AS4T
P. 1 / 4EM-1608 Rev.9
THERMOCOUPLE ALARM
(dual or quad alarm trip; eld-congurable)
MODEL
AS4T
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket + CJC sensor)
........ (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ INSULATION CLASS
•This unit is provided with the class of basic insulation.
Prior to installation, check that the insulation class of this
unit satisfies the system requirements.
■ CONFORMITY WITH LOW VOLTAGE DIRECTIVE OR UL
•ThisequipmentissuitableforuseinaPollutionDegree
2 environment and in Installation Category II, with the
maximum operating voltage of 300V.
Basic insulation is maintained between signal input, out-
put and power input. Prior to installation, check that the
insulation class of this unit satisfies the system require-
ments.
•Altitudeupto2000meters
•Theequipmentmustbemountedinsideapanel.
•The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE/UL requirements. Failure to observe these re-
quirements may invalidate the CE/UL conformance.
■ CONFORMITY WITH EMC DIRECTIVE
•Insertanoisefilterforthepowersourceconnectedtothe
unit.Densei-LambdaNoiseFilterModelMZS-1206-33or
equivalent is recommended.
•
The actual installation environments such as panel con-
figurations, connected devices, connected wires, may affect
the protection level of this unit when it is integrated in
a panel system. The user may have to review the CE re-
quirements in regard to the whole system and employ ad-
ditional protective measures to ensure the CE conformity.
■ POWER INPUT RATING & OPERATIONAL RANGE
•Locatethepowerinputratingmarkedontheproductand
confirm its operational range as indicated below:
100–240VACrating:85–264V,47–66Hz,approx.6VA
(100 – 240V ±10% for UL)
24VDCrating:24V±10%,approx.3.5W
110VDCrating:85–150V,approx.3.5W(110V±10%forUL)
■ GENERAL PRECAUTIONS
•Beforeyouremovetheunitfromitsbasesocketormount
it, turn off the power supply and input signal for safety.
■ ENVIRONMENT
•Indooruse
•Whenheavydustormetalparticlesarepresentintheair,
install the unit inside proper housing with sufficient ven-
tilation.
•Donotinstalltheunitwhereitissubjectedtocontinuous
vibration.Donotsubjecttheunittophysicalimpact.
•Environmentaltemperature must be within-5to+55°C
(23to131°F)withrelativehumiditywithin30to90%RH
in order to ensure adequate life span and operation.
■ WIRING
•Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
•Do not bind these cables together with those in which
noisesarepresent.Donotinstalltheminthesameduct.
■ AND ....
•Theunitisdesignedtofunctionassoonaspowerissup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
INSTALLATION
Detachtheyellowclampslocatedatthetopandbottomof
the unit to separate the body from the base socket.
■ DIN RAIL MOUNTING
Set the base socket so that its
DINrailadaptorisatthebot-
tom. Position the upper hook
at the rear side of base socket
onthe DIN rail and push in
the lower. When removing
the socket, push down the
DIN rail adaptor utilizing a
minus screwdriver and pull.
■ WALL MOUNTING
Refer to “EXTERNAL DI-
MENSIONS.”
Body
Specifications
Base Socket
Connection Diagram
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
Shape and size of the base socket
are slightly different with various
socket types.
CJC
Sensor