VAT 61234-KEGX Owner's manual

Type
Owner's manual
Installation, Operating &
Maintenance Instructions
605429EC Edition 2018-02-09
Butterfly Pressure Control Valve
with EtherCAT interface
Series 612
DN 25-50 mm (I.D. 1” - 2")
This manual is valid for the following product ordering numbers:
Configured with firmware: 600P.1G.27.00
Sample picture
Series
612
2/110
Edition 2018-02-09 605429EC
Imprint
Manufacturer
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Website:
Phone:
Fax:
Email:
www.vatvalve.com
+41 81 771 61 61
+41 81 771 48 30
Publisher
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Editor
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Print
VAT Vakuumventile AG, CH
-
9469 Haag,
Copyright
©
VAT Vakuumventile AG
2018
No part of these instructions may be reproduced in any way (photocopies,
microfilms or any other reproduction processes) nor may it be manipulated with
electronic systems, duplicated or distributed without written permission from VAT.
Offenders are liable to pay damages.
The original VAT firmware and updated state of the art versions of the VAT
firmware are intended for use with VAT products. The VAT firmware contains a
limited, time unlimited user license. The VAT firmware may not be used for
purposes other than those intended nor is it permitted to make copies of the VAT
firmware. In particular, it is strictly forbidden to give copies of the VAT firmware to
other people.
The use of trade names, brand names, trademarks, etc. in these Instructions
does not entitle third parties to consider these names to be unprotected and to
use them freely. This is in accordance with the meaning of the laws and acts
covering brand names and trademarks.
Series 612
605429EC Edition 2018-02-09 3/
110
Contents
1
Description of product ........................................................................ 5
1.1
Identification of product ................................................................................................... 5
1.2
Use of product ................................................................................................................. 5
1.3
Used abbreviations .......................................................................................................... 5
1.4
Related documents.......................................................................................................... 5
1.5
Important information....................................................................................................... 5
1.6
Technical data ................................................................................................................. 6
1.6.1
Control and actuating unit ................................................................................. 6
1.6.2
Valve unit .......................................................................................................... 8
2
Safety ................................................................................................... 9
2.1
Compulsory reading material ........................................................................................... 9
2.2
Danger levels .................................................................................................................. 9
2.3
Personnel qualifications ................................................................................................. 10
2.4
Safety labels .................................................................................................................. 10
3
Design and Function ......................................................................... 11
3.1
Design ........................................................................................................................... 11
3.2
Function ......................................................................................................................... 11
3.2.1
Pressure control system overview and function .............................................. 12
3.2.2
Principle of a pressure control system ............................................................ 13
4
Installation ......................................................................................... 14
4.1
Unpacking ..................................................................................................................... 14
4.2
Installation into the system ............................................................................................ 15
4.2.1
Installation space condition ............................................................................. 16
4.2.2
Connection overview ....................................................................................... 16
4.2.3
Installation procedure ...................................................................................... 17
4.3
Tightening torque .......................................................................................................... 18
4.3.1
Mounting with ISO-KF flanges ........................................................................ 18
4.4
Admissible forces .......................................................................................................... 19
4.4.1
Admissible forces at controller ........................................................................ 20
4.4.2
Requirements to sensor connection ................................................................ 21
4.5
Electrical connection...................................................................................................... 21
4.5.1
Ground connection .......................................................................................... 22
4.5.2
Sensor supply concepts .................................................................................. 23
4.5.3
Power and sensor connection (+24 VDC sensors) ......................................... 24
4.5.4
Power and sensor connection (±15 VDC sensors) without opt. SPS module . 26
4.5.5
Power and sensor connection (±15 VDC sensors) with optional SPS module 28
4.5.6
EtherCAT interface connection ....................................................................... 29
4.5.7
LOGIC I/O ....................................................................................................... 30
4.5.8
Service port connection................................................................................... 31
4.6
Initial operation .............................................................................................................. 32
4.6.1
Setup procedure ............................................................................................. 32
4.6.2
EtherCAT configuration ................................................................................... 33
4.6.3
Valve configuration ......................................................................................... 39
4.6.4
Sensor configuration ....................................................................................... 40
4.6.5
ZERO .............................................................................................................. 42
4.6.6
LEARN (adaptive) ........................................................................................... 43
4.6.7
Pressure control configuration ........................................................................ 45
4.7
Tuning of control performance ....................................................................................... 46
4.7.1
Tuning of control performance with adaptive pressure controller .................... 47
4.7.2
Tuning of control performance with fixed PI pressure controller ..................... 52
4.7.3
Tuning of control performance with soft pump pressure controller .................. 55
4.8
EtherCAT interface commands ..................................................................................... 57
Series
612
4/110
Edition 2018-02-09 605429EC
4.9
EtherCAT interface (Process data – cyclic communication) .......................................... 57
4.9.1
OUTPUT Buffer (Master PLC) ......................................................................... 58
4.9.2
INPUT Buffer (Master PLC) ............................................................................. 61
4.10
EtherCAT interface (Parameter data – acyclic communication) .................................... 66
4.10.1
EtherCAT Object dictionary ............................................................................. 66
4.11
Communication and timing between Master (PLC) and Slave (VAT-Valve) .................. 72
5
Operation ........................................................................................... 73
5.1
Normal operation ........................................................................................................... 73
5.1.1
Local operation ................................................................................................ 74
5.1.2
Remote operation ............................................................................................ 75
5.2
Close valve .................................................................................................................... 76
5.3
Open valve..................................................................................................................... 76
5.4
Position control .............................................................................................................. 76
5.5
Pressure control ............................................................................................................. 77
5.5.1
Pressure control operation with 2 sensors ...................................................... 78
5.6
Display information ........................................................................................................ 79
5.6.1
Power up ......................................................................................................... 79
5.6.2
Operation ........................................................................................................ 80
5.6.3
Fatal error ........................................................................................................ 80
5.6.4
EtherCAT LEDs ............................................................................................... 80
5.6.5
Safety mode .................................................................................................... 82
5.6.6
Service indication ............................................................................................ 82
5.7
Operation during power up ............................................................................................ 82
5.8
Behavior in case of power failure ................................................................................... 83
5.9
Operation under increased temperature ........................................................................ 83
6
Trouble shooting .............................................................................. 84
6.1
Additional EtherCAT warning ......................................................................................... 86
7
Maintenance ...................................................................................... 87
7.1
Maintenance intervals .................................................................................................... 87
7.2
Maintenance procedures ............................................................................................... 88
7.2.1
Replacement of shaft feedthrough seals and valve cleaning .......................... 89
7.2.2
Replacement of Option board ......................................................................... 93
7.2.3
Retrofit / replacement procedure ..................................................................... 95
8
Repairs .............................................................................................. 99
9
Dismounting and Storage .............................................................. 100
9.1
Dismounting ................................................................................................................. 100
9.2
Storage ........................................................................................................................ 101
10
Packaging and Transport ............................................................... 102
10.1
Packaging .................................................................................................................... 102
10.2
Transport ..................................................................................................................... 103
11
Disposal ........................................................................................... 104
12
Spare parts ...................................................................................... 105
12.1
Drawing ....................................................................................................................... 106
12.1.1
ISO-KF valve unit - aluminum blank, without heating .................................... 107
12.1.2
ISO-KF valve unit – stainless steel, without heating ...................................... 107
12.1.3
Control and actuating unit ............................................................................. 108
12.1.4
Accessories ................................................................................................... 108
13
Appendix ......................................................................................... 109
Series 612 DESCRIPTION OF PRODUCT
605429EC Edition 2018-02-09 5/
110
1 Description of product
1.1 Identification of product
The fabrication number and order number are fixed on the product directly or by means of an
identification plate.
Fabrication number
Order number
1.2 Use of product
This product is a Butterfly control valve for downstream pressure control in vacuum systems.
Use product for clean and dry vacuum applications only. Other applications are only allowed with the
written permission of VAT.
1.3 Used abbreviations
Abbreviation Description
CPA Control Performance Analyzer
PFO Power Failure Option
SFS Sensor Full Scale
SPS Sensor Power Supply
ADC Analog-to-digital converter
1.4 Related documents
Product Data Sheet
Dimensional Drawing
IOMI Heating device (if valve with heater)
1.5 Important information
This symbol points to a very important statement that requires particular attention.
Example
:
Refer to chapter: «Technical data» for detailed information.
made in Switzerland
Fabrication No.:
000
.
. -
.
.
.
. -
.
.
.
. /
.
.
.
.
A
-
.
.
.
.
.
.
DESCRIPTION OF PRODUCT Series
612
6/110
Edition 2018-02-09 605429EC
1.6 Technical data
1.6.1 Control and actuating unit
Description
Power input
1)
(α) +24 VDC (±10%) @ 0.5 V pk-pk
max. [connector: POWER]
[
612
. .
-
. .
A
.
-
. . . . /
612
. .
-
. .
G
.
-
. . . . ]
[612 . . - . . C . - . . . . / 612 . . - . . H . - . . . . ]
38 W max. (operation of valve with max. load) without PFO
4)
38 W plus 10 W for PFO
4)
Sensor power supply
2)
(β)
[612 . . - . . A . - . . . . / 612 . . - . . C . - . . . . ]
Input
Output
+24 VDC / 1500 mA max.
±15 VDC (±5%) / 1000 mA max.
[connector: POWER]
[connector: SENSOR]
Sensor power supply
2)
(β)
[612 . . - . . G . - . . . . / 612 . . - . . H . - . . . . ]
Input
Output
+ 24 VDC resp. ± 15 VDC
same as input but:
2.0 A max. at ± 15 VDC
1.5 A max. at + 24 VDC
[connector: POWER]
[connector: SENSOR]
1)
Internal overcurrent protection by a PTC device.
2)
Refer to chapter «Sensor supply concepts» for details.
4)
PFO = Power Failure Option. Refer to chapter «Behavior in case of power failure» for details
Calculation of complete power consumption:
P
tot
= α + β
whereas
β depends on sensor supply concept and sensor power consumption.
Series 612 DESCRIPTION OF PRODUCT
605429EC Edition 2018-02-09 7/
110
Control and actuating unit (continuation)
Sensor input
Signal input
ADC resolution
Sampling time
0-10 VDC / Ri>100 k
0.23 mV
10 ms
[connector: SENSOR]
Digital outputs
3)
Input voltage
Input current
70 VDC or 70 V peak max.
0.1 ADC or 0.1 A peak max.
PFO
4)
battery pack
[612 . . - . . C . - . . . . / 612 . . - . . H . - . . . . ]
Charging time
Durability
2 minutes max.
up to 10 years @ 25°C ambient;
refer to «Durability of power fail battery» for details
Ambient temperature 0 °C to +50 °C max. (<35 °C recommended)
Pressure control accuracy 5 mV or 0.1% of setpoint, whichever is greater
Position resolution / position control
capability 20000
Actuating time closing 0.3 s typ.
opening 0.3 s typ.
Utilizable valve torque 2.5 Nm
3)
Refer to chapter «Schematics» for details.
4)
PFO = Power Failure Option. Refer to chapter «Behavior in case of power failure» for details
DESCRIPTION OF PRODUCT Series
612
8/110
Edition 2018-02-09 605429EC
1.6.2 Valve unit
Description
Pressure range at 20°C
- Aluminum (612 . . - . A. . - . . . . ) 1 × 10E-8 mbar to 1.2 bar (abs)
- Aluminum hard anodized (612 . . - . H. . - . . . . ) 1 × 10E-6 mbar to 1.2 bar (abs)
- Stainless steel (612 . . - . E. . - . . . . ) 1 × 10E-8 mbar to 1.2 bar (abs)
Leak rate to outside at 20°C
- Aluminum (612 . . - . A. . - . . . . ) 1 × 10E-9 mbar l/s
- Aluminum hard anodized (612 . . - . H. . - . . . . ) 1 × 10E-5 mbar l/s
- Stainless steel (612 . . - . E. . - . . . . ) 1 × 10E-9 mbar l/s
Cycles until first service
2’000’000 (unheated and under clean conditions)
Admissible operating temperature
+10°C to +150°C
while temperature of valve body and valve plate should be
kept on about same level
Mounting position Any
Control unit for ISO-KF version needs support when
mounted on horizontal piping and control unit does not
hang.
Wetted materials
- Body, plate (612 . . - . A. . - . . . . ) Aluminum 3.2315 (AA6082)
- Body, plate (612 . . - . H. . - . . . . ) Aluminum 3.2315 (AA6082) hard anodized
- Body, plate (612 . . - . E. . - . . . . ) Stainless steel 316L (1.4404 or 1.4435 )
- Shaft Stainless steel 316L (1.4404 or 1.4435 )
- Plate screws Stainless steel 316L (A4)
- Shaft seal Viton
®
(standard). Other materials available on request.
Seal materials are declared on dimensional drawing of
specific valve ordering number.
- Slide bearing for shaft iglidur
®
X
Valve size DN 25
1" DN 40
1½" DN 50
2"
Max. differential pressure on plate 1000 mbar 1000 mbar 1000 mbar
Min. controllable conductance (C
min
)
[N2 molecular flow] 0.15 l/s 0.25 l/s 0.3 l/s
Conductance in open position
[N2 molecular flow] 22 l/s 80 l/s 150 l/s
Dimensions Refer to dimensional drawing of specific valve ordering
number (available on request)
Series 612 SAFETY
605429EC Edition 2018-02-09 9/
110
2 Safety
2.1 Compulsory reading material
Read this chapter prior to performing any work with or on the product. It contains important information
that is significant for your own personal safety. This chapter must have been read and understood by
all persons who perform any kind of work with or on the product during any stage of its serviceable
life.
NOTICE
Lack of knowledge
Failing to read this manual may result in property damage.
Firstly, read manual.
These Installation, Operating & Maintenance Instructions are an integral part of a
comprehensive documentation belonging to a complete technical system. They must
be stored together with the other documentation and accessible for anybody who is
authorized to work with the system at any time.
2.2 Danger levels
DANGER
High risk
Indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING
Medium risk
Indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION
Low risk
Indicates a hazardous situation which, if not avoided, may result in minor or moderate
injury.
NOTICE
Command
Indicates a hazardous situation which, if not avoided, may result in property damage.
SAFETY Series
612
10/110
Edition 2018-02-09 605429EC
2.3 Personnel qualifications
WARNING
Unqualified personnel
Inappropriate handling may cause serious injury or property damage.
Only qualified personnel are allowed to carry out the described work.
2.4 Safety labels
Label Part No. Location on valve
T-9001-156 On protective foil covering of
valve opening
Series 612 DESIGN AND FUNCTION
605429EC Edition 2018-02-09 11/
110
3 Design and Function
3.1 Design
1 Integrated controller 4 Double seal
2 Coupling 5 Plate
3 Bearing 6 Valve body
3.2 Function
The valve plate (5) acts as a throttling element and varies the conductance of the valve opening.
The integrated controller (1) calculates the required plate position to achieve the setpoint pressure.
See also principle drawing on chapter: «Connection Overview».
Actuation is performed by a stepper motor. An encoder monitors the position. This principle ensures
very fast and accurate process pressure control even in demanding contaminating processes.
Double seal of
rotary feedthrough
1
2
4
5
6
3
DESIGN AND FUNCTION Series
612
12/110
Edition 2018-02-09 605429EC
3.2.1 Pressure control system overview and function
Vacuum pressures are always absolute pressures unless explicitly specified as pressure differences.
Example: Downstream control
1 Valve
2 Process chamber
3 Gas inlet
4 Pressure sensor(s)
5 Sensor cable
6 Controller and actuator
7 Cable to remote control unit
8 Cable to power supply
9 HV Pump
S
eff
Q / p
S
eff
effective pump speed (ls
-1
)
Q Gas flow (mbar)
p Pressure (mbar)
or units used in USA
S
eff
= 12.7 • Q / p
S
eff
effective pump speed (ls
-1
)
Q Gas flow (sccm)
p Pressure (mTorr)
M
3
4
5
7
8
2
1
9
Q
pV
Seff
6
Series 612 DESIGN AND FUNCTION
605429EC Edition 2018-02-09 13/
110
3.2.1.1 Way of operation
The controller compares the actual pressure in the process chamber given by the pressure sensor
with the preset pressure. The controller uses the difference between actual and set pressure to
calculate the correct position of the control valve. The controller drives the control valve into the
correct position and the actual pressure again equals the set pressure.
This control operation is performed continuously. Pressure changes in the process chamber due to
leaks, desorption, and gas flow, reaction products, variations in pumping speed etc. are always
corrected at once.
3.2.1.2 Pressure control
In a vacuum system which is pumped and into which gas is admitted at the same time, the pressure
can be controlled in two ways:
1. Downstream control (standard):
The pressure is controlled by changing the conductance of a control valve between pump and
process chamber. This changes the effective pumping speed at the process chamber. Pressure
and gas flow can be independently controlled over a wide range.
2. Upstream control:
The pressure is controlled by changing the gas flow into the process chamber, while the pumping
speed remains constant.
3.2.1.3 Adaptive controller (standard)
A controller adapting itself to changes in pressure, gas flow and pumping speed without any manual
adjustments. This allows for a completely automatic operation of the system.
3.2.2 Principle of a pressure control system
1. Host computer sends
pressure set point
2. Controller reads actual
pressure from sensor
3. Optimizing module sends
new PID parameters
4. Actuator sets new valve
position
Host computer
(Example)
1.
4.
3.
2.
INSTALLATION Series
612
14/110
Edition 2018-02-09 605429EC
4 Installation
WARNING
Unqualified personnel
Inappropriate handling may cause serious injury or property damage.
Only qualified personnel are allowed to carry out the described work.
4.1 Unpacking
NOTICE
Physical overstraining at controller
Inappropriate handling with the valve may cause in damage of controller.
Do not place the valve on the controller.
NOTICE
Physical overstraining at pedestal
Inappropriate handling with the valve may cause in damage of pedestal.
Lift valve at valve body out of transport case.
Make sure that the supplied products are in accordance with your order.
Inspect the quality of the supplied products visually. If it does not meet your
requirements, please contact VAT immediately.
Store the original packaging material. It may be useful if products must be returned
to VAT.
1. Open the transport case and remove inside packing material as far as necessary.
2. Lift the valve carefully and place it on a clean place.
Do not remove protective foils from valve opening
Series 612 INSTALLATION
605429EC Edition 2018-02-09 15/
110
4.2 Installation into the system
WARNING
Valve opening
Risk of serious injury.
Human body parts must be kept out of the valve opening and away
from moving parts.
Do not connect the controller to power before the valve is installed complete into the
system.
NOTICE
Sealing surfaces
Sealing surfaces of valve and vacuum system could be damage in case of incorrect
handling.
Only qualified personal are allowed to install the valve into the vacuum system.
NOTICE
Wrong connection
Wrong connection may result in damage of controller or power supply.
Connect all cables exactly as shown in the following descriptions and schematics.
