Generac 20kW RD02025ADAE User manual

Type
User manual
4321
43 1
A
B
A
B
1525 [60.0]
TYP
631 [24.8]
DOOR WIDTH
TYP
209 [8.2]
EXHAUST OUTLET
580 [22.8]
EXHAUST OUTLET
1284 [50.6]
OVERALL
HEIGHT
776 [30.6]
OVERALL WIDTH
342 [13.5]
TYP
177 [7.0]
TYP
2052 [80.8]
OVERALL LENGTH
884 [34.8]
CENTER OF GRAVITY
WEIGHT DATA WITH EMPTY BASETANK
(SEE NOTE 5)
GENERATOR AS SHOWN 693 [1528]
WITH WOODEN SHIPPING SKID 731.6 [1600]
SERVICE ITEM 2.5L
OIL FILL CAP RIGHT SIDE
OIL DIP STICK RIGHT SIDE
OIL FILTER RIGHT SIDE
OIL DRAIN HOSE LEFT SIDE
RADIATOR DRAIN HOSE LEFT SIDE
COOLANT RECOVERY BOTTLE LEFT SIDE
RADIATOR FILL CAP ACCESS ROOF
AIR CLEANER ELEMENT LEFT SIDE
MUFFLER FRONT
FAN BELT EITHER SIDE
BATTERY LEFT SIDE
TITLE
INSTALL PROTECTOR D2.5L G2
EXTENDED TANK
ISSUE DATE: 06/2017
SIZE CAGE NO DWG NO
10000018189
REV
B
N/A
C
SCALE
0.050
WT-KG SEE ABOVE SHEET
1 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH
1/2
REV
C
WINDCHILL VERSION
C.2
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1092 (43") WIDE X 2362 (93") LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
4. REMOVE THE REAR STUB-UP AND REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION,
NEUTRAL CONNECTION, AND BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES
AND ACCESSORY RELAY CONNECTION (QTY 4)
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
8. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.
10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
WEIGHT: KG [LBS]
DIMENSIONS: MM [INCH]
REFERENCE OWNERS MANUAL FOR PERIODIC
REPLACEMENT PART LISTINGS.
RADIATOR/EXHAUST
DISCHARGE AIR
AIR INTAKE
(BOTH SIDES)
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
REAR VIEW
REAR ENCLOSURE
COVER PANEL
SEE NOTE 4
CIRCUIT BREAKER
SEE NOTE 3
CUSTOMER ACCESS
ASSEMBLY, CONTROL
PANEL ACCESS,
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
REMOVABLE
STUB-UP COVER
SEE NOTE 4
RIGHT SIDE VIEW
AND LEFT SIDES
DOOR ON FRONT, RIGHT,
PER DOOR, ONE LIFT-OFF
VISE ACTION LATCH, ONE
DIMENSIONS
CENTER OF GRAVITY
SEE NOTES 5, 7 AND
LIFTING PROVISION (4 PLACES)
LIFT OFF DOOR PROVIDES ACCESS
TO: FUEL FILL, FUEL LEVEL GAUGE,
NORMAL VENT, INNER TANK
EMERGENCY VENT, OUTER TANK
EMERGENCY VENT, OPTIONAL 90%
ALARM ASSEMBLY, OPTIONAL 5
GALLON SPILL BOX
LEFT SIDE VIEW
EXHAUST MUFFLER
ENCLOSED WITHIN
GENERATOR ENCLOSURE
OPEN PUNCHED LOUVERS
TYPICAL ON BOTH SIDES
OF FUEL TANK
VENTILATION DUCT TO
PROVIDE ADEQUATE
CROSS-FLOW OF AIR
VENTILATION
FUEL TANK
VENTILATION
DUCT
BATTERY 12 VOLT
NEGATIVE GROUND
TOP VIEW
REMOVE COVER FOR
ACCESS TO RADIATOR
FILL CAP
INTERNAL DIVIDER PANEL
SEPARATES FUEL TANK
VENTILATION DUCT FROM THE
ENGINE, ALTERNATOR AND
EXHAUST SYSTEM
REMOVE PANEL TO ALLOW
TANK VENTS TO
TERMINATE OUTSIDE OF
THE GENERATOR
ENCLOSURE (CHECK LOCAL
AND STATE CODE FOR
APPLICABILITY)
4321
43 1
A
B
A
B
738 [29.1]
674 [26.5]
105 [4.1]
STUB-UP
AREA
9
[.4]
51
[2.0]
1817 [71.5]
100 [3.9]
STUB-UP
AREA
1248 [49.1]
TYP
224
[8.8]
40 [1.6]
559 [22.0]
639 [25.2]
1722 [67.8]
1631 [64.2]
906 [35.7]
357 [14.0]
231 [9.1]
107 [4.2]
210 [8.3]
269 [10.6]
292 [11.5]
464 [18.3]
574 [22.6]
TYP
624 [24.6]
TYP
152 [6.0]
110 [4.3]
TYP
739 [29.1]
TYP
1368 [53.9]
TYP
1950 [76.8]
TYP
2052 [80.8]
290 [11.4]
FUEL TANK
HEIGHT
393 [15.5]
19 [.7]
TYP
739 [29.1]
MTG CENTERS
TYP
776 [30.6]
FUEL TANK
TOTAL CAPACITY 127 [33.5]
USABLE CAPACITY 121 [32]
TITLE
INSTALL PROTECTOR D2.5L G2
EXTENDED TANK
ISSUE DATE: 06/2017
SIZE CAGE NO DWG NO
10000018189
REV
B
N/A
C
SCALE
0.080
WT-KG SEE ABOVE SHEET
2 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH
2/2
REV
C
WINDCHILL VERSION
C.2
CAPACITY: LITER [GALLON]
DIMENSIONS: MM [INCH]
NOTE: STUB-UP AREA FOR HIGH
AND LOW VOLTAGE CONNECTIONS,
CIRCUIT BREAKER, NEUTRAL AND
CUSTOMER CONNECTION OPENING.
TANK IS LISTED TO UL142 AND ULC5601
LEFT SIDE VIEW
HIGH AND LOW
VOLTAGE
STUB-UP AREA
TOP VIEW
INNER TANK NORMAL VENT
(2" NPT FEMALE)
INNER TANK EMERGENCY VENT
(2" NPT FEMALE)
FUEL LEVEL
GAUGE/SENDER
FUEL FILL
(2" NPT
FEMALE)
CUSTOMER OPTION
(2" NPT FEMALE)
OUTER TANK
LEAK DETECTOR
OUTER TANK
EMERGENCY VENT
(2" NPT FEMALE)
FUEL SUPPLY
16.66 [0.66]
MTG HOLES
(8 PLACES)
SEE NOTE 8
REMOVABLE
STUB-UP COVER
SEE NOTE 4
REAR VIEW
  • Page 1 1
  • Page 2 2

Generac 20kW RD02025ADAE User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI