Ruck CON P1000 Owner's manual

Type
Owner's manual
English
Assembly and Operating Manual
CON P1000
Constant pressure control
www.ruck.eu
2
English
Tel. +49 7930 9211-0 Fax. +49 7930 9211-150
Information updated: print 28.11.2023
We reserve the right to make changes
The data specied above only serve to describe the product.
No statements concerning a certain condition or suitability for
a certain application can be derived from our information. The
information given does not release the user from the obligati-
on of own judgment and verication.
It must be remembered that our products are subject to a
natural process of wear and aging.
This document, as well as the data, specications and other
information set forth in it, are the exclusive property of ruck
Ventilatoren GmbH.
It may not be reproduced or given to third parties without its
consent.
The picture on the cover shows an example conguration.
The product supplied may therefore differ from the illustration.
The original manual has been produced
in the German language.
mysc_pb_03d_k10001_en print 28.11.2023
ruck Ventilatoren GmbH Max-Planck-Str. 5 D-97944 Boxberg-Windischbuch Tel. +49 7930 9211-0 Fax. +49 7930 9211-150 [email protected]
3
English
www.ruck.eu
Contents
Assembly and Operating Manual
1. Important information 4
1.1. Rules and regulations 4
1.2. Guarantee and liability 4
2. General safety instructions 4
2.1. Intended use 4
2.2. Improper use 4
2.3. Personnel qualications 5
2.4. Safety instructions in this manual 5
2.5. Adhere to the following instructions 5
2.5.1. General instructions 5
2.5.2. During installation 5
2.5.3. During commissioning 6
2.5.4. During operation 6
2.5.5. During maintenance and repair 6
2.5.6. Disposal 6
3. Delivery contents 6
4. Product and Performance description 6
4.1. Device description 6
5. Transport and storage 7
6. Assembly 7
7. Electrical connection 7
8. Commissioning 9
9. Operation 9
9.1. Operation without a control unit 9
9.2. Operation with a control unit (optionally) 9
9.2.1. Adjustment of the control unit parameter 10
9.2.2. Menu functions 10
9.2.3. Parameter settings Menu 11
9.2.4. Time / Time switch 12
9.2.5. Changing the battery 15
10. Maintenance and repair 15
10.1. Important notes 15
10.2. Cleaning and care 15
11. Modbus communication interface 16
11.1. Wiring diagram 16
11.2. Interface information 16
11.3. Functions implemented 17
11.4. Parameter table 17
11.5. Current value table 18
12. Expansionandreconguration 18
13. Dismantling and disposal 18
13.1. Disassembling the product. 19
13.2. Disposal 19
14. Troubleshooting 19
14.1. Possible operating faults. 19
15. Technical data 20
16. Wiring diagrams 20
4
English
Tel. +49 7930 9211-0 Fax. +49 7930 9211-150
1. Important information
This manual contains important information on the safe and appropriate assembly, transport, commissio-
ning, operation, maintenance, disassembly and simple troubleshooting of the product.
The product has been manufactured according to the accepted rules of current technology.
There is, however, still a danger of personal injury or damage to equipment if the following general safety
instructions and the warnings before the steps contained in these instructions are not complied with.
Read these instructions completely and thoroughly before working with the product.
Keep these instructions in a location where they are accessible to all users at all times.
Always include the operating instructions when you pass the product on to third parties.
1.1. Rules and regulations
1.2. Guarantee and liability
Also observe the generally applicable, legal or otherwise binding regulations of the European or
national legislation and the rules for the prevention of accidents and for environmental protection
applicable in your country.
ruck products are made to the highest technical standards in accordance with the generally reco-
gnized rules of the profession. They are subject to constant quality control and meet the relevant
requirements when delivered. Because the products are being constantly developed, we reserve the
right to make changes to the products at any time and without prior announcement. We do not accept
any liability for the correctness or completeness of this installation and operating manual.
Thewarrantyonlyappliestothedeliveredconguration.The warranty will not apply if the product
is incorrectly assembled or handled or not used as intended.
2. General safety instructions
2.1. Intended use
Exclusively use ruck Ventilatoren in good technical order and condition.
Check the product for visible defects, for example cracks in the housing or missing rivet, screws
and covers.
Only use the product within the performance range provided in the technical data.
Protection against contact and being sucked in and safety distances should be provided in accor-
dance with DIN EN 13857.
Generally prescribed electrical and mechanical protection devices are to be provided by the client.
Safety components must not be bypassed or put out of operation.
The product may be operated by personnel with limited physical, sensory or mental capacities only if they
are supervised or have been instructed by responsible personnel.
Children must be kept away from the product.
Planners, plant engineers and operators are responsible for ensuring that the product is installed and
operated correctly.
ruck CON P1000 has been designed and developed to comply with the requirements of the EU
Low Voltage Directive 2006/95/EU. Use the CON P1000 in accordance with the EU Low Voltage
Directive, and in conjunction with a device that is to be regulated by the CON P1000.
The device may only be taken into service when it is properly connected and the requirements of
the EU Low Voltage Directive 2006/95/EU are fullled.
Observe the operating conditions and performance limits specied in the technical data.
Intended use includes having read and understood these instructions, especially chapter 2 “General
safety instructions”.
Any use of the product other than described in chapter “Intended use” is considered as improper.
Also note the following points, which are improper and dangerous:
Operation in a potentially explosive atmosphere.
Installation outside without any protection against the weather.
Operation in ambient conditions that require a higher degree of protection than IP55.
2.2. Improper use
5
English
www.ruck.eu
Assembly, commissioning and operation, disassembly and service (including maintenance and
repair) require basic mechanical and electrical knowledge, as well as knowledge of the appropriate
technical terms. In order to ensure operating safety, these activities may therefore only be carried
out by qualied technical personnel or a person under the direction and supervision of qualied
personnel. Qualied personnel are those who can recognize possible hazards and institute the
appropriate safety measures due to their professional training, knowledge, and experience, as
well as their understanding of the relevant conditions pertaining to the work to be done. Qualied
personnel must observe the rules relevant to the subject area.
2.3.Personnelqualications
In this manual, there are safety instructions before the steps whenever there is a danger of perso-
nal injury or damage to the equipment. The measures described to avoid these hazards must be
observed.
2.4. Safety instructions in this manual
Safety instructions are set out as follows:
Safety sign (warning triangle) - Draws attention to the risk
Type of risk - Identies the type or source of the hazard.
» Consequences - Describes what occurs when the safety instructions are not complied with.
→ Precautions - States how the hazard can be avoided.
General warning!
Indicates possible hazardous situations. Failure to observe the warnings
may result in personal injury and / or damage to property.
Electricity warning (hazardous voltage)!
Indicates possible hazards due to electricity. Failure to observe the war-
nings may result in death, injury and/or damage to property.
Important instructions follow!
Instructions for safe, optimum use of the product.
Safety sign
(warning triangle)
Denotation
2.5. Adhere to the following instructions
Observe the provisions for accident prevention and environmental protection for the country
where the product is used and at the workplace.
Persons who assemble, operate, disassemble or maintain ruck products must not consu-
me any alcohol, drugs or pharmaceuticals that may affect their ability to respond.
Responsibilities for the operation, maintenance and regulation of the product should be clear-
ly determined and observed so that there can be no unclear areas of responsibility with regard
to safety.
Never overload the product. Do not place anything on it.
The warranty only applies to the delivered conguration.
The warranty will not apply if the product is incorrectly assembled or handled or not used
as intended.
2.5.1. General instructions
2.5.2. During installation
Disconnect all of the product‘s poles from the mains before installing the product or connec-
ting or removing plugs. Make sure that the product cannot be switched back on again.
Lay cables and lines so that they cannot be damaged and no one can trip over them.
Before commissioning, make sure that all gaskets and seals in the plug-in connections are
correctly tted and undamaged in order to prevent uids and foreign matter getting into the
product.
Information signs must not be changed or removed.
6
English
Tel. +49 7930 9211-0 Fax. +49 7930 9211-150
Make sure that all electrical connections are either used or covered. Commission the product
only if it is installed completely.
2.5.3. During commissioning
2.5.4. During operation
In an emergency, or if there is a fault, or other irregularities, switch the equipment off and make
sure it cannot be switched back on again.
The technical data given on the rating plate must not be exceeded.
2.5.5. During maintenance and repair
If operated correctly, ruck products only require a minimum amount of maintenance. Please
follow all of the instructions given in section 10 in this respect.
Make sure that no connections or components are loosened unless the device is disconnected
from the mains. Make sure that the equipment cannot be switched back on again.
Individual components must not be interchanged. For example, the components intended for one
product may not be used for other products.
2.5.6. Disposal
Dispose the product in accordance with the currently applicable national regulations in your
country.
3. Delivery contents
Included in delivery depending on model type:
1 x CON P1000 Constant pressure control
1 x installation and operating manual
4. Product and Performance description
The ruck Constant Pressure Regulator is used in ventilation plant to maintain a constant pressure level.
The Constant Pressure Regulator is installed in a plastic housing that has degree of protection IP55.
It must be possible to adjust the speed of the fan by means of a 0-10V DC voltage.
Commercially available frequency converters are suitable, as are EC motors.
The regulator can be operated without the control unit, but its use makes commissioning much easier; the
control unit is available as an accessory.
The set-point and current values can be displayed on the control unit.
6
1
4
2
3
5
Legend
1. Cover
2. Differential pressure connections
3. Cable glands M25
4. Cable glands M25/32
5. Cable glands M25
6. Cable glands M32
7. Mounting bracket
4.1. Device description
7
Fig. 1:
CON P1000 Constant pressure control
7
English
www.ruck.eu
5. Transport and storage
6. Assembly
Transport and storage should only be performed by specialist personnel in accordance with the installa-
tion and operating manual and regulations in force.
