InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
DesiredowT(Desiredowtemperature)
Read-
out
Read-outofthedesiredowtemperature.
---:
Theoordryingprocessisnotactive
Value:
Theoordryingprocessisactive
Pushthedialto:
•select/deselectcircuit(s)foroordrying
•enter/changethegraphofthe"Functionalheating"or"Curing
heating"process
Thedesiredowtemperaturecanbesetat:
•X1,X2,X3andX4(Functionalheating)
•X5,X6,X7andX8(Curingheating)
Selectionofcircuit(s)foroordrying:
Circuitnumberselected
Circuitnumbernotselected
Examplesofgraph:
TimesforX1,X2,X3andX4arethesame(0h)
DesiredtemperatureatX1is20°C
DesiredtemperatureatX2is20°C
DesiredtemperatureatX3is20°C
DesiredtemperatureatX4is20°C
TimesforX1,X2,X3andX4aredifferent,asshown.
DesiredtemperatureatX1is20°C
DesiredtemperatureatX2is50°C
DesiredtemperatureatX3is50°C
DesiredtemperatureatX4is20°C
Important:Thedesiredowtemperaturevalues,setatX4andX8are
usedascontrollingtemperatures:
•aftertheoordryingprocess,iftheapplicationisnottobestarted
•afterapowerfailure
Applicationwithoneheatingcircuit:
Iftheoordryingprocessisinoperationandthecircuit,byaccident,is
changednottobeselected,theoordryingprocessmustberestarted.
Applicationwithtwoorthreeheatingcircuits:
Iftheoordryingprocessisinoperationfortwoorthreecircuitsand
oneofthecircuits,byaccident,ischangednottobeselected,theoor
dryingprocesscontinues.Justselectthecircuitinquestionagain.