NOTICE
Burned connector pins (spark)
Connector pins or electronic parts could damage, if plugged and unplugged under
power.
Do not plug or unplug connectors under power.
NOTICE
Contamination
Gate and other parts of the valve must be protected from contamination.
Always wear clean room gloves when handling the valve.
Mount valve to a clean system only.
INSTALLATION Series
612
16/110
Edition 2018-02-09 605429EC
4.2.1 Installation space condition
Install the valve with integrated controller with space for dismantling and air circulation
as shown in figure below.
4.2.2 Connection overview
System:
1 Valve with controller and actuator
2 Process chamber
3 Gas inlet
4 Pressure sensor(s)
5 Sensor cable
6 Cable to remote control unit
7 Cable to power supply
8 HV Pump
70 mm
M
3
4
5
6
7
2
1
8
Series 612 INSTALLATION
605429EC Edition 2018-02-09 17/
110
Controller:
4.2.3 Installation procedure
All numbers in brackets refer to chapter: «Connection overview».
1. Remove protective covers from body flanges.
2. Install [1] valve into the vacuum system.
Do not tighten the flange screws stronger than indicated under chapter «Tightening
torque».
Do not admit higher forces to the valve than indicated under chapter «Admissible
forces».
Make sure that enough space is kept free to do preventive maintenance work. The
required space is indicated on the dimensional drawing.
Control unit of valves with ISO-KF (612 . . – K . . .) needs support when mounted
on horizontal piping and control unit does not hang.
3. Install the ground connection cable at controller. Refer to chapter «Electrical connection».
4. Install sensor(s) [4] according to the recommendations of the sensor manufacturer and directives
given under chapter «Requirements to sensor connection».
5. Connect sensor cable [5] to sensor(s) and then to valve (connector: SENSOR). Refer to chapter
«Electrical connection» for correct wiring.
6. Connect valve with cable [7] to remote control unit (connector: INTERFACE). Refer to chapter
«EtherCAT connection» for correct wiring.
7. Connect power supply cable [8] to valve (connector: POWER). Refer to chapter «Electrical
connection» for correct wiring.
To provide power to the valve motor pins 4 and 8 must be bridged, otherwise motor
interlock is active and the valve enters the safety mode and is not operative. Refer
also to chapter «Safety mode».
INSTALLATION Series
612
18/110
Edition 2018-02-09 605429EC
8. This valve may optionally be equipped with a heating device. Connect VAT heating device according
to manual of respective heating device.
9. Perform chapter «Setup procedure» to prepare valve for operation.
Without performing the setup procedure the valve will not be able to do pressure
Control.
4.3 Tightening torque
4.3.1 Mounting with ISO-KF flanges
Tightening torques for ISO-KF flange connections depend on the type of seal which is used. Follow
recommendations of seal manufacturer.
Series 612 INSTALLATION
605429EC Edition 2018-02-09 19/
110
4.4 Admissible forces
NOTICE
Force at valve body
Forces from the weight of other components can lead to deformation of the valve body
and to malfunction of the valve.
Do not higher force the valve body as specified.
The following forces are admissible.
Valve size Axial tensile or
compressive force «F
A
» Bending moment
«M»
mm inch
N lb. Nm Lbf.
25 1 70 16 3 3.2
40 100 22 6 4.5
50 2 150 34 11 8
M F
A
INSTALLATION Series
612
20/110
Edition 2018-02-09 605429EC
4.4.1 Admissible forces at controller
NOTICE
Force at pedestal
In case higher force is applied, the pedestal could be permanently damaged.
Do not pushing, shocking load, or stressing the valve controller
Do not deposit anything at valve controller
The admissible force at valve controller in regards to the pedestal (c) shown in table
below.
Admissible force
«F»
Overview
F = Force
a = middle of aluminium part of controller (b / 2)
400 N
a a
F
bc
a a
F
bc
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110