The following points should be noted and followed:
Check the delivery according to the delivery note to ensure it is complete and correct and check for
any damage. Any missing quantities or damage incurred during transport should be conrmed by the
carrier. No liability is accepted if this is not observed.
Avoid damage or deformation of the housing.
The product must be stored in a dry area and protected from the weather in the original packaging.
Even weatherproof modules should be covered because their weather resistance is only guaranteed
after complete installation.
Storage temperature between –10 °C and +40 °C. Avoid severe temperature uctuations.
Assembly work may only be performed by specialist personnel in accordance with the installation and
operating manual and the regulations and standards in force.
The following points should be noted and followed:
Installation accessories should be provided by the client.
Only suitable installation aids, in accordance with regulations, should be used.
The installation should be easily accessible for maintenance and cleaning and should be easy to
dismantle.
The unit should only be installed with authorized and suitable fastening materials at all fastening
points.
Do not distort the unit when installing.
No holes should be made in the housing, or any screws screwed into it.
7. Electrical connection
Electrical installation may only be performed by qualied electricians in accordance with the installation
and operating manual and the national regulations, standards and guidelines in force:
EN, DIN and VDE specications, including all safety requirements.
Technical connection conditions
Safety at work and accident prevention requirements.
This list does not claim to be complete.
Requirements should be applied under one‘s own personal responsibility.
The following points should be noted and followed:
The electrical connections must be made as shown in the corresponding wiring diagrams and
terminal diagrams.
The type of cable, size of cable and method of laying should be determined by an authorized electri-
cian.
Low and extra-low voltage cables should be laid separately.
An all-pole mains disconnection device with at least 3 mm contact gap must be provided in the supply
line.
Any cable inlets that are not used must be sealed so that it is airtight.
All cable inlets must have strain relief.
Check all protective measures after the electrical connection work (earthing resistance, etc.).
Electricity warning (hazardous voltage)!
» Failure to observe the hazard may result in death, injury or damage to property.
→Beforeperforminganyworkonconductiveparts,alwaysdisconnecttheunitcompletelyfrom
the electricity supply and make sure that it cannot be switched back on again.
8
12
English
Tel. +49 7930 9211-0 Fax. +49 7930 9211-150
Only potential-free contacts may be connected at terminals X3 and X4, and X5 and X6. Applying
an external voltage can seriously damage the regulator.
The regulations for safety extra-low voltages must be observed.
1. Socketforcontrolunit/ModBus (optionally)
2. Power supply 230V AC 50/60Hz
3. X7, X8 Potential-free contact for enabling
frequency converter Imax = 1A
U = 24V
4. X9, X10 Potential-free contact
(set-point reached). Imax = 1A
U = 24V
5. X1 = GND/X2 = 0-10V DC Analog output
6. X3, X4 Open: day-time operation
Closed: night-time operation
7. X5, X6 Open: regulator OFF
Closed: regulator ON
8. Set-point: day 10-990 Pa
9. Set-point: night 10-990 Pa
10a. Pressure + Pressure measurement connec-
tion for 3-6 mm internal diameter hose.
10b. Pressure - Pressure measurement connec-
tion for 3-6 mm internal diameter hose.
11. Fault message input fan
(Tacho In / Fault Relay In)
12. Jumper J1 / J2
The maximum pressure in a ventilation plant must not exceed 5000 Pa.
This would result in severe damage to the regulator.
Control unit connection (optionally)
The control unit is connected to the supply air unit‘s control system with a control cable. A connector on
the control cable is plugged directly into the socket on the control unit from beneath (see Fig. 4). At the
regulator, the control cable passes rst through a cable gland and is then connected at its RJ10 socket on
the regulator PCB.
The control cable must not be shortened. Any excess length must be stowed outside of the housing. If the
cable is too short, extensions can be ordered from the manufacturer or supplier.
Alternatively, a 4-wire data cable with 120 Ohm resistance can also be connected. This is fed through the
back wall of the control unit and connected to the spring-loaded terminals. In the unit, instead of being
connected to the controller board in the RJ10 socket, the cable is connected in the spring-loaded terminals
next to it (see wiring diagram).
Low voltage control leads must be installed so that they are separated from mains leads.
Fig. 2:
Connection terminals in the regulator
9
P1 V 3.0
M
4
1
2
A
B3
English
www.ruck.eu
8. Commissioning
Commissioning by trained technical personnel may only be performed when any risk has been ruled out.
The following checks should be performed in accordance with the installation and operating manual and
the regulations in force:
Check all mechanical and electrical protection measures (e.g. earthing).
Voltage, frequency and type of current must correspond with the rating plate.
Check all electrical connections and wiring.
Check any electrical, switching, safety and control devices connected.
Connect pressure measurement hoses!
