 48 8× Ø250mm
2000 48 8× Ø250mm
5.4 Preparing electrical wiring
5.4.1 Wiring connection
WARNING
A main switch or other means for disconnection, having a
contact separation in all poles, MUST be incorporated in
the fixed wiring in accordance with the applicable
legislation.
You can use a single switch to supply power to units on the same
system. However, branch switches and branch circuit breakers
MUST be selected carefully.
Fit the power supply wiring of each unit with a switch and fuse as
shown in the drawing below.
Complete system example
a
b
b
c
d
e
e
aVRV outdoor unit
bVRV indoor unit
cPower supply
dMain switch
eController
5.4.2 Component electrical specifications
Model 350 500 650 800 1000 1500 2000
Power supply
50Hz 198~264V
60Hz 198~242V
MCA (A) 1.56 2.08 2.80 4.39 4.90 8.78 9.80
MFA (A) 16 16 16 16 16 16 16
Fan motor
P (kW) 0.08×2 0.08×2 0.106×2 0.21×2 0.21×2 0.21×4 0.21×4
FLA (A) 0.62×2 0.83×2 1.12×2 1.76×2 1.96×2 1.76×4 1.96×4
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PMotor Rated Load
FLA Full Load Amps
NOTICE
When using residual current operated circuit breakers,
make sure to use a high speed type 300mA rated residual
operating current.
NOTICE
The power supply MUST be protected with the required
safety devices, i.e. a main switch, a slow blow fuse on
each phase and an earth leakage protector in accordance
with the applicable legislation.
NOTICE
See the engineering data book for details.
5.4.3 Specifications for field supplied fuses and
wires
Power supply wiring
Field supplied
fuses
16A
5 Preparation
Installer and user reference guide
14
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
Power supply wiring
Wire H05VV-U3G
Size Wire size MUST comply with the applicable
legislation.
Transmission wiring
Wiring Shielded wire (2 wire)
Size 0.75~1.25mm²
Precautions
When connecting more than one wire to the power supply wiring,
use a 2mm² (Ø1.6mm) gauge wire.
When using 2 power wires of a gauge greater than 2 mm²
(Ø1.6mm), branch the line outside the terminal board of the unit, in
accordance with electrical equipment standards. The branch MUST
be sheathed to provide a degree of insulation equal to or greater
than the power supply wiring itself.
Keep the total current of crossover wiring between indoor units to
less than 12A.
Do NOT connect wires of different gauge to the same grounding
terminal. Loose connections may reduce the protection.
For the controller wiring, refer to the installation manual of the
controller delivered with the controller.
Wiring example
VRV
HRV
P1
P1
P1
P2 P2
P2
LN1 2
Out
VRV HRV
LN
L N 1 12 2 P1 P2 F1 F1 T1 T1 P2 P1 F1 F2 J2 J3JC L NJ1
ab
e
c
dd
g
f
f
aOutdoor unit/BS unit
bSwitch box
cIndoor unit
dPower supply 220-240V~50Hz
eController for VRV
fTransmission wiring
gController for heat reclaim ventilation unit
All transmission wiring, except for the controller wires, is polarised
and MUST match the terminal symbol.
Use shielded cable for the transmission wiring. Ground the shield
of the shielded cable to at the grounding screw, with the C-cup
washer.
5.5 Preparing the installation of the
ducts
INFORMATION
Flexible ducting with sound insulation is effective to
reduce blowing noises.
When selecting installation materials, consider the
required volume of air flow and the acceptable level of
noise for that particular installation.
When room air infiltrates into the ceiling and the
temperature and humidity in the ceiling become too
high, insulate the metal parts of the unit.
ONLY use the inspection hole to access the inside of
the unit.
The sound pressure level is less than 70dBA.
CAUTION
For safety reasons, the required minimum length of the
ducting is 1.5 m. If the ducting is shorter, or if no
ducting is installed, then you MUST install grilles in the
duct openings or the openings of the unit.
Make sure no wind can blow in the ducting.
6 Installation
Installer and user reference guide
15
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
6 Installation
6.1 Service space: Heat reclaim
ventilation unit
>50
a
>600
150-250
>1000
(mm)
aService space
6.2 Unit orientation
The following illustration helps you to install the heat reclaim
ventilation unit in the correct position:
INFORMATION
When the unit is installed vertically, the installer must
provide a support under the unit to distribute the weight of
the unit between the support and the installation bolts in
the wall.
NOTICE
When the heat reclaim ventilation unit is installed vertically
in low outdoor temperature conditions, dewing or freezing
may occur. If such operating conditions are to be expected,
take the appropriate precautions, e.g. install an electrical
heater.
Installation tips:
Installing the unit upside down allows for common use of the
inspection hole, thus reducing the required maintenance space.
For example, if 2 units are installed closely together, only 1
inspection hole is required for maintaining or replacing filters, heat
exchange elements,…
a
b
c
aControl box
6 Installation
Installer and user reference guide
16
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
bService cover
cInspection hole
NOTICE
When the heat reclaim ventilation unit is installed upside
down, the minimum allowed outdoor air temperature is
5°C. If this cannot be guaranteed, you MUST install a
heater to heat up the outdoor air to 5°C.
Keep in mind that the ceiling hooks must be rotated 180° when
the heat reclaim ventilation unit is installed upside down (see the
figure).
b
a
aCeiling hook
bService cover
6.3 To install the anchor bolts
Prerequisite: Before installing the anchor bolts, remove any foreign
objects, such as vinyl and paper, from the inside of the fan housing.
1Install the anchor bolts (M10 to M12).
2Pass the metal suspension brackets over the anchor bolts.
3Secure the anchor bolts with washer and nut.
For models 350~1000:
a
c
b
d
For models 1500+2000:
a
c
b
d
aCeiling hook
bNut
cWasher
dDouble nut
NOTICE
Always hang up the unit by its suspension brackets.
6.4 Duct connections
Do NOT connect the ducts as follows:
Extreme bend. Do NOT bend the duct more than 90°.
Multi bend
Reduced diameter. Do NOT reduce the duct diameter.
The minimum bend radius for flexible ducts is as follows:
(Øduct/2)×1.5
To prevent air leakage, wind aluminium tape around the section
where the duct joints and the ducts are connected.
Install the opening of the supply air as far as possible from the
opening of the room air.
Use ducts with a diameter that fits the unit model. See the data
book.
Install the two outdoor ducts with a downward slope (minimum
1:50) to prevent entry of rain water. Also provide insulation for
both ducts, to prevent dew formation. (Insulation material: 25mm
thick glass wool)
If the temperature and humidity levels inside the ceiling are always
high, install ventilation inside the ceiling.
Insulate the duct and the wall electrically when a metal duct has to
penetrate the metal lattice and wire lattice or the metal lining of a
wooden structure wall.
Install the ducts in such a way that the wind CANNOT blow inside
the ducting.
6 Installation
Installer and user reference guide
17
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
Models 350~1000
b
c
a
d
a
Name Plate
Models 1500+2000
d
ce e f
aAluminium tape (field supply)
bInsulation material (field supply)
cDuct joint (accessories)
dSlope minimum 1:50
eSupply air
fRoom air
6.5 Electrical wiring
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
WARNING
All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
legislation.
Make electrical connections to the fixed wiring.
All components procured on-site and all electrical
construction MUST comply with the applicable
legislation.
6.5.1 Precautions when connecting electrical
wiring
DANGER: RISK OF ELECTROCUTION
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category III
condition, MUST be installed in the fixed wiring.
WARNING
ONLY use copper wires.
Make sure the field wiring complies with the applicable
legislation.
All field wiring MUST be performed in accordance with
the wiring diagram supplied with the product.
NEVER squeeze bundled cables and make sure they
do NOT come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
Make sure to install the required fuses or circuit
breakers.
Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
WARNING
After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical
components box is connected securely.
Make sure all covers are closed before starting up the
unit.
NOTICE
If the power supply has a missing or wrong N-phase,
equipment will break down.
NOTICE
Do NOT install a phase advancing capacitor, because this
unit is equipped with an inverter. A phase advancing
capacitor will reduce performance and may cause
accidents.
6.5.2 Opening the switch box
CAUTION
Before opening the cover, be sure to turn off the power
switches of the main units and other devices connected to
the main units.
Remove the screws that secure the cover and open the
switch box.
Secure the power supply cable and the control wire
with a tie wrap, as shown in the figures.
6 Installation
Installer and user reference guide
18
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
Models 350~650
X33A
a
X14A
J3 J2 J1JC F2F1P2P1
X35A
X24A
X29A
C-
C+
b
b
kd+e
l
i
f
j
o
o
h
g
r
m
p
n m
a
l
m
j
i
b
b
k d+e
c
n
h
o
i
l
q
q
q
r
aSwitch box
bPCB
cSwitch box cover
dSecuring screw and washer
eGrounding terminal
fTerminal board
gTransmission wiring terminal board (P1, P2, F1, F2)
hTransmission wiring (to optional controller)
iPower supply cable
jWires for connection of additional external damper
(supplied accessory)
kInsulated splices-closed barrel connector (0.75mm²) (field
supply)
lDouble or reinforced insulated flexible cable (0.75mm²) to
external damper (field supply)
mTie wrap (field supply)
nBRP4A50A (optional accessory)
oKRP2A51 (optional accessory)
pCO sensor (optional accessory)
qTapping screw
rWires for fresh-up operation
Models 800+1000
a
p r h m
b
d+e kf lm
n
i
j
b
b
g
o
F2
F1
P2
P1
J3
J2
J1
JC
X33A
X14A
X35A
X24A
X29A
6 Installation
Installer and user reference guide
19
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
m
j
l
i
k
r
n
a
h
f d+e
c
o
i
q
q
q
n
r
l
h
aSwitch box
bPCB
cSwitch box cover
dSecuring screw and washer
eGrounding terminal
fTerminal board
gTransmission wiring terminal board (P1, P2, F1, F2)
hTransmission wiring (to optional controller)
iPower supply cable
jWires for connection of additional external damper
(supplied accessory)
kInsulated splices-closed barrel connector (0.75mm²) (field
supply)
lDouble or reinforced insulated flexible cable (0.75mm²) to
external damper (field supply)
mTie wrap (field supply)
nBRP4A50A (optional accessory)
oKRP2A51 (optional accessory)
pCO sensor (optional accessory)
qTapping screw
rWires for fresh-up operation
Models 1500+2000
a
g
p
b
m
b
b
b
f
k
i
m
l
j
r
n
h
m
d+e
o
A1P X24A
X29A
X27A
X35A
X14A
X33A
F2
F1
P2
P1
J3
J2
J1
JC
6 Installation
Installer and user reference guide
20
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
a
b
f
k
d
+
e
m
l
i
j
r n h
o
o
m
X35A
X24A
c
i
o
r
n
h
l
q
q
qc
aSwitch box
bPCB
cSwitch box cover
dSecuring screw and washer
eGrounding terminal
fTerminal board
gTransmission wiring terminal board (P1, P2, F1, F2)
hTransmission wiring (to optional controller)
iPower supply cable
jWires for connection of additional external damper
(supplied accessory)
kInsulated splices-closed barrel connector (0.75mm²) (field
supply)
lDouble or reinforced insulated flexible cable (0.75mm²) to
external damper (field supply)
mTie wrap (field supply)
nBRP4A50A (optional accessory)
oKRP2A51 (optional accessory)
pCO sensor (optional accessory)
qTapping screw
rWires for fresh-up operation
6.5.3 Electrical connections for additional field
supplied damper
An external damper prevents the intake of outdoor air when the heat
reclaim ventilation unit is switched off.
The heat reclaim ventilation main unit’s PCB operates the heat
reclaim ventilation unit and provides a contact for an external
damper.
PCB
X24A
a
b
c
d
aHeat reclaim ventilation main unit
bExternal damper
cExternal damper earthing
dPower source
CAUTION
Follow the instructions below carefully.
Required electrical connections
Connect one end of the accessory wire to the X24A connector on
the PCB and the other end to the wire leading to the external
damper via an insulated splices-closed barrel connector (0.75mm²).
Make sure that the wire is NOT taut. The electrical circuit requires a
current protection of 3A and a maximum voltage of 250V.
X24A will close the contact when the heat reclaim ventilation fan
starts operating and it will open the contact when the fan is stopped.
6.5.4 Power supply connection, control wire
terminals and switches on the PCB
To connect the power supply
1Connect the power supply to the L and N terminals.
2Secure the power supply with the power supply clamp, as
shown in "6.5.2Opening the switch box"on page17.
3Be sure to connect the earth wire.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48