18
each reading appears to be approximately 0 ohm. If
resistance remains at 1000 ohms, an open or break exists
and compressor should be replaced. Be sure internal line
break overload is not temporarily open.
Ground
Circuit
To determine if a wire has broken or come in direct contact with
shell, causing a direct short to ground:
1. Be sure all power is off.
2. Discharge all capacitors.
3. Remove wires from terminals C, S, and R.
4. On hermetic compressors, allow crankcase heaters to remain
on for several hours before checking motor to ensure
windings are not saturated with refrigerant.
5. Use an ohmmeter on R X 10,000 ohm scale. A
megohmmeter may be used in place of ohmmeter. Follow
manufacturer’s instructions.
6. Place 1 meter probe on ground or on compressor shell.
Make a good metal--to-- metal contact. Place other probe on
terminals C, S, and R in sequence.
7. Note meter scale.
8. If reading of zero or low resistance is obtained, motor is
grounded. Replace compressor.
A compressor of 1 ton capacity or less is probably grounded if
resistance is below 1 million ohms. On larger sized single--phase
compressors, resistance to ground should not be less than 1000
ohms per volt of operating voltage.
Example:
230 volts X 1000 ohms/volt = 230,000 ohms minimum.
SHORT CIRCUIT
To determine if any wires within windings have broken through
their insulation and made contact with other wires, thereby shorting
all or part of the winding(s), be sure the following conditions are
met:
1. Correct motor winding resistances must be known before
testing, either from previous readings or from
manufacturer’ s specifications.
2. Temperature of windings must be as specified, usually
about 70_F (21.1ºC) .
3. Resistance measuring instrument must have an accuracy
within ± 5--10 percent. This requires an accurate ohmmeter
such as a Wheatstone bridge or null balance--type
instrument.
4. Motor must be dry or free from direct contact with liquid
refrigerant.
Make This Critical Test
(Not advisable unless above conditions are met.)
1. Be sure all power is off.
2. Discharge all capacitors.
3. Remove wires from terminals C, S, and R.
4. Place instrument probes together and determine probe and
lead wire resistance.
5. Check resistance readings from C--R, C--S, and R--S.
6. Subtract instrument probe and lead resistance from each
reading.
If any reading is within ±20 percent of known resistance, motor
is probably normal. Usually a considerable difference in reading is
noted if a turn --to --turn short is present.
System Clean-- Up After Burnout
Turn off all power to unit before proceeding. Wear safety glasses
and gloves when handling refrigerants. Acids formed as a result of
motor burnout can cause burns.
NOTE: To analyze level of suspected contamination from
compressor burnout, use Total Testt. See your distributor/branch.
Some compressor electrical failures can cause motor to overheat.
When this occurs, byproducts, which include sludge, carbon, and
acids, contaminate system. If burnout is severe enough, system
must be cleaned before replacement compressor is installed. The 2
types of motor burnout are classified as mild or severe.
In mild burnout, there is little or no detectable odor. Compressor
oil is clear or slightly discolored. An acid test of compressor oil
will be negative. This type of failure is treated the same as
mechanical failure. Liquid line strainer should be removed and
liquid line filter drier installed.
In a severe burnout, there is a strong, pungent, rotten egg odor.
Compressor oil is very dark. Evidence of burning may be present
in tubing connected to compressor . An acid test of compressor oil
will be positive. Complete system must be reverse flushed with
refrigerant. Metering device must be cleaned or replaced. In a heat
pump, accumulator and reversing valve are replaced. These
components are also removed and bypassed during reverse
flushing procedure. Remove and discard liquid line strainer. After
system is reassembled, install liquid and suction line filter driers.
Run system for 2 hrs. Discard both driers and install new liquid
line drier only.
Compressor Removal and Replacement
Once it is determined that compressor has failed and the reason
established, compressor must be replaced.
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when
handling refrigerant and observe the following:
The high flow service valve is equipped with Schrader
valves.
!
CAUTION
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal
injury or death. Relieve pressure and recover all refrigerant
before system repair or final unit disposal. Use all service
ports and open all flow --control devices, including solenoid
valves. Federal regulations require that you do not vent
refrigerant to the atmosphere. Recover during system repair
or final unit disposal.
!
WARNING
1. Shut off all power to unit.
2. Remove and recover all refrigerant from system until
pressure gages read zero psig. Use all service ports.
3. Disconnect electrical plug from compressor. Disconnect or
remove crankcase heater (if equipped) and remove
compressor holddown nuts and washers.
4. Cut compressor from system with tubing cutters. Do not use
brazing torch for compressor removal. Oil vapor may ignite
when compressor is disconnected.
5. Scratch matching marks on stubs in old compressor. Make
corresponding marks on replacement compressor .
6. Use torch to remove stubs from old compressor and to
reinstall them in replacement compressor.
7. Use copper couplings to tie compressor back into system.
8. Evacuate system, recharge, and check for normal system
operation.