Viessmann 7835343 User manual

Type
User manual

Viessmann 7835343 is an instantaneous heating water heater designed for use with Viessmann heat pumps. It provides hot water for domestic use and can be installed in a variety of locations, including residential homes, apartments, and commercial buildings. The device is equipped with a high-efficiency heat exchanger that ensures fast and efficient heating of water, and it features multiple safety systems to prevent overheating and ensure safe operation. Additionally, the Viessmann 7835343 is easy to install and maintain, making it a convenient and reliable solution for your hot water needs.

Viessmann 7835343 is an instantaneous heating water heater designed for use with Viessmann heat pumps. It provides hot water for domestic use and can be installed in a variety of locations, including residential homes, apartments, and commercial buildings. The device is equipped with a high-efficiency heat exchanger that ensures fast and efficient heating of water, and it features multiple safety systems to prevent overheating and ensure safe operation. Additionally, the Viessmann 7835343 is easy to install and maintain, making it a convenient and reliable solution for your hot water needs.

5776 411 GB 11/2015
Installation instructions
for contractors
VIESMANN
Instantaneous heating water heater
For the following heat pumps:
Type BWT/BWT-M 221.A06 to A10
Type BWT/BWT-M 241.A06 to A10
Type BWT/BWT-NC 331.A06 to A10
Type BWT 341.A06 to A10
Type AWT-AC 221.A04 bis A13, B10, B13, B16
Type AWT-AC 241.A04 bis A13, B10, B13, B16
Safety instructions
Please follow these safety instructions closely to prevent accidents
and material losses.
Safety instructions explained
Danger
This symbol warns against the
risk of injury.
!Please note
This symbol warns against the
risk of material losses and envi-
ronmental pollution.
Note
Details identified by the word "Note"
contain additional information.
Installation, commissioning, inspection,
maintenance and repairs must only be
carried out by a competent person
(heating engineer/installation contrac-
tor).
Before working on the appliance/heat-
ing system, isolate the system from the
power supply (e.g. by removing a sepa-
rate mains fuse or by means of a mains
isolator) and safeguard against unau-
thorised reconnection.
Note
In addition to the control circuit, there
may be several power circuits (e.g.
compressor, instantaneous heating
water heater).
Danger
If not all electrical circuits are
isolated, injury through electric
shock and appliance damage
may result.
Isolate all existing electrical cir-
cuits from the power supply and
safeguard against reconnection.
Repairing components that fulfil a
safety function can compromise the
safe operation of your system.
2
For replacements, use only original
spare parts supplied or approved by
Viessmann.
Opening the heat pump
1. Isolate the system from the power
supply.
Heat pump installation and
service instructions
2. Drain the system.
3. Remove front panels.
Heat pump installation and
service instructions
Safety instructions (cont.)
5776 411 GB
3
3.
2.
BK
BU
GNYE
VT
1.
Removing the instantaneous heating water heater
5776 411 GB
4
8. 6.
7. 4.
BKBU VT
12 32
22
5.
Note
The high limit safety cut-out can only be
replaced together with the instantane-
ous heating water heater.
Removing the instantaneous heating water heater (cont.)
5776 411 GB
5
2.
3.
1.
Preparing for installation
5776 411 GB
6
1. 3.
2.
5.
BKBU VT
12 3222
4.
Notes on steps 1 and 2:
Ensure the O-ring and flat gasket are
seated correctly.
Note on step 3:
Bundle the cables below the instanta-
neous heating water heater so that they
do not touch the base plate.
Installing the instantaneous heating water heater
5776 411 GB
7
6.
7.
BK
BU
GNYE
VT
8.
Installing the instantaneous heating water… (cont.)
5776 411 GB
8
1. !Please note
If the heating circuit is not
sufficiently filled with water,
the instantaneous heating
water heater will overheat.
This can damage the instan-
taneous heating water
heater.
Fill the heating system com-
pletely and vent.
2. Check for leaks.
3. Carry out a function check; see
next chapter.
4. Close the heat pump in reverse
order.
Vitocal installation and serv-
ice instructions
5. Start the heat pump.
Vitocal installation and serv-
ice instructions
Carrying out a function check
The function check ascertains whether
the set heating output of the instantane-
ous heating water heater is available
and whether the high limit safety cut-
out responds.
Note
Read through all steps before carrying
out the check.
Carrying out a check with excessively high flow temperature
1. Prevent DHW circulation in the sec-
ondary circuit via valve. The line
between heat pump and on-site
safety valve must remain open dur-
ing this test.
2. Start the instantaneous heating
water heater separately via the
heat pump control unit.
Service menu:
1. Hold down OK + å simultane-
ously for approx. 4 s.
2. "Actuator test".
3. "All actuators" set to "OFF"
4. "Inst.water. stage 1" set to
"ON"
5. "Inst.water. stage 2" set to
"ON"
Commissioning
5776 411 GB
9
Note
The secondary pump must not be
switched on.
3. Measure the current through the
instantaneous heating water
heater:
Measure the current using a clamp
ammeter (current clamp) at every
conductor (L1, L2, L3) of the power
cable for the switching module.
During heat-up, current is present;
the current is interrupted if the high
limit safety cut-out responds.
4. Observe the electricity meter for the
instantaneous heating water heater
and switch OFF other consumers in
the building if required.
Max. heating
output
Current per con-
ductor
8.8 kW approx. 13 A
5.8 kW approx. 9 A
3 kW approx. 4 A
!Please note
If the instantaneous heating
water heater overheats over
a prolonged period, this may
damage the appliance.
If the high limit safety cut-out
does not respond, switch
OFF the instantaneous heat-
ing water heater via the heat
pump control unit.
Service menu:
1. Hold down OK + å simultane-
ously for approx. 4 s.
2. "Actuator test".
3. "All actuators" set to "OFF"
Carrying out a function check (cont.)
5776 411 GB
10
Power supply
400 V/50 Hz 230 V/50 Hz
L3
A
B
L1L2 ?N N NL3
L3
L2
L1
N
?
C
ASwitching module
BJumpers
CMax. fuse rating 16 A
L3
A
B
L1L2 ?N N NL3
L1
L1
L1
N
?
C
N
N
ASwitching module
BJumpers
CMax. fuse rating 16 A
Lowering the temperature in the secondary circuit
1. Re-enable DHW circulation in the
secondary circuit.
2. Switch ON the secondary pump
separately via the heat pump con-
trol unit for approx. 60 s.
Service menu:
1. Hold down OK + å simultane-
ously for approx. 4 s.
2. "Actuator test".
3. "All actuators" set to "OFF"
4. "Secondary pump" set to "ON"
3. Isolate the system from the power
supply.
Carrying out a function check (cont.)
5776 411 GB
11
Resetting the high limit safety cut-out
A
Press reset button A.
Note
The high limit safety cut-out can only be
reset if the flow temperature lies below
78 °C.
Fault analysis
If the instantaneous heating water
heater is not heating (no current) or the
high limit safety cut-out does not
respond, this may have the following
causes:
Cause Steps to take
Airlock in the system Vent the secondary circuit.
Incorrect electrical connection
to switching module
Check connection of instantaneous heating wa-
ter heater to switching module; check switching
module power supply; see Vitocal installation
and service instructions.
Jumpers incorrectly set at the
switching module
Check jumpers; see Vitocal installation and serv-
ice instructions.
High limit safety cut-out faulty Replace the high limit safety cut-out together
with the instantaneous heating water heater.
Temperature sensor in high limit
safety cut-out faulty or capilla-
ries kinked/broken
Replace the high limit safety cut-out together
with the instantaneous heating water heater.
Instantaneous heating water
heater faulty
Replace the instantaneous heating water heater
together with the high limit safety cut-out.
Switching module for instanta-
neous heating water heater
faulty
Replace switching module for instantaneous
heating water heater.
Carrying out a function check (cont.)
5776 411 GB
12
Viessmann Limited
Hortonwood 30, Telford
Shropshire, TF1 7YP, GB
Telephone: +44 1952 675000
Fax: +44 1952 675040
Viessmann Werke GmbH & Co. KG
D-35107 Allendorf
Telephone: +49 6452 70-0
Fax: +49 6452 70-2780
www.viessmann.com
5776 411 GB Subject to technical modifications.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Viessmann 7835343 User manual

Type
User manual

Viessmann 7835343 is an instantaneous heating water heater designed for use with Viessmann heat pumps. It provides hot water for domestic use and can be installed in a variety of locations, including residential homes, apartments, and commercial buildings. The device is equipped with a high-efficiency heat exchanger that ensures fast and efficient heating of water, and it features multiple safety systems to prevent overheating and ensure safe operation. Additionally, the Viessmann 7835343 is easy to install and maintain, making it a convenient and reliable solution for your hot water needs.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI