Potter CA-4064 is a Class A Expander module designed for use with the PFC-4064 and PFC-4410G3 fire alarm control panels. It allows for the Class A/DCLA wiring of the P-Link communication bus and the four built-in NAC circuits, enabling supervised and regulated circuits. The module supports up to 1 amp continuous current at 24 VDC for the P-Link circuit and 3 amps continuous current at 24 VDC for each NAC circuit.

Potter CA-4064 is a Class A Expander module designed for use with the PFC-4064 and PFC-4410G3 fire alarm control panels. It allows for the Class A/DCLA wiring of the P-Link communication bus and the four built-in NAC circuits, enabling supervised and regulated circuits. The module supports up to 1 amp continuous current at 24 VDC for the P-Link circuit and 3 amps continuous current at 24 VDC for each NAC circuit.

PAGE 1 OF 45406300-REV B 11/22
INSTALLATION MANUAL: CA-4064 CLASS A EXPANDER
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the CA-4064 module.
All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA
72 (National Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not
operate as intended. For further information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper
system operation.
1. DESCRIPTION
The CA-4064 is a Class A Expander for the PFC-4064 and PFC-4410G3 re alarm control panel. The CA-4064 allows for
Class A/DCLA wiring of the P-Link communication bus and the four (4) built in NAC circuits. The CA-4064 mounts to the
provided framework in the re alarm control panels.
Before connecting a device to the RS-485 connection, take the following precautions to prevent potential damage to the
RS-485 connection.
Power to the RS-485 connection is removed.
Field wiring on module is correctly installed.
Field wiring has no open or short circuits.
2. TECHNICAL SPECIFICATIONS
Standby Current 15 mA
Alarm Current 60 mA
Operating Temperature Range 32° to 120°F (0° to 49° C)
Operating Humidity Range 10%-93% (non-condensing)
Max no. of CA-4064 Expanders 1
Dimensions (W x H x D) 4” x 6” x 1-5/8”
Note: The P-Link class A/DCLA circuit is rated for a continuous 1 amp at 24 VDC. The NAC class A/DCLA circuits are
each rated for a continuous 3 amps at 24 VDC. The circuits are supervised and regulated.
3. INSTALLATION
Class A/DCLA conguration requires the use of the CA-4064. Once the card is installed, the additional terminals are pro-
vided for the return loop of the P-Link and the NACs. Refer to gures 1 through 3 for examples of installing and wiring a
Class A/DCLA expander card.
PAGE 2 OF 4
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
5406300-REV B 11/22
INSTALLATION MANUAL: CA-4064 CLASS A EXPANDER
FIguRE 1. EXAMPLE OF INSTALLINg AND WIRINg A CLASS A/DCLA EXPANDER CARD
FIguRE 2. INSTALLED CLASS A/DCLA CARD
#6-32 HEX NUT, SEMS
4 PLCS
MAIN PCA BOARD NOT SHOWN FOR CLARITY
CA-4064 CLASS A MODULE
DWG #638-6
PAGE 3 OF 4
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
5406300-REV B 11/22
INSTALLATION MANUAL: CA-4064 CLASS A EXPANDER
FIguRE 3. EXAMPLE OF CA-4064 MODuLE INSTALLED BEHIND MAIN PCA
FIguRE 4. EXAMPLE OF WIRINg A CLASS A/DCLA EXPANDER CARD
NOTES:
NAC wiring supports Class A/DCLA, rated 24 VDC, 3 Amp
RS-485 wiring style supports Class A/DCLA and Class B/DCLB.
RS-485 is power limited.
Wiring for terminals (A, B) and (+, -) are supervised.
All wiring is between #12 (max.) And #18 (min.).
Wire preparation – strip all wires 1/4 inch from their edges as shown here:
NAC 1 NAC 2
- + - +
Notification
Appliance
NAC 1 NAC 2
- + - +
1/4 inch
CA-4064 CLASS A/DCLA MODULE
PFC-4064 MAIN PCA
-+ A B
Expansion
Device
-+ A B
P-LINK
-+ A B
P-LINK
-+ A B
Panel
Connection
CA-4064
Connection
Expansion
Device
PAGE 4 OF 4
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
5406300-REV B 11/22
INSTALLATION MANUAL: CA-4064 CLASS A EXPANDER
– Stripping too much insulation may cause a ground fault.
– Stripping too little may cause a poor connection and subsequently an open circuit.
These instructions do not purport to cover all the details or variations in the equipment described, nor provide for every
possible contingency to be met in connection with installation, operation and maintenance.
Specications subject to change without prior notication.
For Technical Assistance contact Potter Electric Signal Company at 866-956-1211.
Actual performance is based on proper application of the product by a qualied professional.
Should further information be desired or should particular problems arise, which are not covered suciently for the purchaser’s
purpose, the matter should be referred to a distributor in your region.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Potter CA-4064 User manual

Category
Fire protection
Type
User manual

Potter CA-4064 is a Class A Expander module designed for use with the PFC-4064 and PFC-4410G3 fire alarm control panels. It allows for the Class A/DCLA wiring of the P-Link communication bus and the four built-in NAC circuits, enabling supervised and regulated circuits. The module supports up to 1 amp continuous current at 24 VDC for the P-Link circuit and 3 amps continuous current at 24 VDC for each NAC circuit.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI