FUNCTIONAL MODES
Sensing Mode (Visual Only) - Sensing light blinks
@ 60-second intervals (3 ashes).
Pre-Alarm Mode (Visual Only) - Alarm light blinks
@ 60-second intervals when low or no pressure
is sensed. Pre-alarm ends when the pressure is
restored within the selected delay duration or it
enters Alarm Mode.
Alarm Mode - After selected delay duration, buzzer
beeps and Red alarm light ashes, then no light
or beep for 60 seconds, then repeat until “Hush” is
pressed or system is serviced.
Service Mode - After 3 pre-alarm conditions occur
within the selected delay duration, buzzer beeps
and blue Service light ashes, then no light or
beeps for 60 seconds, then repeat until “Hush” is
pressed or system is serviced.
Hush Mode - Silences audible sound for 7 days but
visual remains as programmed; after 7 days goes
back to sensing mode, alarm mode (with sound)
or service mode (with sound).
Low Battery Mode - 1 “chirp” and simultaneous
ash @ 5-minute intervals.
Test Mode - Audible “beep” sounds and all lights
illuminate when “Test” button pressed.
Step 1: Press and hold “Hush” button for a
minimum of 5 seconds to start the time delay
selection mode.
Step 2: Keep “Hush” button held down until the
desired time delay appears (every 5 seconds) as
shown below:
Step 3: Stop depressing “Hush” button when
desired time delay appears as indicated by the
LEDs. Time delay selection mode will cycle in a
continual loop until the “Hush” button is no longer
depressed. Once the “Hush” button is no longer
depressed the time delay mode will no longer be
activated.
ACTIVATION
Prior to alarm activation, make sure both ends of
the silicone pipe connector are connected and
the radon fan is running. Remove the battery
isolator installed for shipping from the positive
pole end of the battery. The battery may have
been shipped separate from the alarm box and
in that case, the battery must be installed to
activate. Ensure battery is properly seated. Alarm
is now powered on and will begin the activation
sequence automatically.
Battery
Isolator
CALIBRATION
The ARNALM self-calibrates automatically upon
installation of the battery. After the alarm is
powered on, the system will run a 20-second
initialization to measure baseline system
operating pressure. The green sensing LED will
ash during this time. A single beep of the buzzer
will indicate the initialization is complete and the
alarm is now active. No additional calibration is
necessary.
AUDIBLE ALARM DELAY SELECTION
The ARNALM comes equipped with three optional
audible & service alarm delays. To select the
desired alarm delay duration complete the
following steps:
P/N: B2209690A 61002032 • 4.22
© 2022 AprilAire | aprilairepartners.com | 800.334.6011
1015 East Washington Ave, Madison, WI 53703
LED States Descriptions Delay durations Note
Both the “SENSING”
and the “ALARM”
LED’s are lighted up.
48 hours Default
Only the “SENSING”
LED is lighted up. 7 days
Selected by holding
down Hush button for
5 Seconds
Only the “ALARM” LED
is lighted up. 30 days
Selected by holding
“Hush” button down
for 10 seconds
FUNCTIONAL SPECIFICATIONS
Sensing Range: -0.1”WC to -20”WC
Alarm Range: ≥90% reduction of
baseline pressure
Service Condition: 3+ Pre-Alarm Trig.
@ 48 Hrs
After 48 Hours, 7 Days
or 30 Days
Low Battery Condition: <3.35 V
Hush Button: Silences alarm sound
for 7 days
Test Button: Sounds alarm /
activates lights
Dimensions: W x H x D (2.19” x
3.75” x 1.37”)
Overpressure: ±20”WC
Audible Alarm: ≈85 dba
INDICATOR LIGHT EXPLANATION
Sensing, Green Light (Flashing)
= Operating / Sensing
Alarm, Red Light (Flashing)
= Low / No Pressure (Vacuum)
Service, Blue Light (Flashing)
= Service Mode
Battery, Yellow Light (Flashing)
= Low Battery
BATTERY REPLACEMENT
1. Remove existing battery.
2. Be sure fan is operating and alarm tubing is
still connected.
3. Install new battery and make sure it is
properly seated.
4. 20-Second self-calibration operation will
then begin (refer to CALIBRATION section for
additional information).
WARRANTY INFORMATION
Subject to applicable consumer protection
legislation, AprilAire warrants that the Alarm
(model ARNALM) will be free from defective
material and workmanship for a period of (2)
years from the date of purchase. Warranty is
contingent on installation in accordance with the
instructions provided. This warranty does not apply
where repairs or alterations have been made or
attempted by others; or the unit has
been abused or misused. Warranty does not
include damage in shipment unless the damage
is due to the negligence of AprilAire. All other
warranties, expressed or written, are not valid.
To make a claim under these limited warranties,
you must return the defective item to AprilAire
with a copy of the purchase receipt. AprilAire is
not responsible for installation or removal cost
associated with this warranty.
In no case is AprilAire liable beyond the repair or
replacement of the defective product FOB AprilAire.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND
THE DESCRIPTION ON THE FACE HEREOF. THERE IS
NO WARRANTY OF MERCHANTIBILITY. ALL OTHER
WARRANTIES, EXPRESSED OR WRITTEN, ARE NOT
VALID.
For service under these warranties, contact
AprilAire for a Return Material Authorization (RMA)
number and shipping information. No returns can
be accepted without an RMA. If factory return is
required, the customer assumes all shipping costs
to and from factory.
9 10 116 7 8