Drawing Vacuum on the System
1. Connect core removal tool to system.
2. Use built in Schrader valve tool to
remove core, set aside for re-use, or
replace with fresh core once evacuation
is complete.
3. Close 4 in 1 ball valve
4. Connect OMNI™ Digital Vacuum Gauge
to side port of core removal tool
5. Connect manifold, hoses, and vacuum
pump to end of core removal tool
6. Turn on vacuum pump and allow to run
until desired vacuum is reached
7. Close ball valve on core removal tool,
disconnect vacuum pump, and shut off
8. Conduct hold test until desired duration
is complete
9. Remove OMNI™ Digital Vacuum Gauge
from side port
10. Proceed to charge the system as indi-
cated in the “Adding Refrigerant to the
System” section, using the side port of
the core removal tool to connect the ball
valve to the system
11. Insert Schrader core into core tool
12. Connect core tool to ball valve end of
core removal tool
13. Open ball valve, insert Schrader core
and tighten to between 3-5 in-lbs
14. Remove core removal tool from system
Single Valve Manifold Connection Guide – continued