Electricity warning (hazardous voltage)!
» Failure to observe the hazard may result in death, injury or damage to property.
→ Beforeperforminganyworkonconductiveparts,alwaysdisconnecttheunitcompletelyfrom
the electricity supply and make sure that it cannot be switched back on again.
Switching the regulator on and off
Bridging terminals X5 and X6 switches the constant pressure regulator CON P1000 on, and remo-
ving the bridge switches it off again.
Changing day-time set-point
Adjust set-point Day with the decade switches (8).
e.g. 3 2 = 32 x 10 = 320 Pa
Adjusting the night-time set-point
Adjust set-point Night with the decade switches (9).
e.g. 4 1 = 41 x 10 = 410 Pa
9.1. Operation without a control unit
9. Operation
9.2. Operation with a control unit (optionally)
The control unit is used for controlling and entering various functions. The display shows the vari-
ous operating parameters and error messages. You can select individual menu points or change
values with the various buttons.
Fig. 3:
Control unit
Switches to the control unit
parameter menu.
Button for switching the unit on or off or
switching to menu management.
Buttons for increasing and decreasing the
set-point for “DAY
Buttons for increasing and decreasing the
set-point for “NIGHT
when regulator on
when regulator off
OFF
PA
150 50 0
ATTENTION: When disconnecting the control unit from the unit after programming, the
adjusted setpoints will be deleted. The manually adjusted setpoints by the rotary switch
will then apply.
M
1) Mode button
2) ON/OFF button
A) Button A:
B) Button B:
3) Control cable
4) Display
10
English
Tel. +49 7930 9211-0 Fax. +49 7930 9211-150
To be able to make changes to the control unit parameter, you must press the „Mode button“ (M)
for at least 5 seconds. P 1 will appear on the display. Use button A () to change to your desired
parameter.
9.2.1. Adjustment of the control unit parameter
P 1 V
1.1
5 sec
M
A
OFF
DAY NIGHT
2 sec
M
0 ENGLISH
P 2 Language setting
Range of values
0 DEUTSCH 0 DEUTSCH
1 ENGLISH
2 FRANCAIS
3 DANSK
4 ESPAÑOL
5 NEDERLANDS
6 PORTUGUÊS
7 POLSKI
8
9
Factory setting
P 2 Language setting
Use button A () to change to language setting
P 2. Now press button B () and the control
unit will change to input mode. You can now
use buttons A (and ) to select the langu-
age required.
Press button B () again to accept the langu-
age selected.
Then press the Mode button“ (M) for at least
2 seconds. The parameters will be saved and
the menu will close. The Display switches into
operating mode.
A
B
10 sec
Status ON / OFF
Status display
OFF
9.2.2. Menu functions
Switching the unit on/off on the control unit.
Press the ON/OFF button (1) to switch the unit on or off.
The unit‘s status now appears on the display with the current values.
DAY – Changing the setting
Use the A buttons on the control unit to increase (▲) or reduce (▼) the set-point.
(The setting range is limited by parameters P01 and P02.)
The DAY set-point is retained in memory after a power failure.
PA
150 60 150
B
A
when regulator on
when regulator off
OFF
PA
150 50 0
or
P 2 V 1.1
150
60
Parameter settings Menu
see Section 9.2.3
PA
150
NIGHT - Changing the setting
Use the B buttons on the control unit to increase (▲) or reduce (▼) the set-point.
(The setting range is limited by parameters P01 and P02.)
The NIGHT set-point is retained in memory after a power failure.
Current display
Pressure difference
11
English
www.ruck.eu
9.2.3. Parameter settings Menu
You move to the parameter settings menu menu P by pressing the ON/OFF button, which must
be held down for approx. 10 seconds.
Parameter P01 is displayed on the screen. With the A (and ) buttons on the control unit,
the individual P parameters can be called up. Press the „mode button“ (M) once to return to the
starting function.
10 sec
P01 MIN-VALUE
5
P02 MAX-VALUE
990
A
A
P01 Minimum set-point on control unit
Parameter for display and setting of the minimum set-point.
The setting range is from 10 Pa to 500 Pa.
The parameters can be changed with the buttons B (▲ and ▼).
P02 Maximum set-point on control unit
Parameter for display and setting of the maximum set-point.
The setting range is from 100 Pa to 990 Pa.
The parameters can be changed with the buttons B (▲ and ▼).
P03 P-COMPONENT
5
A
P03 P-Anteil
The setting range is from 5 to 15.
05 = no gain
10 = average gain
15 = high gain
The parameters can be changed with the buttons B (▲ and ▼).
The works setting is 5.
The regulation tends to pulsate at high gain.
P04
AIR QUALITY
0
A
P04 Pressure correction
P05 DAY NIGHT
10 100 200
P05
Control of the decade switches for Day and Night.
The current program version is listed below „P05“.
The works setting is “0”.
The parameters can be changed with the buttons B (▲ and ▼).
Settings between -20 Pa and +20 Pa are possible.
B
B
B
B
12
English
Tel. +49 7930 9211-0 Fax. +49 7930 9211-150
B
B
B
B
.
.
.
M
B
A
A
A
A
A
21,0° 0%
4%
9.2.4. Time / Time switch
OFF
1 4:30 ON
DAY 22:00 OFF
1 4:00 ON
DAY 22:00 OFF
2 4:30 ON
DAY 22:30 OFF
2 4:30 ON
DAY 22:30 OFF
3 4:30 ON
DAY 22:30 OFF
OFF
Setting the time switch
With the setting parameters for the time switch, the times when the unit is to come on (ON) or off
(OFF) can be set individually for each day of the week.
From the status display, press button A (▲) and B (▲) to get to the menu for setting the time switch.
On the top line, the display ashes for the „hour“ in which the unit is to
come on (ON) on day 1. Press buttons B (▲ and ▼) to set the „hour“ and
then conrm the entry with button A (▲). The display then moves on to
the „minutes“ which can be set in the same way with buttons B (▲ and ▼)
and conrmed with button A (▲).
(The minutes are set in 5-minute increments)
On the bottom line, the display now ashes for the „hour“ in which the
unit is to switch off on day 1. The „hour“ and „minutes“ are again set and
conrmed with buttons B (▲ and ▼) and button A (▲).
Once the entry has been conrmed, the display moves on to day 2 where the individual on and off
times can be set. Days 3 to 7 then follow.
Once you have set all of the parameters / days, press the „Mode button“ (M) to go back to the unit‘s
status display.
However, you do not have to go through the whole time switch menu to get back to the status display.
You can press the „Mode button“ (M) at any time to go back to the status display.
Note:
If the time 0:00 is given in the parameters, the unit will not switch on or off.
If, for example, you do not want the unit to come on during the weekend, you should set the value to
0:00 for „Day 6“ and „Day 7“.
The values set are saved even when there is a power failure or if the battery in the control unit runs
down. Only the current time and day of the week have to be reset.
Note: Instructions on changing the clock battery are give in section 9.2.5.
Set
Day
1Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
7
Sunday
13
English
www.ruck.eu
Setting the current time / day
From the status display, press button A (▲) and B (▲) for approximately 8 s to get to the menu for
setting the current time and the current day of the week.
The display shows the current time and day set.
Above the „DAY“ display, there is a value indicating the current day of
the week.
When the value is ashing, the value can now be set. Press buttons B
(▲ and ▼) to set the current day of the week (see table). Press button A
(▲) to conrm the set value.
On the display, the „hour“ now starts to ash. The hour is set by again
pressing buttons B (▲ and ▼) and then conrmed with button A (▲). The
display then moves to „minutes“ which can be set in the same way with
buttons B (▲ and ▼) and conrmed with button A (▲).
Press the „Mode button“ (M) to go back to the status display.
M
B
21,0° 0%
OFF
1 11:30:45
DAY
Set
Day
1Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
7
Sunday
8 sec
B
1 11:30:45
DAY
B
1 11:30:45
DAY
A
A
B
A
21,0° 0%
14
English
Tel. +49 7930 9211-0 Fax. +49 7930 9211-150
21,0° 0%
4%
21,0° 0%
4%
Time switch on Time switch off
Switching the time switch on and off.
The time switch can be switched on and off as required.
From the status display you can switch the time switch on or off by pressing button A () and B ()
at the same time.
When the time switch is on, a continuous clock symbol is shown on the display.
If the time switch is off and the switching contact for day and night operation is open, the unit func-
tions in day operation mode.
Setting day - night switch-over
This menu works similar as the timer, however it does not set the on (ON) and off (OFF) times, but
the times when the unit switches from day to night mode.
On the display, push button A (▲) and B (▲) simultaneously for approx. 3 seconds to get to the menu
for day-night switch-over.
21,0° 0%
1 18:00
DAY 22:00
1 18:00
DAY 22:00
2 18:30
DAY 21:30
2 18:30
DAY 21:30
3 18:30
DAY 21:30
.
.
.
3 sec
The display ashes on the top line for the time point in which the device
starts the night mode on day 1 (Monday). Press buttons B (▲ and ▼) to
set the „hour“ and then conrm the entry with button A (▲). The display
then moves on to the „minutes“ which can be set in the same way with
buttons B (▲ and ▼) and conrmed with button A (▲).
(The minutes are set in 5-minute increments)
The display now ashes on the bottom line for the time point in which
the device stops the night mode on day 1 (Monday). The „hour“ and
„minutes“ are again set and conrmed with buttons B (▲ and ▼) and
button A (▲).
Once the entry has been conrmed, the display moves on to day 2 where the individual on and off
times can be set. Days 3 to 7 then follow.
Once you have set all of the parameters / days, press the „Mode button“ (M) to go back to the unit‘s
status display.
However, you do not have to go through the whole time switch menu to get back to the status display.
You can press the „Mode button“ (M) at any time to go back to the status display.
Note:
If the time 0:00 is given in the parameters, the unit will not switch to night operation.
The values set are saved even when there is a power failure or if the battery in the control unit runs
down. Only the current time and day of the week have to be reset.
Note: Instructions on changing the clock battery are give in section 9.2.5.
M
Set
Day
1Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
7
Sunday
B
B
B
B
B
A
A
A
A
A
OFF
OFF
15
01
125987
01
125987
2
B)
C)
3
A)
1
English
www.ruck.eu
21,0° 1 0%
0%
21,0° 1 0%
0%
The battery‘s operating capacity is checked when voltage is applied to the unit.
A dead battery is
indicated by a battery symbol in the status display.
Change the battery as follows:
Remove the control cable (1) from the control unit.
Open the control unit by removing the cover (2).
The holder (3) for the battery is on the board. Remove the battery and replace it with a new one
as shown in Fig. 26 C.
The control unit can now be closed again and the control cable connected again.
You only have to reset the current time (see Section 9.4.). The battery symbol disappears from
the status display. Your control unit is fully functional again.
Note: requires a 3 V lithium CR 1616 button cell battery.
9.2.5. Changing the battery
Status display:
Display after changing the battery:
Fig. 4
(1) Control cable
(2) Control unit cover
(3) Battery holder
Servicing, troubleshooting and cleaning may only be performed by specialist personnel in
accordance with this installation and operating manual and the regulations in force.
If operated correctly, ruck products only require a small amount of maintenance.
The following work should be performed at regular intervals, in accordance with health and safety
regulations:
Check the operation of the control system and safety devices.
Check electrical connections and wiring for damage.
Beforeputtingbackintoserviceaftercareandmaintenancework,carryoutasafetycheck
as described in Sections 7 + 8!
10.2. Cleaning and care
Maintenance and repairs may only be performed by specialist personnel in accordance with this
installation and operating manual and the regulations in force.
Do not repair defective or damaged units yourself, but report the damage or faults to the manuf-
acturer in writing.
Unauthorized repairs may cause personal injury and / or damage to property, in which
case the manufacturer‘s guarantee or warranty will not apply.
10. Maintenance and repair
10.1. Important notes
Electricity warning (hazardous voltage)!
» Failure to observe the hazard may result in death, injury or damage to property.
→ Beforeperforminganyworkonconductiveparts,alwaysdisconnecttheunitcompletely
from the electricity supply and make sure that it cannot be switched back on again.
16
Bl.
Blatt
Ursp.
Norm
Gepr.
Bearb.
Datum
Name
Datum
Änderung
Zustand
ruck Ventilatoren GmbH
Max-Planck-Strasse 5
D-97944 Boxberg
Tel +49 (0) 7930 9211-300
8
=CONP
CONP 1000Für BDA
CONP 1000
136064_00
S. Kuhbach
14
E
D
C
B
F
A
E
D
C
B
F
A
8765
4
3
2
1
PE
PE
L
L
N
N
Day
Night
Sollwert erreicht
X10
X9
X8
X7
X6
X5
X4
X3
X2
X1
Freigabe
enable
day / night
GND
0-10V
Freigabe enable
Frq.
CON_P 1000
X12
X11
GND
Tacho / Fault
GND
A
B
24V
J1
J2
+
-
A
B
Bl.
Blatt
Ursp.
Norm
Gepr.
Bearb.
Datum
Name
Datum
Änderung
Zustand
ruck Ventilatoren GmbH
Max-Planck-Strasse 5
D-97944 Boxberg
Tel +49 (0) 7930 9211-300
9
=CONP
CONP 1000 CONP 1000
136064_00
S. Kuhbach
26
E
D
C
B
F
A
E
D
C
B
F
A
8765
4
3
2
1
PE
PE
L
L
N
N
Day
Night
Sollwert erreicht
X10
X9
X8
X7
X6
X5
X4
X3
X2
X1
Freigabe
enable
day / night
GND
0-10V
Freigabe enable
Frq.
CON_P 1000
X12
X11
GND
Tacho / Fault
GND
A
B
24V
J1
J2
+
-
05
Adresse = 5
2
Baudrate = 9600
0 = 2400
1 = 4800
2 = 9600
3 = 14400
4 = 19200
Einstellung Adresse und Baudrate
English
Tel. +49 7930 9211-0 Fax. +49 7930 9211-150
11. Modbus communication interface
11.1. Wiring diagram
11.2. Interface information
The device works as a Modbus RTU slave. The interface conguration is 8N1, 9600Baud, slave
address 1. The address and the baud rate can be set, see the following gure. As bus line is
recommended a twisted pair data cable with 120 Ohm impedance.
