Vimar 01470.1 Installation guide

Type
Installation guide
Viale Vicenza 14
36063 Marostica VI - Italy
www.vimar.com
01470.1SEN 02 1908
01470.1
EXAMPLE OF “HOTEL CLIMATE CONTROL” CONFIGURATION
INPUT ACTION OUTPUT
I1: Entrance door contact. On opening, if there is nobody present in the room the courtesy
light comes on for 30 s.
O1: Courtesy light circuit (the circuit is made
upstream from O2).
I2: Contact on badge switch or pres-
ence detector.
It switches off the courtesy light and enables the “Welcome” sce-
nario when the first presence in the room is detected; 10 minutes
after detecting that there is no presence in the room, it switches
off the lights, loads (activated with the “Welcome” scenario) and
the “Do not disturb” signal.
O2: FM radio line, lights line, IN/OUT signal
for landing calls and/or signalling in re-
ception (there must be a contactor with
3 NO and 1 NC).
I3: Fancoil selector 1. Fancoil management mode:
- when first entering the room, if the set point set manually on the
thermostat allows, activate V2 to reach the set temperature.
- after this the speed is managed using the slide switch 20095.
O3: V1 fancoil
I4: Fancoil selector 2. O4: V2 fancoil.
I5: Fancoil selector 3. O5: V3 fancoil.
I6: Thermostat contact.
When the contact is closed relay O6 is closed (output for room
solenoid valve or for summer-winter selector) only if I9 is closed,
while when the contact is opened relay O6 is opened.
O6: Connection to the heating solenoid valve
or, if present, input to the summer/winter
selector.
I7: Push button for additional heating
(for example, towel heater).
A long (< 2 s) or short press of the push button and the detection
of presence in the room switch on the towel heater; it is switched
off by another long or short press of the push button or when there
is no longer anyone present in the room.
O7: Additional heating line (for example, tow-
el heater).
I8: Ceiling pull. ON landing call alarm and/or signalling in reception.
Reset the alarm with a long press (5 s) on push button I7. O8: Alarm signalling light.
I9: Window contact. When is opened the fancoil outputs are deactivated while when it
is closed the previous operation is restored. -
01400
POWER SUPPLY
By-me
230V~
230V~
AUX
NL
150mA
29V
BUS +AUX
≤400mA
50/60Hz
29V
+
BUS
+
01470.1
9IN/8OUT
OUT6
OUT5
OUT7
OUT8
OUT2
OUT1
OUT3
OUT4
CONF.
By-me
16A
μ
3,5A
120-230V ~
ID:
M
50/60Hz
08
I1 I2 I3 I4 I5 I6 I7 I8 I9
C C C C C
CC
07 06
CC
05 04
CC
03 02
CC
01
6 mm
L N IN NC NO C
- T40
5(2)A
1.B
120-230V~
50/60Hz
6 mm
3 2
1L
6 mm
120-230V~ 50/60Hz 4A
CN0 L N
µ
2A
M
10mm
L
1
10mm
L
1
V1
V2V3
Landing
alarm call Bathroom
heating line
(Boiler and/or
towel heater)
Heating solenoid
valve (SV)
Fancoil Courtesy
light
Contactor
Presence in room
Contactor output contacts:
• 1 NO FM radio line
• 1 NO lights line
• 1 NO IN/OUT signal
• 1 NC multi-function thermostat input
for temperature reduction
Thermostat 02950
Connection to NC
contactor contact for
signalling presence
in room
Badge switch
20463 or 20465
Entrance door
contact Window
contact
Switch
20095 Push button
20008 for
additional heating
Ceiling
pull
20053
Viale Vicenza 14
36063 Marostica VI - Italy
www.vimar.com
01470.1SEN 02 1908
01470.1
EXAMPLE OF “HOTEL LIGHTS” CONFIGURATION
INPUT ACTION OUTPUT
I1: Entrance door contact. On opening, if there is nobody present in the room the courtesy
light comes on for 30 s. O1: Courtesy light circuit.
I2: Contact on badge switch or pres-
ence detector.
It switches off the courtesy light and enables the “Welcome” sce-
nario when the first presence in the room is detected; 10 minutes
after detecting that there is no presence in the room, it switches
off the lights, loads (activated with the “Welcome” scenario) and
the “Do not disturb” signal.
O2: FM radio line, lights line, IN/OUT signal
for landing calls and/or signalling in re-
ception (there must be a contactor with
3 NO and 1 NC).
I3: Bathroom light push button. Bathroom light toggle ON/OFF. O3: Bathroom light circuit.
I4: Bedside table light A push button. Bedside table A light toggle ON/OFF. O4: Bedside table light A circuit.
I5: Bedside table light B push button. Bedside table B light toggle ON/OFF. O5: Bedside table light B circuit.
I6: Room light push button. Room light toggle ON/OFF. O6: Room light circuit.
I7: “Do not disturb” push button.
“Do not disturb” signal ON/OFF.
Cancelled if there is no longer a presence in the room.
A long press cancels the ceiling pull alarm.
O7: IN/OUT signalling (inside and outside the
room).
I8: Ceiling pull. ON landing call alarm and/or signalling in reception.
Reset the alarm with a long press (5 s) on push button I7. O8: Alarm signalling light.
I9: Lights OFF push button.
Switches off all the lights; if other devices 01470.1 in Plug & Play
configuration are connected, it switches off the lights and lowers
the roller shutters. -
01400
POWER SUPPLY
By-me
230V~
230V~
AUX
NL
150mA
29V
BUS +AUX
≤400mA
50/60Hz
29V
+
BUS
+
01470.1
9IN/8OUT
OUT6
OUT5
OUT7
OUT8
OUT2
OUT1
OUT3
OUT4
CONF.
By-me
16A
μ
3,5A
120-230V ~
ID:
M
50/60Hz
08
I1 I2 I3 I4 I5 I6 I7 I8 I9
C C C C C
CC
07 06
CC
05 04
CC
03 02
CC
01
6 mm
120-230V~ 50/60Hz 4A
CN0 L N
µ
2A
M
10mm
L
1
10mm
L
1
10mm
L
1
10mm
L
1
10mm
L
1
10mm
L
1
10mm
L
1
DO NOT
DISTURB
20026.DND
“Do not disturb”
signal
Room
light
Bedside
table B
Bedside
table A
Bathroom
Bathroom light
push button
20008
Bedside table
light B push
button 20008
Room light
push button
20008
“Do not disturb”
light push button
20008
Lights OFF
push button
20008
Badge switch
20463 or 20465
Landing
alarm call
Presence in room
Contactor output contacts:
• 1 NO FM radio line
• 1 NO lights line
• 1 NO IN signal
• 1 NC OUT signal
Contactor
Courtesy
light
Ceiling
pull
20053
Bedside table
light A push
button 20008
Entrance door
contact
  • Page 1 1