ZTE ZXCLOUD R5300 G3 Maintenance Manual

  • Hello! I am an AI chatbot trained to assist you with the ZTE ZXCLOUD R5300 G3 Maintenance Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
ZXCLOUDR5300G3
RackServer
MaintenanceGuide
Version:V1.0
ZTECORPORATION
No.55,Hi-techRoadSouth,ShenZhen,P .R.China
Postcode:518057
Tel:+86-755-26771900
Fax:+86-755-26770801
URL:http://support.zte.com.cn
LEGALINFORMATION
Copyright©2015ZTECORPORATION.
Thecontentsofthisdocumentareprotectedbycopyrightlawsandinternationaltreaties.Anyreproductionor
distributionofthisdocumentoranyportionofthisdocument,inanyformbyanymeans,withoutthepriorwritten
consentofZTECORPORATIONisprohibited.Additionally,thecontentsofthisdocumentareprotectedby
contractualcondentialityobligations.
Allcompany,brandandproductnamesaretradeorservicemarks,orregisteredtradeorservicemarks,ofZTE
CORPORATIONoroftheirrespectiveowners.
Thisdocumentisprovided“asis”,andallexpress,implied,orstatutorywarranties,representationsorconditions
aredisclaimed,includingwithoutlimitationanyimpliedwarrantyofmerchantability,tnessforaparticularpurpose,
titleornon-infringement.ZTECORPORATIONanditslicensorsshallnotbeliablefordamagesresultingfromthe
useoforrelianceontheinformationcontainedherein.
ZTECORPORATIONoritslicensorsmayhavecurrentorpendingintellectualpropertyrightsorapplications
coveringthesubjectmatterofthisdocument.ExceptasexpresslyprovidedinanywrittenlicensebetweenZTE
CORPORATIONanditslicensee,theuserofthisdocumentshallnotacquireanylicensetothesubjectmatter
herein.
ZTECORPORATIONreservestherighttoupgradeormaketechnicalchangetothisproductwithoutfurthernotice.
UsersmayvisittheZTEtechnicalsupportwebsitehttp://support.zte.com.cntoinquireforrelatedinformation.
TheultimaterighttointerpretthisproductresidesinZTECORPORATION.
RevisionHistory
RevisionNo.RevisionDateRevisionReason
R1.02015-03-20
SerialNumber:SJ-20150306151222-003
PublishingDate:2015-03-20(R1.0)
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
AboutThisManual
Purpose
Thismanualdescribesthemaintenanceoperationsandtroubleshootingmethodsforthe
server.
IntendedAudience
Thismanualisintendedfor:
lNetworkplanningengineers
lEquipmentinstallationengineers
lMaintenanceengineers
WhatIsinThisManual
Thismanualcontainsthefollowingchapters.
Chapter1,SafetyOverviewDescribesthesafetyinformationandprecautionsthatmaintenance
personnelshouldknow.
Chapter2,Maintenance
Operations
Describeshowtorestarttheserverandqueryalarminformation.
Chapter3,TroubleshootingDescribeshowtotroubleshootcommonfaults.
Conventions
Thismanualusesthefollowingconventions.
Note:providesadditionalinformationaboutatopic.
I
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
Thispageintentionallyleftblank.
II
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
Chapter1
SafetyOverview
TableofContents
SafetyInformation......................................................................................................1-1
SafetyInstructions......................................................................................................1-1
1.1SafetyInformation
Maintenancepersonnelshouldknowthefollowingsecurityinformation:
lToreducetheriskofbodilyinjury,electricalshock,re,andequipmentdamage,
readthischapterandobserveallwarningsandprecautionsinitbeforemaintaining
theserver.Thesafetyinstructionsinthismanualdonotrepresentallthesafety
instructions.Theyareonlysupplementstothesafetyinstructions.
lTheservermustbeintegratedandmaintainedbytechnicallyqualiedpersons.ZTE
Corporationdisclaimsanyresponsibilitycausedbytheviolationsofgeneralsafety
operationrequirementsorsafetystandardsforequipmentdesign,production,and
usage.
1.2SafetyInstructions
Maintenancepersonnelshouldknowthefollowingsafetyconsiderations:
lEquipmentoperationspecications
àConformtolocaloccupationalhealthandsafetyrequirementswhenyouare
movingandliftingequipment.
àUsemechanicalassistanceorothersuitableassistancewhenmovingandlifting
equipment.
lPowerandelectricalwarnings
àMakesurethatthepowercablesareunpluggedbeforeyoureplaceorinstall
hardwarecomponentsontheserver.
àThepowersupplyinthisproductcontainsnouser-serviceableparts.Donotopen
thepowersupply.
lSystemaccesswarnings
àIftheserverhasbeenrunning,anyinstalledprocessorsmaybehot.T oavoidthe
possibilityofcontactwithhotcomponentsduringthemaintenanceprocess,allow
thesystemtocoolbeforeopeningthecoveroftheserver.
1-1
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
ZXCLOUDR5300G3MaintenanceGuide
àToavoidpersonalinjuryordevicedamage,donotcontactmovingfanmodules
beforethefanmodulesarepoweredoff.Ifthereisaguardoverthefan,donot
operatethesystemwithoutthefanguardinplace.
àUseonlycopyrightedsoftwareontheservertopreventtheserverfrombeing
attackedbyviruses.
lElectrostaticdischarge
Whenyoudisassembleandreassembletheserver,wearanESDwriststrapthatis
properlygrounded.
lCoolingandairow
àTokeepwellventilation,makesurethatthewindinletandoutletoftheserverare
notcoveredbyanything.
àToensurethecoolingcapabilityofthesystem,makesurethatallrequired
componentsareinstalledintheserver.
1-2
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
Chapter2
MaintenanceOperations
TableofContents
RestartingtheServer.................................................................................................2-1
QueryingAlarmInformation........................................................................................2-1
2.1RestartingtheServer
Iftheserverisfaulty,youcanrestarttheservertoseewhethertheservercanberecovered.
Steps
1.Performthecorrespondingoperationsasneeded:
To...Do...
Restarttheserverinasoftwareway,releasethesystem
memory,andrestarttheoperatingsystem
PressCtrl+Alt+Del.
Releasethesystemmemory,performthePOSTself-test
again,restarttheoperatingsystem,andrebootall
peripherals
Pressdownthepowerbuttononthe
frontcontrolpaneloftheserver.
EndofSteps
2.2QueryingAlarmInformation
Queryingalarminformationisacommonmethodformaintainingthe.Thealarm
informationhelpsyouverifyfailurecauses.
Youcanquerythecurrentandhistoricalalarmsandnoticationsoftheserversystem.This
proceduredescribeshowtoquerythecurrentalarms.
lCurrentalarms:alarmsthatexistinthesystemandarenotcleared.
lHistoricalalarms:alarmsthathavebeenclearedandarestoredinthedatabase.
lNotications:informationalpromptsgeneratedinthesystemoperation.Notications
allowmaintenancepersonneltoknowtheoperationalstatusofeachmoduleintime.
Context
Alarmsaredividedintofourlevelsaccordingtoeffectsonthesystem.Fordetails,referto
Table2-1.
2-1
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
ZXCLOUDR5300G3MaintenanceGuide
Table2-1AlarmLevels
LevelDescription
CriticalIndicatesthatthenormalserviceisaffectedseverelyandthatthealarmmustbe
clearedimmediately.
MajorIndicatesasymptomaffectingthenormalservice.Thisalarmmustbecleared
immediately.
MinorIndicatesthatafactornotaffectingthenormalservicesexistsinthesystem.
Correctiveactionsarerequiredtopreventworseproblems.
WarningIndicatesapotentialproblemoraproblemthatmayaffectthenormalservicesoon.
Adiagnosisisrequiredtopreventthealarmfrombecomingaworseproblemthat
affectsnormalserviceoperation.
Steps
1.OnthenavigationbarintheWebpageoftheBMC,selectAlarm>CurrentAlarm.
TheCurrentAlarmpageisdisplayed,seeFigure2-1.
Figure2-1CurrentAlarm
2.(Optional)UnderQueryFilter,selecttheltercriteria,andthenclickQuerytoquery
thecurrentalarmsmeetingthecriteria.
Ifnoltercriteriaareset,allcurrentalarmsaredisplayed.
3.(Optional)Selectoneormultiplecurrentalarms,andthenacknowledge,
unacknowledge,ordeletethem.
lAcknowledginganalarmconvertsthealarmfromtheUnacknowledgestatusto
theAcknowledgestatus.Itisrecommendedthatyouacknowledgeanalarm
beforeyouhandleit.
lIfyoucannotclearthealarm,youcanreturnthisalarmtotheunacknowledged
status.
EndofSteps
2-2
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
Chapter3
Troubleshooting
TableofContents
CannotOpentheKVMRemoteManagementPage....................................................3-1
SystemCannotBePoweredOn.................................................................................3-7
MonitorDisplaysNothing............................................................................................3-8
KeyboardandMouseCannotOperate.......................................................................
3-8
TroubleshootingSystemStartupFailures...................................................................3-9
TroubleshootingPowerSupplies................................................................................
3-9
TroubleshootingCoolingFans....................................................................................3-9
TroubleshootingHardDisks.....................................................................................3-10
TroubleshootingExpansionCards............................................................................
3-10
3.1CannotOpentheKVMRemoteManagementPage
Symptom
WhentheKVMoftheclientPCconnectstotheserverremotely,themonitordisplays
nothing.
ProbableCause
lIftheJREisnotinstalled,theWebbrowserpromptsyoutodownloadandinstallthe
plug-inmanually.
lIftheKVMRemoteManagementpagestillcannotbeopenedaftertheJREisinstalled,
theremaybeaprobleminthebrowsersetting.
Note:
InternetExplorer8andFirefoxarerecommended.Thefollowingdescribeshowtoset
InternetExplorer8.
Action
AddingtheBMCNetworkManagementSystemAddresstotheTrustedSitesZone
1.OntheIEmenubar,selectTools>InternetOptions.TheInternetOptionsdialog
boxisdisplayed.
2.ClicktheSecuritytab.SeeFigure3-1.
3-1
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
ZXCLOUDR5300G3MaintenanceGuide
Figure3-1InternetOptionsDialogBox—SecurityTab
3.ClicktheTrustedsitesicon,andthenclicktheSitesbutton.TheTrustedsitesdialog
boxisdisplayed,seeFigure3-2.
3-2
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
Chapter3Troubleshooting
Figure3-2TrustedsitesDialogBox
4.UnderAddthiswebsitetothezone,enterthenetworkmanagementsystemaddress
oftheBMC,forexample,https://192.168.5.7.
5.CleartheRequireserververication(https:)forallsitesinthiszonecheckbox.
6.ClickAdd.
7.ClickClose.
SettingtheSecurityLevelforTrustedSites
8.IntheInternetOptionsdialogbox(seeFigure3-1),clicktheTrustedsitesicon,and
thenclicktheCustomlevelbutton.TheSecuritySettings-TrustedSitesZone
dialogboxisdisplayed.
9.ExpandActiveXcontrolsandplug-ins,andthenselecttheEnableoptionboxforall
sub-items,seeFigure3-3.
3-3
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
ZXCLOUDR5300G3MaintenanceGuide
Figure3-3ActiveXControlsandPlug-insOptions
10.ExpandDownloads,andthenselecttheEnableoptionboxforallsub-items,see
Figure3-4.
3-4
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
Chapter3Troubleshooting
Figure3-4DownloadsOptions
11.ClickOK.
SettingIEBrowsingHistory
12.ClicktheGeneraltabintheInternetOptionsdialogbox,seeFigure3-5.
3-5
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
ZXCLOUDR5300G3MaintenanceGuide
Figure3-5InternetOptionsDialogBox—GeneralTab
13.SelecttheDeletebrowsinghistoryonexitcheckbox.
14.ClicktheSettingsbutton.TheTemporaryInternetFilesandHistorySettingsdialog
boxisdisplayed,seeFigure3-6.
3-6
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
Chapter3Troubleshooting
Figure3-6TemporaryInternetFilesandHistorySettingsDialogBox
15.SelectEverytimeIvisitthewebpage.
16.ClickOK.
StartingtheIEBrowser
17.RestarttheIEbrowsertovalidatetheconguration.
3.2SystemCannotBePoweredOn
Symptom
Thepowerindicatorisnotlitafterthepowerswitchispressed.Theserversystemhasno
powersupply.
ProbableCause
Theserversystemisnotpoweredonorthecableisconnectedincorrectly.
3-7
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
ZXCLOUDR5300G3MaintenanceGuide
Action
1.Verifythatthepoweroutletcansupplypowerproperlyandthepowercableis
connectedcorrectly.
2.Pressthepowerswitchseveraltimestopowerontheserversystem.
3.Disconnectthepowercableoftheserversystem,andthenopenthecoverplateofthe
serverchassis.Verifythatintheserverchassisthecableconnectionsarecorrectand
thettingsareinstalledsecurely.
4.Removetheexternalplug-indevices.
5.Installthecoverplateoftheserverchassisandpowercable,andthenpoweronthe
serveragain.
3.3MonitorDisplaysNothing
Symptom
Theserversystemispoweredon,thehostisoperatingproperly,butthemonitordisplays
nothing.
ProbableCause
Thesignalcableisnotconnectedorsetincorrectly.
Action
1.Verifythatthesignalcableandthepowercableofthemonitorareconnectedproperly
andsecured.
2.Verifythatthemonitoristurnedon.
3.Adjustthecontrastandlightnessofthemonitor.
4.Turnofftheserversystem,disconnectthepowercable,andthenverifythatthepins
ofthesignalcableplugthatisconnectedtothehostarebent.
5.Replacethemonitorwithanothermonitorfortesting.
3.4KeyboardandMouseCannotOperate
Symptom
Theserversystemispoweredon,thehostisoperatingproperly,butthekeyboardand
mousefailtooperate.
ProbableCause
Themouseandkeyboardarenotconnectedorsetincorrectly.
Action
1.Verifythatthecablesofthemouseandkeyboardareconnectedproperly.
3-8
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
Chapter3Troubleshooting
2.Verifythattheconnectorpinsarenotbent.
3.Verifythatthemousesettingsarecorrect.
4.Cleanthescrollwheelandaxes.
5.Replacethekeyboardandmouse.
3.5TroubleshootingSystemStartupFailures
IfyoubootthesystemtotheBIOSbootmodeafterinstallinganoperatingsystemfromthe
UEFIBootManager,thesystemissuspended,andviceversa.Youmustbootthesystem
tothesamebootmodeinwhichyouinstalledtheoperatingsystem.
Forallotherstartupfailures,notethesystemmessagesdisplayedonthescreen.
3.6TroubleshootingPowerSupplies
Note:
Atleastonepowersupplymustbeinstalledfornormalsystemoperation.Afterapower
supplyisinstalled,waitforseveralminutesforthesystemtoidentifythispowersupply.
1.Identifyafaultypowersupplybyusingthefaultindicatoronthispowersupply.
2.Removeandinstallthepowersupplyagain.Ifthefaultpersists,replacethispower
supply.
3.7TroubleshootingCoolingFans
1.Openthecabinetcoverplate.
2.LocatethefaultyfanindicatedbytheESM.
3.Re-installthefanorthefan'spowercable.
Note:
Waitforatleast30secondsforthesystemtoidentifythefananddeterminewhether
itisoperatingproperly.
4.Ifthefaultpersists,replacethefaultyfanwithasparefan.
3-9
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
ZXCLOUDR5300G3MaintenanceGuide
3.8TroubleshootingHardDisks
Runtheappropriatediagnostictest.Dependingontheresultsofthediagnosticstest,
performthefollowingsteps:
1.Restartthesystem,andpressF10duringsystemstartuptoruntheLifecycle
Controller,andthenruntheHardwareCongurationwizardtochecktheRAID
conguration.
2.EnsurethattheharddriveshavebeenconguredcorrectlyfortheRAIDarray.Ifa
harddriveintheRAIDisfaulty,keeptheharddriveofineandresetthedrive.
3.Exitthecongurationutilityandallowthesystemtoboottotheoperatingsystem.
4.Ensurethattherequireddevicedriversareinstalledandconguredcorrectly.
5.VerifythatthecontrollerisenabledandthedrivesaredisplayedintheSystemSetup.
3.9TroubleshootingExpansionCards
Runtheappropriatediagnostictest.Dependingontheresultsofthediagnosticstest,
performthefollowingsteps:
1.Turnoffthesystemanditsperipherals,anddisconnectthesystemfromthepower
source.
2.Openthecabinetcoverplate.
3.Ensurethateachexpansioncardisrmlyinstalledinitsconnector.
4.Closethecabinetcoverplate,andpoweronthesystem.
5.Ifthefaultpersists,openthecabinetcoverplate,removeallexpansioncards,and
theninstallthemagain.
6.Closethecabinetcoverplate.
3-10
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
Glossary
BMC
-BaseboardManagementController
JRE
-JavaRuntimeEnvironment
KVM
-Keyboard,VideoandMouse
PC
-PersonalComputer
POST
-Power-OnSelf-Test
I
SJ-20150306151222-003|2015-03-20(R1.0)ZTEProprietaryandCondential
/