Fig. 5
Abb. 6
Setting address and baud rate
17
English
www.ruck.eu
11.3. Functions implemented
Function
code Name Description
03 Hex Read Hold Register Read device parameter
04 Hex Read Input Register Read current value
06 Hex Write Single Register Write device parameter word by word
10 Hex Write Multiple Register Write several device parameters word by word
Function
code Name Sub-function Description
08 Hex Return Query Dat 00 Send the received message back
08 Hex Restart Communications 01 Restart communication
08 Hex Force Listen Only Mode 04 Switch to listen-only mode
11.4. Parameter table
Register
address
Protocol
address Parameter name Value range Data type Autho-
rity
40001
0
Reserved
integer
40002
1
Min. set-point value
10 - 500 PA
integer
40003
2
Max. set-point value
100 - 990 PA
integer
40004
3
P - component
5 - 15
integer
40005
4
Pressure correction
-20 - 20 PA
integer
40006
5
Reserved
integer
40007
6
Reserved
integer
40008
7
Reserved
integer
40009
8
Reserved
integer
40010
9
Reserved
integer
40011
10
Set-point: day
Pressure (PA)
integer
40012 11 Set-point: night Pressure (PA) integer R/W
40013
12
day/night switching
0 = Day-time operation, 1 = Night-time operation
integer
40034
33
Status and control word
See Table below
integer
40036
35
Save parameters
12439 Value change after saving under 0
integer
Status and control word, protocol address 33
Function Authority Comment
Bit 0
1 = Error present
R
Bit 1
Reserved
R/W
Bit 2
Reserved
R/W
Bit 3
Reserved
R/W
Bit 4
Reserved
R/W
Bit 5
1 = Cancel error
R/W
With rising slope, error is cancelled
Bit 6 0 = Unit switched ON
1 = Unit switched OFF
R/W
shut-off with increasing ank
Bit 7 1 = Unit switched ON
0 = Unit switched OFF
R/W
With rising slope, unit switched ON
Bit 8
Reserved
R/W
Bit 9
Reserved
R/W
Bit 10
Reserved
R/W
Bit 11
Reserved
R/W
Bit 12
Reserved
R/W
Bit 13
Reserved
R/W
Bit 14
Reserved
R/W
Bit 15
Reserved
R/W
Example for switching on and off:
To switch on, 128 (decimal) must be written into register 33 (status and control word).
To switch off, 64 (decimal) must be written into register 33 (status and control word).
18
English
Tel. +49 7930 9211-0 Fax. +49 7930 9211-150
11.5. Current value table
Register
address
Protocol
address Parameter name Value range Data type Authority
30001
0
Reserved
integer
R
30002
1
Room temperature
integer
R
30003
2
Measured pressure
Pressure (PA)
integer
R
30004
3
Set day internal switch
Pressure (PA)
integer
R
30005
4
Set night internal switch
Pressure (PA)
integer
R
30006
5
Reserved
integer
R
30007
6
Reserved
integer
R
30008
7
Reserved
integer
R
30009
8
Reserved
integer
R
30010
9
Reserved
integer
R
30011
10
Reserved
integer
R
30012
11
Control fan
0 - 100 %
integer
R
30013 12 Pressure in range
0 = Pressure difference between setpoint and measured > 20 Pa
1 = Pressure difference between setpoint and measured < 20 Pa integer R
30014
13
Set pressure
Pressure (PA)
integer
R
30025
24
Error number
See Table below (PA)
integer
R
The unit must not be recongured.
ruck Ventilatoren‘swarrantyonlyappliesforthecongurationdelivered.
Thewarrantywillceasetoapplyafteranyrecongurationorexpansion.
12. Expansionandreconguration
13. Dismantling and disposal
Dismantle the unit as follows:
Risk of injury if dismantled under hazardous voltage!
»If you do not switch off the voltage before starting to dismantle the unit you may injure your-
self and damage the product or parts of the installation.
→ Makesurethattherelevantpartsoftheinstallationhavebeendisconnectedfromthevoltage
supply.
Current value table, protocol addresses 24 (error numbers)
Value
0 Reserved
1 Reserved
2 Reserved
3 Reserved
4 Reserved
5 Reserved
6 Reserved
7 Reserved
8 Reserved
9 Reserved
10 Fan defective
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
16 Reserved
17 Reserved
18 Reserved
19 Reserved
20 Reserved
19
English
www.ruck.eu
13.2. Disposal
13.1. Disassembling the product.
Observe the safety instructions given in Sections 2 to 8 and Section 12 when decommissioning
and disassembling the unit.
Careless disposal of the unit may be cause pollution.
Please therefore dispose of the unit in accordance with the national requirements that apply in
your country.
14. Troubleshooting
Please note the following instructions:
Proceed systematically and purposefully when troubleshooting, even when under the pressure of
time. In the worst case, randomly and indiscriminately dismantling and changing set-
tings may result in it no longer being possible to determine the original cause of the fault.
Get an overview of the unit‘s operation in conjunction with the overall installation.
Try to clarify whether the unit provided the required function in the overall installation before the
fault occurred.
Try to nd any changes to the overall installation in which the unit is installed:
»Have the unit‘s operating conditions or operating range been changed?
»Have any changes (e.g. recongurations) or repairs been performed on the overall system
(installation, electrics, control) or to the unit? If yes: what?
»Has the unit been operated correctly?
»How does the fault appear?
Form a clear idea of the cause of the fault. If necessary, question the immediate operator or the
installation operator.
If you have not been able to remove the fault, please contact the manufacturer. The contact address
can be found at www.ruck.eu or on the back cover of this operating and installation manual.
14.1. Possible operating faults.
Further faults may occur before and during operation of the unit which are not indicated by an error
message on the display.
Fault Possible causes Fault correction
Fan does not run.
The regulator is not switched on.
No electricity supply
Supply lead not connected.
Switch on regulator.
- With remote control (optional)
- with a contact between X5 and X6
(see Section 7!)
Check fuse / power supply.
Have electrical power supply connected by an
authorised electrician.
No regulation!
Pressure measured in the wrong place
Connect measurement hose to a suitable point in
the ventilation duct
No ModBus communication
Jumper J2 is set to control unit
Set jumper J2 to ModBus
Remote control unit shows ERR
Jumper J2 is set to ModBus
Set jumper J2 to control unit
Jumper J1 set to tacho signal
Fan does not run and green LED
D23 ashes quickly
Motor has a fault relay
Error input not connected
Bridge in fault input
Motor defective
Set jumper J1 to the error relay
Set jumper J1 to the error relay and connect a
bridge to the error input
Set jumper J1 to the error relay
Contact service
Jumper J1 set to fault relay
Fan does not run and green LED
D23 ashes quickly
Motor has a tachometer signal
Error input not connected
Motor defective
Set jumper J1 to tacho signal
Connect a bridge to the error input
Contact service
F10 FAULT
FAN
F10 FAULT
FAN
20
L
H
B
Bl.
Blatt
Ursp.
Norm
Gepr.
Bearb.
Datum
Name
Datum
Änderung
Zustand
ruck Ventilatoren GmbH
Max-Planck-Strasse 5
D-97944 Boxberg
Tel +49 (0) 7930 9211-300
7_ETI
=CONP
CONP 1000 CONP 1000
07.01.2020
S. Kuhbach
13
E
D
C
B
F
A
E
D
C
B
F
A
8765
4
3
2
1
PE
PE
L
L
N
N
Day
Night
Sollwert erreicht
X10
X9
X8
X7
X6
X5
X4
X3
X2
X1
Freigabe
enable
day / night
GND
0-10V
Freigabe enable
Frq.
CON_P 1000
X12
X11
GND
Tacho / Fault
GND
A
B
24V
J1
J2
+
-
Spannungsversorgung
Power supply
230V AC
50/60Hz
Bedienteil
Remote control
(Optional)
153173
100er
10er
Bl.
Blatt
Ursp.
Norm
Gepr.
Bearb.
Datum
Name
Datum
Änderung
Zustand
ruck Ventilatoren GmbH
Max-Planck-Strasse 5
D-97944 Boxberg
Tel +49 (0) 7930 9211-300
1
=CONP
CONP 1000 CONP 1000
136064_00
S. Kuhbach
13
E
D
C
B
F
A
E
D
C
B
F
A
8765
4
3
2
1
PE
PE
L
L
N
N
Day
Night
Sollwert erreicht
X10
X9
X8
X7
X6
X5
X4
X3
X2
X1
Freigabe
enable
day / night
GND
0-10V
Freigabe enable
Frq.
CON_P 1000
X12
X11
GND
Tacho / Fault
GND
A
B
24V
J1
J2
PE
PE
L
L
N
N
Day
Night
Sollwert erreicht
X10
X9
X8
X7
X6
X5
X4
X3
X2
X1
Freigabe
enable
day / night
GND
0-10V
Freigabe enable
Frq.
CON_P 1000
X12
X11
GND
Tacho / Fault
GND
A
B
24V
J1
J2
Normal Betrieb
Modbus Betrieb
+
-
+
-
English
Tel. +49 7930 9211-0 Fax. +49 7930 9211-150
15. Technical data
Model: CON P1000 Constant pressure control
Size:
Length
L mm 139
Width
B mm 118
Height
H mm 70
Technical data:
Pressure regulation range:
10 – 990 Pa
Supply voltage:
230V AC 50/60 Hz
Digital inputs:
2 x potential-free (on/off, day/night switching)
Relay outputs:
2 (enable frequency converter, set-point reached) 24 V - 1 A
Analog output: 0–10V DC
Degree of protection:
IP55
Interfaces:
1 x RS485 for control unit (optional remote control unit) / MODBUS
16. Wiring diagrams
Normal operation / Operation with a control unit Modbus operation
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27

Ruck CON P1000 Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI