34-350XL

Zurn-Wilkins 34-350XL, 1-350XL, 1-350XLFT Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Zurn-Wilkins 34-350XL Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766
OUTDOOR INSTALLATION
The Model 350XL Backow Preventer may
be installed outdoors only if the device is pro-
tected against freezing conditions. Exposure
to freezing conditions will result in improper
function or damage to the device. The instal-
lation location must be kept above 32°F. All
the basic installation instructions apply.
Installation Testing Maintenance Instructions
1
INSTALLATION INSTRUCTIONS
CAUTION: Installation of Backow Preventers must be performed by qualied, licensed
personnel. The installer should be sure the proper device has been selected for the par-
ticular installation. Faulty installation could result in an improperly functioning device.
ZURN WILKINS Model 350XL Double Check Valve assemblies are for use on potable
water lines where a health hazard does not exist in the event of a backow situation.
Damage to the device could result wherever water hammer and/or water thermal expan-
sion could create excessive line pressure. Where this could occur, shock arresters, check
valves and/or pressure relief valves should be installed downstream of the device.
If installation is in a pit or vault, the Backow Preventer must never be submerged in
water because this could cause a cross-connection. Make sure that the pit or vault always
remains dry by providing ample drainage.
1. Before installing a Model 350XL Backow Preventer, ush the line thoroughly to
remove all debris, chips and other foreign matter. If required, a strainer should be
placed upstream of the Backow Preventer. CAUTION: Do not use a strainer in
seldom used emergency waterlines such as re lines.
2. Provide adequate space around the installed unit so that the test cocks will be
accessible for testing and servicing.
3. Install valve at least 12 inches above surrounding ood level.
4. Always consult local codes for installation methods, approvals and guidance.
INDOOR INSTALLATION
Indoor installation is preferred in areas that
are subject to freezing conditions. All the
basic installation instructions apply to such
installations.
PLACING THE MODEL 350XL IN SERVICE
1. Start with both shut-off valves closed.
Slowly open the inlet shut-off valve until the
backow preventer is completely pressur-
ized.
2. When the unit has been pressurized,
vent any trapped air by slightly opening
each of the four test cocks.
3. Slowly open the downstream shut-off
valve. The Model 350XL Double Check
Valve assembly is now in service.
4. After the Model 350XL has been prop-
erly installed, test the device (see “TEST
PROCEDURES”). If the device fails the
test, remove the rst and second check
valves and thoroughly ush the device.
Clean rubber and seats of all debris and
place unit back in service.
VERTICAL INSTALLATION
Vertical installation is acceptable in appli-
cations where inlet and outlet piping are
owing vertically upwards. All the basic
installation instructions apply to such
installations. Consult factory for approval
status.
Model 350XL LEAD-FREE*
Double Check Valve Assembly (3/4” & 1”)
*This product contains a weighted average lead content less than 0.25% for wetted surfaces.
*Certied to NSF/ANSI 61-G
DIRECTION OF FLOW
WILKINS 350XL
DIRECTION OF FLOW
WILKINS 350XL
DIRECTION OF FLOW
WILKINS 350XL
PROTECTIVE
ENCLOSURE
DIRECTION OF FLOW
12" MIN.
30" MAX.
OPTIONAL LEAD-FREE STRAINER
(MODEL SXL)
WILKINS 350XL
®
www.zurn.com
®
Testing Procedures
2
ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766
MODEL 350XL DOUBLE CHECK VALVE ASSEMBLY
Equipment Required: Differential pressure gauge test kit.
TEST NO. 1 - TIGHTNESS OF #1 CHECK VALVE
REQUIREMENT:
The static pressure drop across check valve #1 shall be at least
1.0 psid. If test cock #3 is not at the highest point of the check
valve body, then a vertical tube must be installed on test cock #3
so that it rises to the top of the check valve body.
PROCEDURE:
1. Slowly open all 4 test cocks to remove any foreign material
and attach ttings.
2. Attach hose from the high side of the test kit to the #2 test cock.
3. Open test cock #2 and bleed all air from the hose and gauge
by opening the high side bleed needle valve. Close high side
bleed needle valve. If a tube is attached to test cock #3, open
test cock #3 to ll the tube. Close test cock #3. Close #2
shut-off valve then close the #1 shut-off valve.
4. Hold gauge at same level as test cock #3 or water level in
tube. Slowly open test cock #3. Record the static pressure drop
across check valve #1 after gauge reading stabilizes and
water stops running out of test cock #3.
5. Close all test cocks, open shut-off valve #1 and remove test
equipment.
TEST NO. 2 - TIGHTNESS OF #2 CHECK VALVE
REQUIREMENT:
The static pressure drop across check valve #2 shall be at least
1.0 psid. If test cock #4 is not at the highest point of the check
valve body, then a vertical tube must be installed on test cock #4
so that it rises to the top of the check valve body.
PROCEDURE:
1. Attach hose from the high side of the test kit to the #3 test cock.
2. Open test cock #3 and bleed all air from the hose and gauge
by opening the high side bleed needle valve. Close high side
bleed needle valve. If a tube is attached to test cock #4,
open test cock #4 to ll the tube. Close test cock #4.
Close #1 shut-off valve.
3. Hold gauge at same level as test cock #4 or water level
in tube. Slowly open test cock #4. Record the static pressure
drop across check valve #2 after gauge reading stabilizes
and water stops running out of test cock #4.
4. Close all test cocks, slowly open shut-off valve #1 & #2 and
remove test equipment.
VENT HOSE
LOW SIDE HOSE
HIGH SIDE HOSE
LOW SIDE BLEED
NEEDLE VALVE
#1 TEST COCK
#2 TEST COCK
#3 TEST COCK
#4 TEST COCK
#1 SHUT-OFF
VALVE
#2 SHUT-OFF
VALVE
HIGH SIDE BLEED
NEEDLE VALVE
WILKINS 350XL
®
www.zurn.com
No. 1
Test Cock
No. 2
Test Cock
No. 3
Test Cock
No. 4
Test Cock
Housing
Inlet
Ball Valve
Outlet
Ball Valve
Body
#1 Check
Assembly
#2 Check
Assembly
Inlet
O-ring
Outlet
O-ring
#1 Check
O-ring
#2 Check
O-ring
Spring
Poppet
Tailpiece
Hex Flange Bolts
#1 Seat
#2 Seat
Maintenance Instructions
ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766
3
FIGURE 1 FIGURE 2 FIGURE 3
Spring
Seat
Poppet
Tailpiece
CHECK ASSEMBLY
All Model 350XL Double Check Valve Backow Preventers must
be inspected and maintained by licensed personnel at least once
a year or more frequently as specied by local codes. Replace-
ment of worn or damaged parts must only be made with genuine
“ZURN WILKINS” parts.
GENERAL MAINTENANCE
1. Clean all parts thoroughly with water after disassembly.
2. Carefully inspect rubber seal rings and o-rings for damage.
3. Test unit after reassembly for proper operation (refer to
“TESTING PROCEDURES”).
SERVICING CHECK VALVES
1. Close inlet and outlet shut-off valves.
2. Open No. 2, No. 3 and No. 4 test cocks to release pressure
from valve.
3. Unscrew the 4 bolts (1/4-20 UNC Hex Flange) holding the
housing in place.
4. Using a #2 athead screwdriver, pry loose housing by placing
the screwdriver in the notch between housing and body.
5. Pull housing out of the body and remove checks by sliding
them towards the outlet of housing.
6. Using the same screwdriver, locate the notch between seat
and tailpiece of each check. Insert screwdriver and twist to
“snap” checks apart. CAUTION: Checks are spring loaded.
7. Inspect the rubber seal ring around poppet for cuts or
embedded debris.
8. If the poppet is damaged, replace with a new poppet.
9. Inspect the remaining check parts and seating areas.
Remove any debris.
10. If necessary, replace any damaged parts with new ones.
11. Lightly grease o-rings on checks and reinstall into housing
following the above procedures in reverse order.
12. Flush body prior to reinstalling housing.
13. Lightly grease o-rings on housing and reinstall into body
following the above procedures in reverse order.
Note: When installing housing, match slight taper on the outlet of
the housing with corresponding taper in body.
®
www.zurn.com
ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766
MODEL 350XL 3/4" & 1" (STANDARD & METRIC)
0
5
10
15
0 20 40 60 80
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
0
34
69
103
0.00 1.26 2.52 3.79 5.05
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
IS350XL 34-1 (REV. 4/13)
4
Performance Characteristics
Troubleshooting
PROBLEM
1. LEAKING CHECK VALVES
2. LOW OR NO FLOW
POSSIBLE CAUSES
1. Debris on seat or seal ring
2. Damaged seat
3. Damaged seal ring
4. Damaged check o-ring
1. Device installed backwards
2. Shut-off valves or valve upstream
may not be fully open
3. Low supply pressure
CORRECTIVE ACTION
1. Clean seat and seal ring area
2. Replace seat
3. Replace poppet
4. Replace check o-ring
FLOW CHARACTERISTICS
3/4" (20mm)
1" (25mm)
SPECIFICATIONS
Maximum working water pressure 175 PSI
Maximum working water temperature 180°F
Hydrostatic test pressure 350 PSI
End connections Threaded ANSI B1.20.1
Capacity thru Schedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
1/8" 1 1 2 3
1/4" 2 2 3 5
3/8" 3 4 6 9
1/2" 5 7 9 14
3/4" 8 12 17 25
1" 13 20 27 40
1 1/4" 23 35 47 70
1 1/2" 32 48 63 95
2" 52 78 105 167
Proper performance is dependent upon licensed, qualied personnel performing regular, periodic testing according to ZURN
WILKINS’
specications and prevailing governmental & industry standards and codes and upon following these installation in-
structions. Failure to do so releases ZURN WILKINS of any liability that it might otherwise have with respect to that device. Such
failure could also result in an improperly functioning device.
Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects
or other reproductive harm.
®
www.zurn.com
/