Wiring Diagram
Input Specification
Aspect & Panel Cutout Dimension
ME0205K071126
Suffix Code Structure
Unit : mm
Before you use, read safety precautions carefully, and use this product properly. The
precautions described in this manual contain important contents related with safety; therefore,
please follow the instructions accordingly. The precautions are composed of DANGER,
WARNING and CAUTION.
There is a danger of occurring electric shock in the input/output terminals so please never let
your body or conductive substance is touched.
1. This product does not contain an electric switch or fuse, so the user needs to install a
separate electric switch or fuse externally. (Fuse rating: 250V 0.5A)
2. To prevent defection or malfunction of this product, apply a proper power voltage in
accordance with the rating.
3. To prevent electric shock or malfunction of product, do not supply the power until the wiring
is completed.
4. Do not decompose, modify, revise or repair this product. This may be a cause of
malfunction, electric shock or fire.
5. Reassemble this product while the power is OFF. Otherwise, it may be a cause of
malfunction or electric shock.
6. If you use the product with methods other than specified by the manufacturer, there may be
bodily injuries or property damages.
7. There is a possibility of occurring electric shock so please use this product after installing it
onto a panel while it is operating.
1. The contents of this manual may be changed without prior notification.
2. Before using the product you purchased, make sure that it is exactly what you ordered.
3. Make sure that there is no damage or abnormality of the product during the delivery.
4. Do not use this product at any place with occurring corrosive (especially noxious gas or
ammonia) or flammable gas.
5. Do not use this product at any place with direct vibration or impact.
6. Do not use this product at any place with liquid, oil, medical substances, dust, salt or iron
contents. (Use at Pollution level 1 or 2)
7. Do not polish this product with substances such as alcohol or benzene. (Use neutral
detergent.)
8. Do not use this product at any place with a large inductive difficulty or occurring static
electricity or magnetic noise.
9. Do not use this product at any place with possible thermal accumulation due to direct
sunlight or heat radiation.
10. Install this product at place under 2,000m in altitude.
11. When the product gets wet, the inspection is essential because there is danger of an
electric leakage or fire.
12. If there is excessive noise from the power supply, using insulating transformer and noise
filter is recommended.
13. The noise filter must be attached to a panel which is already connected to a ground and the
wire between the filter output side and power supply terminal must be short as possible.
14. If twisting the power cables closely together then it is effective against noise.
15. Do not connect anything to the unused terminals.
16. After checking the polarity of terminal, connect wires at the correct position.
17. When this product is connected onto a panel, use a circuit breaker or switch approved with
IEC947-1 or IEC947-3.
18. Install a circuit breaker or switch at near place for convenient use.
19. Write down on a label that if the circuit breaker or switch is operating then the power will be
disconnected since the circuit breaker or switch is installed.
20. For the continuous and safe use of this product, the periodical maintenance is
recommended.
21. Some parts of this product have limited life span, and others are changed by their usage.
22. The warranty period for this product including parts is one year if this product is properly used.
Safety information
WARNING
CAUTION
DANGER
Power Supply
Power Consumption
Voltage for Sensor
Measurement
Accuracy
Measurement Range
Prescale
Input Signal
Max. Displayable Digits
Display Method
Display Cycle
Hysteresis
Functions
Output Types
Insulation Resistance
Noise Immunity
Dielectric Strength
Durability
Malfunction
Output
100 ~ 240 V a.c (50 - 60 Hz), 24 ~ 60 V (a.c / d.c)
Approx. 9.5 V A (220 V a.c 60 Hz), Approx. 5 W(24 V d.c)
12 V d.c 10 % 120
Mode F1 : FS 0.05 rdg 1 dig
Mode F2, F3, F4, F5, F6: FS 0.01 % rdg 1 dig
Mode F1 : 0.0003 ~ 10
Mode F2 : 0.0003 ~ 1000
Mode F3, F4, F5, F6 : 0.001s-3,200 s
Mode F7, F8, F9 : 0-4 109Count
Non-Contact Input :
Max. 10
(ON voltage: 4.5 V - 24 V, OFF voltage: 0 - 1.0 V)
Contact Input :
Max. 30 Hz
(12 V DC, able to switch the current of 2 mA sufficiently)
5 digits (0 ~ 99999)
7 Segment (Font size(W)83 mm x (H)14 mm)
0.05/0.5/1/2/4/8 sec
0 ~ 9999 (applicable only for output type)
Auto Zero Time Setting Function
Display Cycle Setting Function
Time Unit Selection Function
Parameter Lock Function
Remote/Local Conversion Function
(applicable only for communication output type)
Current Output Range Selection Function
(applicable only for current output type)
Max. Min. Peak Value 10 Steps Memory Function
Start Compensation Timer Function
Electricity Failure Compensation (applicable only for F9)
Comparative Output Function (HH, H, GO, L, LL)
Transistor Output (NPN/PNP Open Collector Output):
Comparative Alarm Output
Relay Output (HH, H, GO, L, LL)
PV Transfer Output (4 - 20 d.c): Displayed Value
Output
RS485 Communication Output : 32 channels : Displayed
Value Output, PC Setting Function)
BCD Dynamic Displayed Value Output Function
Low Speed serial Output
Above 10 (at 500 V DC mega) Between electrically
chargeable part and non-electrically chargeable part
By noise simulator, square-shaped wave noise
(pulse width 1 ) 2000 V
2000 V AC 50 Hz for 1 minute
(between AC power terminal and case,
between AC terminal and measurement input terminal)
10 - 55 Hz double amplitude width 0.75 mm
in each X YZ direction for 2 hours
10 - 55 Hz double amplitude width 0. 5 mm
in each X YZ direction for 10 minutes
Ratings
HEAD OFFICE
1381-3, Juan-Dong, Nam-Gu Incheon, Korea
TEL:(82-32)876-4697 FAX:(82-32)876-4696
MAIN PRODUCTS
- DIGITAL : Temperature Controller, Counter, Timer,Speedmeter,
Tachometer, Panel Meter, Recorder
- SENSOR : Proximity Sensor/Photo Electric Sensor,
Rotary Encoder, Optical Fiber Sensor,
Pressure Sensor
- ANALOG : Timer, Temperature Controller
Multi Pulse Meter
RP3
We appreciate you for purchasing HanYoung NUX Co.,Ltd
product. Before using the product you have purchased,
check to make sure that it is exactly what you ordered. Then,
please use it following the instructions below.
INSTRUCTION MANUAL
Input Type Setting
Caution when selecting Sensor Type
Multi Pulse Meter
DIN Size: 96 x 48 x 105.6
5 digits 1 stage
100 - 240V a.c (50 - 60 )
24 - 60 V a.c / d.c
Main output
Only Display
Relay 3 stages Output
Relay 5 stages Output
NPN Open Collector 5 Stages Output
NPN Open Collector
5 Stages Output
NPN Open Collector 5
Stages Output
NPN Open Collector 5
Stages Output
Subsidiary output
-
-
-
BCD Output
4 - 20 Current
Output
RS-
485 communication
Low Speed Serial
-
Model Name Suffix code Description
RP3
Durability
Malfunction
Operating Ambient
Temperature
Storage Temperature
Operating Ambient
Humidity
Weight
Shock
Resis
-tance
300 m/s2(approx. 30G) in each X YZ direction for 3times
100 m/s2(approx. 10G) in each X YZ direction for 3times
-10 ~ +60 (without condensation)
-20 ~ +60 (without condensation)
35 ~ 85 % RH
Approx. 220 g
Input Specification
The max input frequency is 10 when ON/OFF time is
higher than the minimum 50 .
At this time, it can be accurately measured if the duty rate
of the input pulse is 50 %.